jablotron HESTIA-915 Installation Manual Download Page 10

INSTALLER PROGRAMMING WORK SHEET:

  

Press 

[

] [6] [Installer Code]

 to enter installer programming level. The

 [#]

 must be pressed to exit programming level. Fill 

out the following tables and use them as guide when programming.

 

 

[0] [xxxx] New Installer Code

 

default programmed 

1010 

0   _  _  _  _

 

 

[1] [xyy] Zone definition 

[yy] - zone type 

(alarm) 

 00 - Off 

(none) 

 01 - 24Hr. 

(intruder) 

 02 - Instant 

(intruder) 

 03 - Delay 

(intruder) 

 04 - Next delay 

(intruder) 

 05 - 24Hr. silent 

(panic) 

 06 - Instant silent 

(panic) 

 07 - Delay silent 

(panic) 

 08 - Interior instant 

(intruder) 

 09 - Next delay interior  (intruder) 
 10 - Fire 

(fire) 

 11 - 24Hr. delay silent  (panic) 
 12 - Warning 24Hr. 

(warning) 

 13 - Warning instant 

(warning) 

Note: loop 6 can work as arming control 
[411]

 

zone 

[x] 

default 

programmed 

enter [yy]

delay 

 

1   1 _  _

next del. in. 

 

1   2 _  _

interior inst. 

 

1   3 _  _

instant 

 

1   4 _  _

instant 

 

1   5 _  _

instant 

 

1   6 _  _

 

[2] [xms] System Times 

 
[m] = 

minutes (from 0 to 9)

 

[s]  = 

x10 seconds (from 0 to 5)

 

examples:  
[ms] = 32 = 3min. and 20sec. 
[ms] = 04 = 40sec. 

Note: if  [ms] = 00  = 5sec

 

[x]   time 

default 

programmed 

enter [ms] 

 0  

 entry

 

20 sec. 

 

2   0 _  _

 1   

exit

 

40 sec. 

 

2   1 _  _

 2   

alarm

 

3 min. 

 

2   2 _  _

 

[y] Ext. Siren   Relay   Int. Siren

 

 0      OFF          OFF      OFF 
 1      ON            OFF      OFF 
 2      OFF          ON        OFF 
 3      ON            ON        OFF 
 4      OFF          OFF       ON 
 5      ON            OFF       ON 
 6      OFF          ON         ON 
 7      ON            ON         ON 
For Panic alarm [y] can only be 0 or 2 
Panic alarm always activates Panic o. 
Fire alarm aiways activates Fire out. 
 

ES

 = Ext. Siren;  

IS

 = Int. Siren 

[3] [xy] Alarm outputs definition 

[x] 

alarm

 

default otputs 

programmed

enter [y]

technic.

 

Relay 

 

3   0 _

 

fire

 

ES, IS, Relay, Fire

 

3   1 _

 

intruder

 

ES, IS, Relay 

 

3   2 _

 

3

 panic

 

Panic 

 

3   3 _

 

 

[4] [xy] System option functions 

Chirp sounds: 

 0=buzzer only, 1=IS, 

                          2=ES, 3=IS & ES   

L6 arm control:

 0=OFF (L6 = zone) 

                           1=ON (L6=arming)

 

Attempts number: 

can be from 0 to 9 

                           

 0=without  any limit 

Quick arming: 

0=disabled, 1=enabled 

Auto At Home: 

0=disabled, 1=enabled 

Silent if. sb in: 0=adible (IS &rel. can work) 
                       1=silent (IS & rel.disabled) 

 

Examples: 
401 = Chirp Sounds by Internal siren 
411 = L6 works as external arming input 
431 = Quick arming enabled

 

[x]

  function  

default  programmed

enter [y]  

0  

chirp sounds

 

buzzer only

 

 

4   0 _

 L6 arm control

 

OFF 

 

4   1 _

2  

attempts no.

 

 

4   2 _

3  

quick arming

 

OFF 

 

4   3 _

4  

auto AT HOME

 

OFF 

 

4   4 _

5

   

silent if sb. in

 

OFF 

 

4   5 _

 

[5] [xy] Testing of outputs 

 

If you also install a device with 

optional outputs use [51y] 
commands for their testing. See the 
manual you got with the optional 
device. 

To activate 

enter 

Relay 

5   0 0

 

Ext. Siren 

5   0 1

 

Panic 

5   0 2

 

Fire 

5   0 3

 

Arm 

5   0 4

 

Int. Siren 

5   0 5

 

press

 ∗

 to switch the output off 

 

H-915  installation manual   

11/10 

TBT502 01 

Summary of Contents for HESTIA-915

Page 1: ...Security Alarm Control Panel HESTIA 915 installation manual...

Page 2: ...ired 12V from 1 2Ah to 40Ah stand by consumption 25mA back up power output 12V max 500mA inputs eight loops FIRE TAMPER and 6 fully programmable loops type of loops balanced with End Of Line resistor...

Page 3: ...put is also triggered if normally closed contacts wired in series with EOL resistor are opened see the wiring diagram The Fire alarm is activated if a detector connected to a FIRE input is triggered T...

Page 4: ...5 can be used connect all of them in parallel Check carefully that you have connected corresponding wires before you turn on the power to the control panel The built in keypad on the H 915C model is c...

Page 5: ...n was enabled in the installer programming level If quick arming is enabled the H 915 can be AT HOME armed by entering only the 9 command DISARMING Enter a valid access code to disarm If the chime jum...

Page 6: ...tically in the moment when used once for arming NOTE If you press 9 in user programming level the H 915 control panel will send information about events history to the special serial interface printer...

Page 7: ...f the premises is entered without coming through a delay entrance and a next delay loop is triggered an immediate intruder alarm will be generated 05 24Hr silent loop operates as the type 01 but it tr...

Page 8: ...med by both sirens The y can only be from 0 to 3 4 1y External arming control with loop 6 input If y 0 zone input 6 will work as programmed in section 1 If y 1 than zone input works as input for exter...

Page 9: ...will start in the alarm condition when the power is switch on again If there is any reason to switch the power completely off for example when you want to extend the system with an optional device we...

Page 10: ...3 ON ON OFF 4 OFF OFF ON 5 ON OFF ON 6 OFF ON ON 7 ON ON ON For Panic alarm y can only be 0 or 2 Panic alarm always activates Panic o Fire alarm aiways activates Fire out ES Ext Siren IS Int Siren 3...

Page 11: ...USER S OPERATION GUIDE OF H 915 Zone location No protected area zone type 1 2 3 4 5 6 Tamper Fire Exit Entry Alarm if troubles call your installer phone H 915 installation manual 11 11 TBT502 01...

Page 12: ...H 915 installation manual 11 12 TBT502 01...

Reviews: