Installation
AirModule –6 720 813 268(2014/10)
17
7.11
Connecting the heat pump module to the heat pump
Insulate pipes and connections against condensation if cooling is to be
used.
▶ Select pipe size according to table 11.
▶ Connect the return to the heat pump [4] to the heat transfer medium
▶ Connect the flow from the heat pump [3] to the heat transfer medium
Fig. 13 Heat pump connections heat pump module
[1]
Heat transfer medium out (to the heat pump)
[2]
Heat transfer medium in (from the heat pump)
[3]
Flow from heat pump
[4]
Return to heat pump
6 720 809 156-14.1I
<50V
230V
/
400V
<50V
230V
/
400V
1
2
4
3
Heat pump
output (kW)
Heat
transfer
fluid delta
(K)
Nominal flow
(L/s)
Maximum pressure
drop (kPa)
1)
1) For pipes and components between the heat pump module (indoor unit) and heat pump (outdoor unit).
AX20
inner-Ø 15 (mm)
AX25
inner-Ø 18 (mm)
AX32
inner-Ø 26 (mm)
AX40
inner-Ø 33 (mm)
Maximum pipe length PEX (m)
5
5
0.32
68
28
60
7
5
0.33
55
14
33
60
9
5
0.43
40
8
21
60
13
5
0.62
56
14
60
60
17
5
0.81
18
15
60
Table 11 Pipe dimensions and max. pipe length for connection of heat pump to heat pump module