It is recommended to purge all the piping which have to be connected to the
boiler to ensure that they do not contain any foreign bodies such as fragments
of gaskets, welding slag or anything else which might damage the generator
equipment before finally connecting it to the boiler!
ELECTRIC PANEL
The control switches with relevant pilot lamps are installed on this panel.
1 - Main switch in position “1” supplies voltage to the panel.
2 - The green pilot lamp signals that the panel is live.
3 - The red lamps signal defects in working of various circuits.
4 - The main switch in position “0” cuts off the current to the panel.
5 - The main switch in position “1” starts up the boiler.
TROUBLES SIGNALLED BY THE PANEL LAMPS AND REMEDIES TO BE
TAKEN
1 - Feed water block lights out
The burner goes out - lights up on the panel - check whether there is water in
the service tank.
Pump defect: check the capacity in liters/minute - if capacity is insufficient
remove the pump bell - check gaskets and change them if necessary.
2 - Steam block lights out
The burner goes out, due to the lack of fuel delivery.
3 - Chimney block lights out
This indicates that the boiler is dirty on the fume side.