The AC-160-DIN Wireless multipurpose relay for DIN rails 

The AC-160-DIN wireless multipurpose relay for DIN rails 

2 / 2 

MLZ54301 

published  for  downloading,  file  type *.fwp).  If  Automatic  updates  
are enabled, the FW pack will be selected automatically. 

7.  F-Link shows a window with a device listing, select USB. 
8.  Then  press 

OK 

and  perform  the  upgrade  for  the  selected  device 

(the relay). 

9.  Disconnect the cable and attach the relay front cover. 
10.  Check the settings via the 

F-Link

 software

.

 

Note:

 

The MicroUSB cable (required for FW upgrade) is not supplied 

with the MFR.

 

Stand-alone mode 

Up  to  64  one-way  communicating  detectors  of  the  JA-15x  series 

and keyfobs  of  the  JA-15xJ  MS  and  JA-16xJ  series  can  be  enrolled  
in the MFR. EnrollmentEnrolment and setup of the detector and keyfob 
modes  is  done  by  the  Learn/Set  button  (3).  The  relay  can  recognize  
3 lengths of pressing: 

Short press   < 3 s 

Turns the relay ON or scrolls the menu 

Long press  > 3 s < 6 s 

Enters the menu or sends an enrollment 
signal 

Very long press 6 s 

Exits the menu or confirms the timer 

Enrolling the detectors and keyfobs

 

First  of  all  select  the  mode  in  which  the  device  should  be  operated 

and then enroll it. 

Procedure: 

1.  Perform  a  long  press  of  the  Learn/Set  button  (3)  until  the  yellow 

LED starts flashing. 

2. 

When  you  release  the  button  the  relay  is  ready  to  receive  
an enrolling signal from a device, confirmed by permanent lighting 
of the yellow LED and a flashing red LED. The number of flashes 
determines the operation mode to which the device will be enrolled. 
Operation  mode  selection  is  done  by  repeatedly  briefly  pressing  
the button.

 

No. of red LED flashes. 

Mode 

1x  *  *  *  * 

Copy (extended  

with detectors) 

Switch on /Switch off  

(with keyfobs) 

2x  **  **  **  ** 

Impulse 

3x  ***  ***  ***   

Change status 

4x  ****  **** 

Always switches off 

5x  *****  ***** 

Block 

1x longer lit, short pause 

Mode for deleting detectors 

Note:

 

Extended copy and Impulse – minimum switching time is 1s 

 

3.  Enrolling a detector - Insert the batteries into the detector – it sends 

an enrollment signal. 

4.  Enrolling  a  keyfob  –  long  press  of  a  selected  button  –  The  MFR  

will  react  to  this  button  being  pressed.  Each  button  can  be 
individually  enrolled  to  the  MFR’s  positions.  A  4-buttton  keyfob  
can  take  4  MFR  positions  with  different  relay  switching  modes. 
Enrolling by pressing a pair of buttons at the same time is possible; 

5.  Enrolling  is  confirmed  by  alternate  flashing  of  the  LED  in  red  

and green. 

6.  When the enrollment procedure has been done correctly, the MFR 

goes  back  to  its  normal  operating  mode  –  the  green  LED  is  ON.  
If  you  want  to  enroll  the  next  device  you  must  repeat  the  whole 
enrollment procedure. 

Erasing a device

 

1.  Perform a long press of the Learn/Set button (3) until the yellow 

LED starts flashing. Now release the button and the yellow LED 
indicates permanently and the red LED flashes. 

2.  By  repeated  pressing  (5x)  of  the  button  (3)  select  the  mode 

when the red LED lights and regularly fades out. 

3.  Insert  the  batteries  into  the  detector  or  long-press  a  keyfob 

button which is to be erased from the MFR. 

4.  Erasing  a  device  from  the  MFR  is  confirmed  by  alternate 

flashing of the red / green LED indicators. 

5.  When the erasing procedure has been finished, the relay goes 

back to its normal operating mode. 

Note: Erasing is also possible by deleting a production code 
in the internal settings of the MFR located in the F-

/LQNVRIWZDUH

 

Common timer setup 

1.  Perform  a  long  press  of  the  Learn/Set  button  (3)  until  the  yellow 

LED  starts  flashing.  Now  release  the  button.  The  yellow  LED 
indicates permanently and the red LED flashes. 

2.  Perform  a  long  press  of  the  Learn/Set  button  (3)  again  until  

the  flashing  of  the  red  LED  changes  to  permanent  lighting  of  the 
green LED. 

3.  When  the  button  is  released  the  green  LED  will  start  flashing.  

The  number  of  flashes  determines  the  pre-set  period  
of the Common timer. 
By  repeated  pressing  of  the  button  (1)  select  the  required  time  
of  the  common  timer.  The  table  shows  5  default  options.  
Those values cannot be changed in stand-alone mode. When it is 
pre-set  by  F-Link  to  a  different  time  (not  to  predefined/default 
values), the green LED lights and regularly fades away. 

No. of green LED flashes. 

Timer period 

1x  *  *  *  * 

1 s (default) 

2x  **  **  **  ** 

1 min 

3x  ***  ***  ***   

3 min 

4x  ****  **** 

15 min 

5x  *****  ***** 

30 min 

1x longer lit, short pause 

Different settings (via F-Link) 

 

4.  Confirm the selected value by pressing the button for more than 6 s 

until the red/green LED indicators start flashing. Settings are saved. 

Note

:  No  activity  for  longer  than  1  minute  terminates  

the  setup/enrollment  mode,  saves  the  changes  and  goes  to  normal 
operating mode.  

Operation status - optical indication 

LED indication 

Mode 

ERR 

(yellow) 

OFF 

Everything OK 

ON 

(stand-alone mode) 

Setting 

ON 

(operation with control 

panel) 

Loss of 

communication 

or 

Internal settings 

entered 

Flashes 1/s 

Low battery in one of 

the devices 

RELAY 

(red/green)

 

RED LED ON 

Relay ON 

GREEN LED ON 

Relay OFF 

GREEN flashes 4/1 

Blocking when OFF 

GREEN/RED 

 flashes 4/1 

Blocking when ON 

Resetting the relay  

A  full  relay  reset  and  complete  erasing  of  all  enrolled  devices  

is performed by pressing the button for more than 6 s (3). It is indicated 
with  the  alternate  flashing  of  red/green  of  the  ‘RELAY’  LED 
simultaneously with a permanently lit ‘ERR’ LED. The Learn/Set button 
must  be  then  released  within  3 s  and  then  (also  within  3  s)  briefly 
pressed again. The MFR reset is confirmed by quick alternate flashing 
in red/green of the ‘RELAY’ LED with a yellow ‘ERR’ LED. After this only 
the green and yellow LED stays lit. Resetting doesn´t erase an enrolled 
control panel which is currently in service mode (in this case the yellow 
LED will not be lit). 

Technical specifications 

Operational power 

230 V/50 Hz 

Own power consumption for 230 V AC (min / max)  

0.5 W/1.7 W 

Communication band 

868.1 MHz, Jablotron protocol 

Antenna 

Internal/optional external antenna type AN-868 

MFR Contact rating - protection class II: 

 

- Maximum switching voltage 

250 V AC 

5HVLVWLYHORDGFRVij 

 

max.16 A 

,QGXFWLYHFDSDFLWLYHORDGFRVij 

 

max.

 

8 A 

- Halogen lights 

max. 1000 W 

- Minimum switching DC power 

0.5 W 

Recommended connection wires: 

max. 2 x 1.5 mm

; max. 1 x 2.5 mm

2

 

IP covering 

IP-20 (according to EN 65529), IP-40 (with a front panel) 

Dimensions 

18 x 90 x 64 mm 

Weight 

65 g 

Operational temperature range 

-10 to + 40°C,  

 

relative humidity 75% no condensation 

Complies with   

ETSI EN 300 220-1, EN 50130-4 

 

 

EN 55022, EN 60950-1, EN 50581 

Can be operated to 

ERC REC 70-03 

 

JABLOTRON ALARMS a.s. hereby declares that the AC-160-
DIN is in a compliance with the relevant Union harmonisation 
legislation: Directives No: 2014/53/EU, 2014/35/EU, 
2014/30/EU, 2011/65/EU. The original of the conformity 
assessment can be found at www.jablotron.com - Technical 
Support section.

 

 

Note: Although this product does not contain any harmful 
materials we suggest you return the product to the dealer  
or directly to the producer after use

 