INTRODUCTION 

A Vortex A/C enclosure cooler is designed to use filtered 
compressed air to cool industrial control cabinets without the 
use of any refrigerants. Hot air in the cabinet is vented to the 
surroundings through a built-in vent in the Vortex A/C. Noise 
generated by the Vortex A/C is comparable to normal speech 
levels. The Vortex A/C has a built-in mechanical thermostat that 
requires no electricity. To operate, simply install on your enclosure 
and connect the compressed air source.

COMPRESSED AIR SUPPLY

The compressed air supply must be filtered (5 micron maximum) 
to remove water and dirt. A 5 micron filter is supplied for this 
purpose (Vortec model 701S-24A or 701S-36A). If oil is present 
in the compressed air supply, remove the oil using an optional 
0.01 micron coalescing filter (Vortec model 701S-48 or 701S-54). 
Filter recommendations are given in Table 1.
If an oil removal filter is necessary, install it downstream of 
the 5 micron filter. Change the filter elements as needed (see 
Maintenance).
The appropriate size of compressed air supply line should be 
selected to ensure optimal performance of the Vortec product. 
Please refer to Table 2 to determine what supply line size is 
recommended for your application. Contact Vortec at 1-800-441-
7475 for further assistance.

INTERNAL CABINET PRESSURE

The Vortex A/C, when operating at 100 psig (6.9 bar), will maintain 
the internal enclosure pressure at approximately 35” (889 mm) 
of water column. When the Vortex A/C is not cooling (when the 
thermostat senses acceptable temperatures), the Vortex A/C is 
not pressuring the enclosure. If you desire a constant positive 
internal enclosure pressure, even when the Vortex A/C is not 
cooling, this may be accomplished by removing a set screw 
that is adjacent to the mechanical thermostat on the bottom of 
the unit. By removing this set screw with a 3/32” (2 mm) hex 
key), a small amount of air (3 cfm or 85 lpm) will pressurize the 
sealed enclosure to approximately 1.5” (38 mm) water column. 
This “pressurization air” will run continuously, regardless of the 
thermostat operation, until the set screw is re-installed.

MAINTENANCE

The only maintenance involved with the Vortex A/C is normal 
element changes to the compressed air filter. The filter element 
should be changed when there is a noticeable decrease in 
performance or when pressure drop across the filter exceeds 
5 psig (0.3 bar). The Vortex A/C has only one moving part (the 
mechanical thermostat/valve) which is not serviceable in the 
field. Do not disturb the setting of the thermostat. Evidence of 
tampering with the thermostat may void the warranty.
If it is suspected that the compressed air filter has not been 
maintained after an extended period of operation, there may be 
dirt in the Vortex A/C. If the Vortex A/C is not cooling sufficiently, 
there may be debris in the “generator” of the unit. To check, pull 
the 1/2” (13 mm) inside diameter vinyl tubing off the cold air 
outlet of the Vortex A/C and unscrew (with a 1” (25 mm) open 
end wrench) the cold air outlet. Remove the O-ring. Remove the  
white nylon washer(s). Then remove the red (model 7615) or the 
blue (model 7625) or the brown (model 7635) generator. Inspect   
the six slots in the generator for dirt and clean if necessary. Clean 
the cavity in the Vortex A/C that the generator was located in 
if necessary. Reassemble in reverse order. Tighten the cold air 
outlet to 100 inch-pounds (11 newton meters) torque. Be sure to 
supply clean (filtered to 5 micron) and oil free compressed air to 
the Vortex A/C.

INSTALLATION

To maintain the UL Type 12 rating, the Vortex A/C MUST be 
installed in one of the following configurations on a UL Type 12 
enclosure: 

a.  Top mounted in an upright and vertical orientation, on 

a flat horizontal surface (as shown)

b.  Side mounted, on a flat vertical surface of the 

enclosure, with the compressed air inlet pointing 
upward. When side mounted, rotate the aluminum 
louvered outlet on the back of the Vortex A/C so the 
louvers point downward to the floor.

1.  Position the Vortex A/C on the top or side of your enclosure 

so that there is sufficient clearance for the internal mechanical 
thermostat and cold air outlet, and, so that the entire mounting 
“footprint” of the Vortex A/C is supported by the enclosure. (A 
4-3/4” wide x 3-3/8” deep (121 mm wide x 86 mm deep) area). 
Position the unit so that the louvered outlet on the back of the 
Vortex A/C is away from personnel, if possible. Also, position 
so that no internal enclosure components obstruct air flow 
around the mechanical thermostat.

2.  Cut a 1-15/16” (49 mm) diameter hole (1-1/2” knockout size) 

in the selected location on the enclosure. De-burr any sharp 
edges around this hole.

3.  Remove the 1-1/2” electrical locknut from the Vortex A/C. 

Insert the threaded portion of the Vortex A/C into the 1-15/16” 
(49 mm) hole in the enclosure. (Be careful not to damage the 
mechanical thermostat during installation.)

4.  From inside the enclosure, screw the electrical locknut onto 

the threads of the Vortex A/C. Tighten the locknut securely 
to compress the 1/8” (3 mm) thick sealing gasket that is 
positioned between the enclosure and the Vortex A/C.

5.   Determine a suitable location for the Cold Air Muffler inside the 

enclosure that is close to the cold air outlet of the Vortex A/C. 
(You will need a surface area of approximately 2” x 9” (50 mm 
x 229 mm) to mount the muffler. The Muffler can be mounted 
in any orientation, horizontal or vertical.) Using the supplied 
Muffler Mounting Clamp (with double sided tape), attach this 
Clamp at the desired location. Clean the mounting surfaces 
so that the double sided tape bonds securely. If desired, this 
Clamp can be permanently mounted to the enclosure using 
the supplied mounting hardware. Two 5/32” (4 mm) diameter 
holes positioned on 3/4” (19 mm) centers must be drilled to 
mount the Muffler Clamp. Use the plastic snap rivets to secure 
the Muffler Clamp to the panel.

6.  Snap the Cold Air Muffler into the Mounting Clamp.
7.  Cut a sufficient length of the 1/2” (13 mm) inside diameter 

vinyl tubing from the supplied #701M-43 Cold Air Ducting Kit 
to connect the cold air outlet of the Vortex A/C to one of the 
hose barbs on the Cold Air Muffler. Attach this length of vinyl 
tubing so that it is free of sharp bends and kinks. Direction of 
cold air flow through the Muffler is not important. 

8.  Attach all (or a portion of) the remaining supplied vinyl tubing 

of the #701M-43 Cold Air Ducting Kit to the opposite hose barb 
connection on the Cold Air Muffler. Holes can be punched 
or drilled into this 1/2” (13 mm) tubing to distribute the cold  
air evenly inside your enclosure, or, the entire cold air output 
can be directed to a heat sensitive component. If the end of 
the 1/2” (13 mm) vinyl tubing is plugged, at least sixteen 1/8” 
(3 mm) diameter holes should be punched into the tubing to 
allow the cold air to escape. Use the nine self adhesive tubing 
clips provided in the kit to mount the tubing.

9. Connect the compressed air filter (model 701S-24A or 

701S-36A) to the compressed air inlet on the side of the 
Vortex A/C with a length of 3/8” pipe. Install the compressed 
air filter as close as possible to the Vortex A/C, in a location 
where the temperature does not exceed 125

o

F (52

o

C). Allow 

the filter to hang at the side of the enclosure as shown in 
the installation drawing. Use a 13/16” (21 mm) wrench to hold 
the air fitting on the side of the Vortex A/C stationary while 
tightening the pipe connections. Note the air flow direction 
arrow on top of the filter. 

10.  Connect the compressed air supply to the inlet of the air filter. 

See “Compressed Air Supply”.

OPERATION

Operate the Vortex A/C at 90 to 100 psig (6.2 to 6.9 bar) 
compressed air pressure. Do not operate at pressures above 150 
psig. (10.3 bar) Operation at pressures less than 90 psig (6.2 
bar) and above 100 psig (6.9 bar) can affect the “on” and “off” 
temperatures at which the unit cycles. The Vortex A/C will cycle 
on and off to maintain temperatures between 80

o

 to 90

o

F (27

o

 to 

32

o

C). The Vortex A/C will not work properly at pressures below 

70 psig (4.8 bar).
CAUTION: The louvered outlet on the back of the Vortex A/C 
becomes hot during operation and can remain hot for a period of 
time after the unit has cycled off. Note warning label precaution, 
and avoid direct contact with this area of the unit during or after 
operation. 

TROUBLESHOOTING

Insufficient cooling may be caused by the following:
1.  Undersized compressed air line size.
2.  Compressed air pressure at the product is too low.
3.  Partial or complete blockage of internal compressed air paths, 

due to dirt.

4.  Water vapor in the compressed air supply.
5. Loose cold air outlet fitting. This may occur if not tightened 

properly after being disassembled for cleaning.

If trouble persists, please contact Vortec at 1-800-441-7475.

LIMITED WARRANTY

Vortex A/C compressed air enclosure cooling products 
manufactured by ITW Air Management will be replaced or 
repaired if found to be defective due to manufacture within ten 
years from the date of invoice. Refer to our website www.vortec.
com for full warranty details and limitations. ITW Air Management 
makes no specific warranty of merchantability or warrant of 
fitness for a particular purpose.

GENERAL SAFETY CONSIDERATIONS

1.  Do not operate a Vortex A/C at compressed air pressures 

above 150 psig (10.3 bar).

2. Do not operate a Vortex A/C at line temperatures above 

110

o

F (43

o

C).

3. Avoid direct contact with compressed air.
4. Do not direct compressed air at any person.
5. When using compressed air, wear safety glasses with 

side shields.

WARNING:  COMPRESSED AIR COULD CAUSE DEATH, 

BLINDNESS OR INJURY.

VORTEX A/C TYPE 12

(SHOWN TOP MOUNTED ON CUSTOMER’S ENCLOSURE)

Hole 1-15/16” (49 mm)

1-3/4” (44 mm) diameter 
x 3-19/32” (91 mm) long

muffler and mounting 

clamps

Vent Air

Filter

5-7/8”

(149 mm)