3.
Alarms
3.1 General
This section described the following functions:
●
●
Alarm.
●
●
Alarm lists.
●
●
History lists.
●
●
Acknowledge alarms.
●
●
Reset alarms.
●
●
Alarm and history lists can contain a maximum of 60 entries.
●
●
Each alarm entry includes description, notification class, alarm group, date and
time.
●
●
Every new alarm generates an entry in the alarm list and in the history list.
●
●
Active alarm:
–
The alarm indicator on the external control unit flashes.
–
The alarm symbol in the built-in control unit flashes.
●
●
Alarm acknowledged but still active:
–
The alarm indicator on the external control unit lights up.
–
The alarm symbol in the built-in control unit lights up.
●
●
Alarm reset:
–
Alarm list: the alarm entry is removed.
–
History list: the alarm entry is displayed as removed.
Procedure for alarm that releases values:
Active
unconfirmed
Active
unconfirmed
Normal
LED flashes
LED off
Normal
Confirm
Alarm disappears
LED lights continuously
Alarm disappears
Alarm occurs
Procedure for alarm that retains values:
Inactive,
not confirmed
LED flashes
LED off
Normal
Normal
Active,
not confirmed
Active,
confirmed
Inactive,
confirmed
LED flashes
LED lights continuously
LED lights continuously
Confirm
Confirm
Alarm
displayed
Alarm disappears
Confirm
Confirm
(Reset)
Principles
Alarm that retains or releases
values
Quick Start Manual for the EcoHeater Climatix control system
18710-6011 SMCX.151008.00EN
Page 15