Chapter 5 Specifications
25
Chapter 5 Specifications
5.1 Specifications
Basic specifications
SS-663
SS-664
SS-665
Sensitivity [mV/A]
50
20
10
Peak current [kA]
120
300
600
Peak di/dt [kA/
μ
s] 8
20
40
Absolute maximum di/dt
Peak [kA/
μ
s] 80
80
80
RMS [kA/
μ
s] 3
3
3
Frequency bandwidth
f
L
to 30MHz [-3dB], f
L
:
Low frequency cutoff
Low frequency cutoff
[Hz]
65 32
17
Noise [mV rms]
3.5
2.5
2.0
Sensitivity accuracy
±2%
At the center of the coil loop with sensor part temperature of
−
10
C to
+70
C
* Add an error of ±250 ppm/
C when the temperature is
−
10
C or less or
+70
C or more.
Output
Maximum voltage range: ±6 V (load
≧
100 k
Ω
)
* Output becomes ±2V and sensitivity becomes about the half
for 50
Ω
load.
Connector
BNC
Linearity
±0.05 % of full scale
Zero point
adjustment range
±300 mV or more
Sensor part
Coil length
84 mm ± 4 mm
Wire rod diameter
at coil part
1.0 mm (Max)
Maximum rating
voltage between
ground
600Vpeak
Sensor cable length
1.5 m ± 50 mm
Operating
temperature range
-40
℃
to 125
℃
(including sensor cable
)
General specification
Dimensions
Approx. 80 (W) × 165 (H) × 35 (D) mm(excluding protrusions)
Weight
Approx.
0.37 kg
Power supply
Four AA dry batteries
Note 1
or dedicated AC adaptor (option)
Battery life
Note2
Approx. 18 hours (when alkaline batteries are used)
Accessories
BNC cable (1), Adjustment Screwdriver (1), AA dry battery (4),
Instruction Manual (1), and hard case (1)
Summary of Contents for SS-663
Page 1: ...Rogowski Coil Current Probe SS 663 664 665 Instruction Manual...
Page 2: ...2018 IWATSU ELECTRIC CO LTD All rights reserved...
Page 4: ...Memo...
Page 16: ...Chapter 2 Names and Functions of Parts 12 Chapter 2 Names and Functions 2 1 Main Unit...
Page 31: ...Chapter 5 Specifications 27 5 2 Appearance 1 Main Unit Unit mm...
Page 32: ...Chapter 5 Specifications 28 2 Rogowski Coil Sensor Unit mm...
Page 34: ...SS 663 664 665...