background image

JABLOTRON

ALARMS

a.s.

Pod

Skalkou

4567/33

46601

Jablonec

n.

Nisou

Czech

Republic

www

.jablotron.com

||

|

JA-120PW Bus combined PIR and MW motion detector

JA-120PW Bus dual PIR and MW motion detector 

1 / 2

MML51104

The JA-120PW is a bus component of the 

JABLOTRON 100 

system. It is used for the detection of human movement in building 
interiors.  The combination of PIR and microwave (MW) detection 
provides great immunity against false alarms. The detector works 
like a classic PIR detector, however when PIR detects movement in 
a guarded place, the MW part is activated and confirms the 
previous PIR activation. Only then an alarm is triggered and is sent 
to the control panel. The detector takes one position in the system 
and should be installed by a trained technician with a valid 
certificate issued by an authorised distributor.

Installation

Given the principle and detection characteristics of the MW 

detector, the best results can be achieved when the detector is 
installed in a corner of a room. No moving objects (e.g. waving 
curtains above a radiator) or animals should be in the detector’s 
field of vision. There should be no obstacles in front of the detector 
which could obstruct its view and it should not be installed near
metal objects (they could affect the MW field). It is also not possible 
to install two and more detectors in an area where MW transmitters
could affect each other.

Figure: 1 – digital bus terminals; 2 – MW part connector; 3 – production code; 

4 – PCB tab ; 5 – PIR sensor; 6 – tamper contact; 7 – cover tab; 

8 – test jumper; 9 – MW sensor; 10 – MW sensitivity settings;

1. Open the detector cover by pushing the tab (7). Avoid touching the 

PIR sensor inside (5) – you could damage it. 

2. Take out the PCB – it is held by tabs (4).  It is not necessary 

to unplug the connector (2) of the MW part.

3. Punch through the holes for the screws and the cable in the plastic 

base. The recommended detector installation height is 2.5 m above 
the floor.

4. Insert the bus cable and attach the plastic base to the wall using 

screws (vertically, with the cover tab (7) facing downwards).

Always switch the power off before connecting
the detector to the system bus.

5. Put the PCB back and connect the bus cable to the terminals 

(1). 

6. Proceed according to the control panel installation manual. Basic 

procedure:
a. When the device is powered, the yellow LED starts flashing 

repeatedly to indicate that the module has not been 
enrolled into the system.

b. Go to the 

F-Link

software, select the required position 

in the 

Devices

tab and launch enrollment mode by clicking 

on the 

Enroll

button.

c. In the next window, click on “

Scan/add new BUS devices”,

select the detector from the list and double-click on it to confirm 
your selection. You can also enrol the device by pressing the 
tamper contact in the detector (6). The yellow LED light will 
shut down after successful enrollment.

7. Close the detector cover. 

Note:

-

The detector can also be enrolled into the system by entering its 
serial number (5) in the F-Link program. The serial number is on 
a label with a bar code which is placed inside the detector (3).
All numbers shall be entered (example: 1400-00-0000-0001).

-

If you want to remove the detector from the system, delete it from 
its position in the control panel.

Detector internal settings

The detector properties can be set in the 

Devices

tab of the 

F-Link software. Use the 

Internal settings

button, on the same 

position as the detector, to open a dialog window where you can 
set following (factory settings are marked with*):

Activation indicated by LED:

disable* / enable

movement indication 

by a red LED. Indication always works in Service mode 

PIR immunity level:

determines a level of immunity to false alarms. 

Standard*

combines basic immunity with a fast sensor reaction.

Increased

has stronger immunity with a slower reaction time.

MW immunity level:

determines the level of analysis performed by 

the MW motion detector. 

Standard*

combines basic immunity with 

a fast sensor reaction.

Increased

has stronger immunity and 

provides a slower reaction time.

Detector Testing

Check the functioning of both sensors using a jumper (8) when 

the control panel is in 

Service mode. Warning: 

Confirmation of 

activation by the MW detector can’t be carried out when the control 
panel is unset therefore it’s not possible to fully test its function and 
configuration.

The PIR detector

is equipped with a 110°/12m lens. Coverage –

see Fig 2. Check the coverage with the jumper (8) in the 

“PIR”

position. Movement is indicated by a red LED.

Fig 2: Coverage characteristics can be changed by using an alternative lens:

JS-7904

Designed for long corridors - with a working range of up 
to 20m

Increased immunity cannot be used with this lens!

JS-7910

Equipped only with the upper beam covering 120 
degrees / 12 m and doesn’t cover the floor (can ignore 
the movement of small pets on the floor)

JS-7902

Vertical curtain – it does not cover an area but creates a 
detection wall (can be used to create a barrier and 
report its breach)

After changing a lens, it’s necessary to test 

whether the detector sufficiently covers the area.

The MW detector

reacts to movement from in a 1 m to 15 m

range. The detection range is set by a trimmer (10). In some cases, 
the detector can detect movement of non-metal materials behind 
fixed obstacles (behind a thin wall, a door, glass, flowing water in 
plastic pipes etc.).

It is recommended to set the MW detection range the way 

it won’t exceed the field of view of PIR. Testing is carried out by 
placing the jumper (8) in the MW position. MW activation 
is indicated by a red LED. Given the principle of MW, its coverage 
characteristics may significantly differ depending on a size, shape 
and facilities of the room in which the detector has been installed.
Especially regarding metal surfaces which cause reflection 
or shielding of the signal generated by MW.

During installation, it’s always necessary to test

whether the detector sufficiently covers the area.

Reviews: