jablotron JA-111ST Manual Download Page 2

JA-111ST Bus combined smoke and heat detector

JA-111ST  Bus combined smoke and heat detector

2 / 2

MLW55307

Proceed according to the control panel installation manual

.

Basic procedure:

a. Go to the 

F-Link

program, select the required position in the 

Detectors

window and launch enrollment mode by clicking on the 

Enroll option.

b. Insert the detector into the plastic base. The detector can be 

inserted in the base in one position only. It is marked with arrows 
(4). Close the detector by turning it clockwise (2). The tamper 
contact inside the detector is thus triggered and the detector is 
enrolled. The yellow LED indicator goes off. When inserting the 
detector, bear in mind that the connecting wires must not restrain 
the functioning of the testing buttons.

Warning:

Detector insertion into the base is blocked unless all 3 

batteries are inserted!

(only if EN 14604 compliance is required).

The mounting base must not be replaced by bases meant for 

detectors without the test button consisting of pressing the body 
of the detector.

Note:

The detector can also be enrolled into the system by entering 

its production code (5) in the F-Link program (or using a bar code 
scanner). All numbers stated under the bar code shall be entered 
(1400-00-0000-0001).

Detector setting

The detector properties can be set in the Detectors window in the 

F-Link

program:

The 

Reaction

option in the 

Detectors

window allows you to set the 

type of system reaction to the activation of the enrolled detector.

To set the detector properties use the 

internal settings

access 

button. This opens a window where can be set internal setting and 
behavior of the detector.

Alarm memory in the stand-alone mode 

determines whether the 

detector will indicate alarm memory with a LED indicator even when the 
detector is in a stand-alone mode.

Reaction 

enables setting which impulses the detector should react to:

Smoke

EN 14604, EN 54-7

Temperature

EN 54-5

Smoke or temperature

EN 14604, EN 54-5
EN 54-7

Smoke and temperature at once

Acoustic signalling

sets the time for which the detector keeps 

chirping (applies in the system detector mode only). When in the stand-
alone mode, the detector keeps chirping for the whole duration of the 
alarm (smoke in the room or high temperature). The chirping can be 
terminated by pressing the detector against the base.

Batteryless operation

. When this parameter is set, the detector 

works only as a control panel-powered system detector and the low 
battery detection is disabled. 

When batteryless detector operation is required (EN 54-x), the 

blocking mechanisms preventing insertion of the detector without 
inserted batteries should be removed.

The detector does not comply with EN 14604 with this 

setting.

Thermal class EN54-5

determines the reaction speed of the 

detector to temperature increases.
A1  – A fast reaction to temperature changes. It has to react within 

1 min 40 sec when the temperature reaches 30 °C/s. 

A2  – A slow reaction to temperature changes. It has to react within 

2 min 25 sec when the temperature reaches 30 °C/s. These 
detector settings have a high immunity to false alarms in 
problematical installations.

Fire alarm

Fire alarm 

is signalled both acoustically and optically.

When the conditions for fire alarm triggering are met (smoke is 

detected in the room, the alarm temperature is reached, or both 
conditions are met), the detector signals the danger by sounding the
siren and quickly flashing of the LED indicator (3). The alarm 
information is concurrently sent to the system control panel.

Silencing the siren during an alarm:

The siren can be silenced by 

pressing the detector body against the base. The siren is inactive for 10 
minutes. If the detector still detects smoke or heat after this time, the 
siren is activated again.

When the need arises (e.g. in the case of a detector failure), it is 

possible to postpone siren reactivation by up to 12 hours. This can be 

done by pressing the detector again for 5 s after silencing the siren. 
When the detector chirps, you have to release the pressure within 1 s.
The switchover to the postponed siren mode is confirmed with 5 chirps. 
The detector LED flashes all the time during the postponement. 

Alarm memory: 

LED indication continues flashing slowly even when 

the smoke clears or when the temperature decreases. The indication 
lasts 24 hours unless it is terminated by pressing the detector body.

Tamper alarm:

When the detector cover is opened, the detector 

sends a tamper signal to the control panel.

Detector testing and maintenance

The detector should be tested at least once per month.

To test the 

detector press the detectors body against the base and wait until a LED 
indicator switches on. The LED flashing signals switchover to the testing 
mode. The LED is flashes for the whole duration of the test. When the 
test is complete, the LED switches off. The detector then signals the result. If 
the detector beeps once, the test has been done successfully. If a 
failure is discovered, the LED flashes and beeps three times. If the 
battery is low, there is no acoustic signalling but just one flash when the 
test is completed. 

The complete functioning of the optical part of the detector can be 

tested with a testing spray (e.g. SD-TESTER). The heat sensor can be 
tested with heated air (e.g. with a hair dryer). If the control panel is not 
in the SERVICE mode, a fire alarm is triggered.

Warning: never test the detector with fire.

Fault indication

The detector checks its functioning. If it discovers a fault, it chirps and 

flashes the LED three times and then flashes shortly three times every 
30 s.

A detector test can be carried out when a fault is signalled, see paragraph 

Detector testing and maintenance. When the detector is fixed the detector 
beeps once briefly.

If you have not managed to fix the fault, the detector must be sent to a 

service centre.

Battery replacement

The detector checks the battery status if used and if the batteries are 

running low, the detector signals that they need replacing by short 
flashes repeated every 30 s. The information is also sent to the control 
panel. Replace the batteries as soon as possible. Always replace all 
three batteries of the same type and manufacturer.

Use only high-quality 1.5 V AA alkaline batteries.

Do not throw used batteries into ordinary household waste. 

Deposit of them at authorized collection points.

Removal of the detector from the system

The system reports any possible detector loss. If you have removed it 

on purpose, you also have to erase it from the correspondent address in 
the control panel memory.

Technical specifications

Power

9 – 15 V DC/3.5 mA (150 mA during an alarm)

3 pcs of alkaline batteries type LR6 (AA) 1.5 V

Please note: Batteries are not included

Typical lifetime 

approx. 3 years

Smoke detection

optical light scattering

Smoke detector sensitivity

m = 0,11 

y

0,13 dB/m 

pursuant to EN 14604, EN 54-7

Heat detection

class A1 according to EN 54-5

Alarm temperature

+ 60 °C to +65 °C

Operating temperature range

-10 °C to +65 °C

Dimensions, weight

diameter 126 mm, height 52 mm, 150 g

Conformity 

EN 50130-4, EN 55022

          

14

1293-CPR-0396

1293

JABLOTRON ALARMS a.s. hereby declares that the JA-111ST 
is in a compliance with the relevant Union harmonisation legislation: 
Directives No: 2014/30/EU, 2011/65/EU. The original of the 
conformity assessment can be found at www.jablotron.com -
Section Downloads.

Note:

Although this product does not contain any harmful 

materials we suggest you return the product to the dealer 
or directly to the producer after use.

Reviews: