GSXP12HRN
1 – 1
GSXP12HRN
Service Manual
CHAPTER 1.
SPECIFICATION
[1] SPECIFICATION
1. GS-XP12HR-N / AE-X12FR-N
NOTE: The condition of star "
✩
" marked item are ‘ISO5151’ : 1994(E), condition T1, Voltage 230V.
MODEL
INDOOR UNIT
OUTDOOR UNIT
ITEMS
GS-XP12HR-N
AE-X12FR-N
Cooling capacity (Min. ~ Max.) kW
3.5 (0.9 - 4.0)
Heating capacity (Min. ~ Max.) kW
4.2 (0.9 - 6.0)
Moisture removal (at cooling)
Liters/h
0.9
Electrical data
Phase
Single
Rated frequency
Hz
50
Rated voltage
V
230
Rated current
✩
(Min - Max.)
Cool
A
4.5 (1.2 - 6.0)
Heat
A
4.7 (1.3 - 7.0)
Rated input
✩
(Min - Max.)
Cool
W
900 (200 - 1300)
Heat
W
970(180 - 1800)
Power factor
✩
Cool %
87
Heat %
90
Compressor
Type
Hermetically sealed rotary type
Model 5RS092XDF
Oil charge
RB68A or FREOL ALPHA68M 320ml
Refrigerant system
Evaporator
Louver Fin and Grooved tube type
Condenser
Corrugate Fin and Grooved tube type
Control Expansion
valve
Refrigerant (R410A)
1000g
De-lce system
Micro computer controled reversed systems
Noise level (at cooling)
High
dB(A)
43
49
Low
dB(A)
35
-
Soft
dB(A)
29
-
Fan system
Drive
Direct drive
Air flow quantity (at cooling)
High
m
3
/min.
12.9
30.2
Low
m
3
/min.
10.3
–
Soft
m
3
/min.
7.3
–
Fan
Centrifugal fan
Propeller fan
Connections
Refrigerant coupling
Flare type
Refrigerant tube size Gas, Liquid
1/2", 1/4"
Drain piping mm
O.D
φ
20
Others
Safety device
Compressor: Thermal protector
Fan motors: Thermal fuse
Fuse, Micro computer control
Air filters
Polypropylene net (Washable)
Net dimensions
Width
mm
1025
780
Height
mm
212
540
Depth
mm
680
265
Net weight
kg
31
37