background image

big plug

small plug

Max. cable diameter

8mm -10,5mm

5mm - 6mm

Type

DIN EN175301-803 Form A

Industrial connector type C

AC/DC

Steuerung 2 Punkt  

control 2 point

Anschluss  

connection

DC

Interne Funktion  

internal function

Versorgungsstecker

supply plug

Endlagenstecker

end position plug

Regelung 3 Punkt  

regulation 3 point

Steuerung 2 Draht  

control 2 wires

J+J

Manual J4C S20-S300

-PAGE 2-

Commissioning

Mounting on the valve

Taking the medium and pressure into account, as well as after multiplication with a sufficient safety factor, the torque of the valve 

may never exceed the rated torque of the drive. Before mounting, any end stops of the valve must be removed.

If the shaft or flange pattern of the valve can not be directly mounted with the drive, corresponding adaptions are needed.

The shaft of the valve may never be longer than the insertion depth of the actuators output.

The assembly can be done with grub screws, ensuring a sufficient screwing depth in the drive.

In addition, care must be taken during assembly to align the valve and actuator.

In this case, it can be helpful to bring the alignment by using the manual override (see manual override).

Depending on the valve, the working angle may need to be adjusted (see adjustment of cam system).

Electric connection

The connection may only be made by electrically trained specialist personnel.

The general electrical safety rules and VDE regulations apply.

The connection is made with the supplied industrial connectors. While wiring always take care of a correct cable diameter,

otherwise the degree of protection IP67 is not guaranteed.

Each plug is fastened to the quarter-turn actuator with a screw, it must not be over-tightened.
J+J quarter-turn actuators must be connected with a single phase and controlled via relays or switches.

Depending on requirements, three different wiring methods without reconfiguration are available for the control.

Due to the internal power supply, the actuator can be viewed as a capacitive load.
Accordingly, an external fuse with appropriate 

trigger characteristics (e.g. circuit breaker type D)

 must be provided.

Switching contacts should have a 

suitable contact material (e.g. silver-tin oxide AgSnO)

 or a zero voltage switch.

No external consumers should be connected parallel to the actuator.

AC/DC

Steuerung 2 Punkt  

control 2 point

Anschluss  

connection

DC

Interne Funktion  

internal function

Versorgungsstecker

supply plug

Endlagenstecker

end position plug

Regelung 3 Punkt  

regulation 3 point

Steuerung 2 Draht  

control 2 wires

9

8

     

10

4

1

2

3

5

6

7

1  Sealing

2  Terminal block

3  Clamp

4  Housing

5  Sealing ring

6  Clamp ring

7  screw-in pod

8  Washer

9  Screw

10  Sealing washer

Connection plugs

A  Supply plug

B  Option

C  End position plug

A

B

C

1

2

3

4

5

6

7

9

8

10