background image

The JA-80S wireless fire detector 

 

MHS51505 

 

The JA-80S wireless fire detector  

 

This  device  is  designed  to  detect  the  presence  of  fire  inside  residential  or 

commercial buildings. It should not be installed in industrial premises. The battery-
powered  detector  has  a  built-in  local  warning  siren  combined  with  a  red  LED 
indicator. Alarm information can also be transferred 

via a wireless connection to JA-80 

OASiS systems. 

 

The JA-80S detector combines an optical smoke sensor with a heat sensor. Both 

sensors  have  their  outgoing  signals  processed  digitally,  resulting  in  higher  false 
alarm  immunity.  The  optical  sensor  works  using  a  light  diffusion  principle  and  is 
very sensitive to the presence of  large-sized particles  which are characteristic of 
dense  smokes.  By  contrast,  the  sensor  is  less  sensitive  to  small-sized  particles 
which  are  typical  of  cleanly  burning  fires.  In  particular,  the  smoke  sensor  is  not 
capable of detecting the by-products of cleanly-burning fluids such as alcohols, for 
instance.  This  deficiency  is  compensated  for  by  the  built-in  heat  sensor.  This 
sensor  provides  a  slower  reaction  when  compared  to  the  smoke  sensor,  but  is 
much better at reacting to fires with rapidly rising heat producing only a little smoke. 

Smoke / heat sensor participation is configurable by jumper-settings.  

 

Detection range, detector positioning 

The  smoke  detector  must  be  installed  so  that  any  smoke  easily  drifts  into  the 

detector,  such  as  on  the  ceiling.  It  is  suitable  for  residential  buildings,  but  not 
suitable for free spaces or an outdoor  environment. 

However, the detector is not 

suitable for installation in outdoor spaces or interiors with an extremely high ceiling 
(more  than  5  m)  where  fire  by-products  would  not  reach  the  detector  position.

 

The  detector  must  always  be  placed  in  the  section  leading  to  the  exit  of  the 
apartment (escape route), see Figure 1. If the apartment has a floor area greater 
than  150  m

2

,  an  additional  detector  is  required  in  the  apartment,  see  Fig.2. 

An  apartment  block  must  be  equipped  with  a  detector  in  each  apartment.  In 
family houses and residential flats or maisonettes a detector must also be placed 
at the highest point of common hallways or spaces (escape routes), see Fig.3. 

KITCHEN

MINIMUM SECURITY

FOR MORE SECURITY

LIVING ROOM

BEDROOM

BEDROOMS

 

 

Fig. 1 

BEDROOMS

BEDROOM

BEDROOM

LIVING ROOM

KITCHEN

MINIMUM SECURITY

FOR MORE SECURITY

 

Fig. 2 

It 

is 

recommended 

to 

place 

additional  detectors  in  rooms  where 
people  sleep  or  in  rooms  with  an 
increased  risk  of  fire,  see  Fig.2.  

 

Positioning on level ceilings

 

Place  the  detector  in  the  center  of 

the  room,  as  level  as  possible. 
Detectors  must  not  be  recessed  into 
the  ceiling  (worse  conditions  for  the 
spread  of  smoke).  Never  place  the 
detector  in  a  room  corner  (ensure  a 
distance  of  at  least  0.5  meters  from 
the corner), see Fig 4. 

BED

ROOM

KITCHEN

MINIMUM SECURITY

BED

ROOM

BED

ROOM

 

Fig. 3 

   Installation on sloping ceilings 

If the ceiling is not suitable for mounting on a level surface (e.g. a room under a 

roof ridge), the detector can be installed as in Figure 5. 

 

0.5m

CEILING

BEST LOCATION

(CENTRE OF CEILING)

ACCEPTABLE 
LOCA

TION

 

Fig. 4 

90cm

 

 

Fig. 5 

  Walls, partitions, barriers and lattice ceilings 

The JA-80S 

must not be installed closer than 0.5 m from any wall or partition

. A 

narrow  room  with  a  width  of  less  than  1.2m  requires  the  detector(s)  to  be  placed  at  a 
distance of at least one third of the room’s width away.  In the case of separating walls 
(partitions, warehouse objects) which do not reach the ceiling, the space is 

considered 

to  be  fully  separated  if  the  gap  between  the  top  of  the  separating  wall  and  the 
ceiling  does  not  exceed  0.3  m

.  A  free  space  of  at  least  0.5m  is  required  under  the 

detector.  Irregularities  in ceiling shape  which  do  not

 exceed 5% of ceiling height are 

considered insignificant 

– the ceiling can be regarded as being even and limits from 

the table are 

applicable. 

However, any irregularity (including beams) exceeding 5% 

of  the  ceiling  height  is  considered  to  be  a  wall  with  the  consequences  stated 
above

  Ventilation and air circulation 

The  detectors  must  not  be  installed  directly  by  a  fresh  air  inlet

,  e.g.  air 

conditioning vents. In the case of air being supplied through a perforated ceiling, each 
detector must be placed so that no perforation hole occurs within 0.6m of the detector. 

  Avoid installing the detector in the following locations: 

 

Places with poor air circulation (niches, corners, apexes of A-shaped roofs). 

 

Places exposed to dust, cigarette smoke or steam. 

 

Places  with  over-intense  air  circulation  (close  to  ventilators,  heat  sources  or  air 
conditioning outlets). 

  Kitchens  and  other  cooking  places  (because  steam,  smoke  or  oily 

fumes can reduce detector sensitivity). 

 

Beside lights (electrical interference can cause a false alarm)

 

 

Areas with lots of small insects

 

 

Caution: Most false alarms are due to detector misallocation 

See CEN/TS 54-14 standards for detailed installation guidelines. 

 

 

Installation 

1.  Open the detector by turning the rear cover to the left and remove the battery 
2. 

Screw the rear cover

 onto the desired location  

3. 

Set the required function

 using the jumpers

 

– see the table below 

4.  Please read the receiving device (control panel) installation manual before you connect the 

battery (remove the insulation tape) and set the control panel to enrollment mode  

5.  When the battery is connected, the detector sends a signal to connectto the system  
6.  After  installing  the  detector,  allow  approx.  20  seconds  for  stabilisation.  This 

period is indicated  by the  LED being  continuously lit  and is 

followed by an 

auto-test

. Successful performance of the auto-test is 

confirmed acoustically.

 

 

op

en

clo

se

L

IT

H

IU

M

 3

,6

V

 A

A

TEST

1

 

 

ON 

INSTANT alarm mode 

OFF 

Smoke (EN 14064)  
or heat (EN 54-5) 

OFF 

FIRE alarm mode 

OFF 

ON 

Memory ON  

ON 

Only smoke (EN 14604) 
(heat indifferent) 

OFF 

Memory OFF 

OFF 

1

1

2

3

4

 

ON

OFF

 

OFF 

Only heat (EN 54-5) 
(smoke indifferent) 

ON 

ON 

Smoke and heat 
(both simultaneously) 

ON 

 

 

Testing the detector is automatically performed up to 10 secs after 
battery insertion. New settings are saved directly afterwards. 

 

J1:

 The 

FIRE / INST

 alarm mode jumper sets the reaction of the system. FIRE 

=  alarm  is  triggered  even  if  the  system  is  disarmed  while  INST  =  alarm  is 
triggered only in an armed system. The 

FIRE / INST

 jumper only has an effect if 

the  detector  has  a  natural  reaction  assigned  to  its  address  in  the  Oasis  control 
panel.  It also has no effect when used with a UC-8x or AC-8x receiver.  

Warning:  In  the  INST  position,  while  the  system  is  disarmed,  it  is  not 
protecting  against  fire.    This  setting  also  fully  disables  the  optical  and 
acoustic indication on the detector itself. 

J2: Alarm memory:

 

If the event memory is ON at the time of alarm, alarm LED 

indication continues even if normal conditions are restored. The indication can be 
stopped by pressing the button (indication is valid only for FIRE settings).  

J3 and J4: Smoke / heat sensor participation 

Optical smoke sensor

: Smoke entry into the detector is indicated as a pre-alarm 

state  by  the  LED  flashing.  If  the  smoke  threshold  density  is  exceeded,  a  siren 
sound is generated (indication is valid only for FIRE settings). 

Heat sensor:

 indication logic is equal to that of the smoke sensor. 

Whenever the detector cover is opened, a tamper signal is sent. 

 

 

 

   Testing the detector  

The functioning of the detector can be tested by pressing and holding the test 

button (e.g. for 1 sec).  This activates the siren and the LED flashes (LED only if 

Reviews: