Continuous product development at IV Produkt may give rise to specification changes without notice.

Flexomix 060-950

DU14.F.110907.05.EN   

Fan, power supply and rated current 

The power supply and rated current can be read from the 
fan rating plate (see example below) or the relevant values 
can be read from the table below. 

Typ

Type

Tyyppi

Typ

0.42

290-2920

K-faktor

K-factor

K-kerroin

Wsp. K
Max. temp

Max. temp

Max. lämp.

Maks. temp

51.43

50

°C

Q =

× p (m³/s)

1

K

kW

r/m

230

V

A

2.8

Min./Max. frekvens Hz

Min./Max. frequency Hz

Min./Max. taajuusalue Hz

Min./Maks. częstotliwość Hz

025-EC-0042

Fläkt / Fan / Puhallin / Wentylator

Tillv. månad

Manuf. month

Valmistus kk

Miesiąc

1105

Art. Nr. 19121-1301_01

Y Y M M

Typical fan rating plate

 

N.B! The fans can be of different sizes/variants. Read the 
rating plate of both the supply air and the extract air fan.

Motor type 025-EC 1×230V 0,42 kW

TK/NC

TK/COM

0-10V

GND

L

N

PE

+10V

+

ALARM (OPENS 

IN EVENT OF LARM)

CONTROL

0-10V=

POWER SUPPLY

1×230V~50Hz

Motor type EC 1×230V (all excl.  

025-EC 1×230V 0,42 kW)

+

NO

COM

GND

Ain1 U

0-10V

L

N

NC

PE

POWER SUPPLY

1×230V~50Hz

CONTROL

0-10V=

ALARM
(CLOSES BETWEEN
 COM-NO IN EVENT
 OF ALARM)

Motor type EC 3×400V

+

NO

COM

GND

Ain1 U

0-10V

L1
L2
L3

NC

PE

CONTROL

0-10V=

POWER SUPPLY

3×400V~50Hz

ALARM
(CLOSES BETWEEN
 COM-NO IN EVENT
 OF ALARM)

Motor type I2F1 3×400V

+

X102

X101

1
2

8
2

6

L3

L1
L2

3

4

PE

ALARM
(CLOSES BETWEEN
 1-2 IN EVENT
 OF ALARM)

POWER SUPPLY

3×400V~50Hz

START/

STOP

CONTROL

0-10V=

Summary of Contents for Flexomix MIE-FD

Page 1: ...ontact motors for impeller size 080 090 have a thermistor The fan and motor unit are mounted on slide rails to facilitate servicing The air temperature should not exceed 50 C to ad equately cool the motor Fan and motor are very effectively vibrationisolated from the casing by means of a vibration isolating outlet connection and rubber antivibration mount ings sized according to the fans operating ...

Page 2: ...115 100 300 050 900 1580 805 120 100 360 050 1050 1580 990 125 100 360 056 1050 1580 990 140 112 480 056 1200 1950 990 145 100 480 063 1200 1950 990 230 132 600 063 1200 2160 1095 225 132 600 071 1350 2160 1095 250 132 740 071 1350 2480 1240 265 132 740 080 1500 2480 1240 335 160 750 071 1350 2020 1370 365 132 750 080 1500 2020 1370 335 160 850 071 1350 2560 1370 375 132 850 080 1500 2560 1370 345...

Page 3: ...35 30 30 190 1000 500 180 100 1300 635 30 30 240 1000 600 180 100 1300 740 30 30 300 1200 600 190 100 1520 740 30 30 360 1200 800 190 95 1520 930 30 30 480 1400 800 275 95 1890 930 30 30 600 1600 800 280 150 2100 1035 30 30 740 2000 900 240 170 2380 1140 50 50 750 1600 1000 210 185 1920 1270 50 50 850 2200 1000 180 185 2460 1270 50 50 950 1600 1200 210 230 1920 1560 50 50 C E A D Fan capacity ELFD...

Page 4: ...Manuf month Valmistus kk Miesiąc 1105 Art Nr 19121 1301_01 Y Y M M Typical fan rating plate N B The fans can be of different sizes variants Read the rating plate of both the supply air and the extract air fan Motor type 025 EC 1 230V 0 42 kW TK NC TK COM 0 10V GND L N PE 10V ALARM OPENS IN EVENT OF LARM CONTROL 0 10V POWER SUPPLY 1 230V 50Hz Motor type EC 1 230V all excl 025 EC 1 230V 0 42 kW NO C...

Page 5: ...30 400V 50Hz 5 72 7 8 10 4 4 3 8 0 3 3 4 5 6 0 360 050 EC E1 2 82 2 2 3 400V 50Hz 3 230 400V 50Hz 7 8 4 3 4 5 360 056 EC E1 4 70 3 0 4 0 3 400V 50Hz 3 230 400V 50Hz 10 4 13 7 7 7 6 0 7 9 480 056 F1 E1 3 0 3 0 3 400V 50Hz 3 230 400V 50Hz 10 4 6 4 6 0 480 063 F1 E1 4 0 4 0 5 5 5 5 7 5 7 5 3 400V 50Hz 3 230 400V 50Hz 13 7 18 4 25 1 8 4 11 1 15 1 7 9 10 6 14 5 600 063 F1 E1 4 0 4 0 5 5 5 5 3 400V 50Hz...

Page 6: ...ling unit The fan speed is adjusted to provide the correct airflow If the fan generates a lower airflow this may disturb ventilation system performance If the supply airflow is too low there will be imbal ance in the system and this may cause draught problems If the ventilation capacity is too low this may contribute to poor room climate If the extract airflow is too low poor ventilation capac ity...

Page 7: ...a base frame fitted with rubber anti vibration mountings Check that the anti vibration mountings are firmly mounted and are intact 6 Check the condition of the mounting screws the suspension devices and the base frame 7 Check that the gaskets on the connection plates around the connection opening are intact and are firmly fitted 8 Check that the measurement tubes are firmly fitted to their relevan...