Heat exchanger, operation and  

maintenance instructions

Inspection

1.  Inspect the fins for fouling. Inspection can be 

carried out through e.g. an inspection door to the 

filter section.

2.  Check the auto defrosting function and make sure 

that the bypass damper closes securely when 

defrosting is not in progress.

3.  Check the drip tray, drainage and water trap 

function. A water trap without a non-return value 

should be filled with water.

Cleaning

If cleaning is required this can be done with a vac-

uum cleaner, blowing with compressed air or by using 

detergent suitable for aluminium and rinsing off with 

hot water. 

Cleaning is best done by flushing water through every 

single air duct (possibly adding ordinary detergent that 

does not corrode aluminium) across the entire length 

of the heat exchanger.

At operating temperatures below 0°C the heat 

exchanger assembly must be dry before being 

commissioned.

Damper, operation and maintenance 

instructions

Inspection

1.  Check the function of the damper actuator.

2.  Check the dampers for tightness when they are 

closed. If they are not sealed, adjust the damper 

actuator to make the damper tight.

3.  Check the sealing strips.

Cleaning

Clean the damper blades with a cloth. If they are severely 

fouled, an environmentally friendly degreasing agent 

can be used.