TABLE 2: 

DETERMINING COMPRESSED AIR LINE SIZE 

1.  Calculate total product compressed air consumption (SCFM, SLPM).
2.  Determine length of compressed air line required for connection to main supply.
3.  Locate pipe length in left column and read to the right to find the compressed air requirements.
4.  Locate pipe size at top of column.

MAXIMUM AIRFLOW (SCFM) THROUGH PIPE AT 5 PSIG PRESSURE DROP (100 PSIG AND 70

O

F)

Pipe Length 

(Feet)

Pipe Size (Nominal) - Schedule 40

1/4

3/8

1/2

3/4

1

1-1/4

1-1/2

2

2-1/2

10

29

65

120

254

480

978

1483

2863

4536

20

21

46

85

180

340

692

1049

2024

3208

30

17

37

70

147

277

565

856

1653

2619

40

15

32

60

127

240

489

792

1431

2268

50

13

29

54

114

215

437

663

1280

2029

60

12

26

49

104

196

399

606

1169

1852

70

11

25

46

96

181

370

561

1082

1715

80

10

23

43

90

170

346

524

1012

1604

90

10

22

40

85

160

326

494

954

1512

100

9

21

38

80

152

309

469

905

1435

MAXIMUM AIRFLOW (SLPM) THROUGH PIPE AT 0.3 BAR PRESSURE DROP (6.9 BAR AND 21

O

C)

Pipe Length 

(Meters)

Pipe Size (Nominal) - Schedule 40

1/4

3/8

1/2

3/4

1

1-1/4

1-1/2

2

2-1/2

3

821

1840

3396

7188

13584

27677

42117

81023

128369

6

594

1302

2406

5094

9622

19584

29687

57279

90786

9

481

1047

1981

4160

7839

15990

24225

46780

74188

12

425

906

1698

3594

6792

13839

20999

40497

64184

15

368

821

1528

3226

6085

12367

18763

36224

57421

18

340

736

1387

2943

5547

11292

17150

33083

52412

21

311

708

1302

2717

5122

10471

15877

30621

48535

24

283

651

1217

2547

4811

9792

14829

28640

45393

27

269

623

1132

2406

4528

9226

13980

26998

42790

31

255

594

1075

2264

4302

8745

13273

25612

40611

Rubber hose maximum airflow rating:  1/2” I.D. rubber hose = 3/8” pipe; 3/4” I.D. rubber hose = 1/2” pipe

FILTER AND REPLACEMENT PART ITEM NUMBERS

Vortec Model #

Oil Removal Filter

Replacement Generator Kits (5 pc)

7115, 7615

701S-48

208GK-15H

7125, 7625

701S-48

208GK-25H

7135, 7635

701S-54

208GK-35H

TABLE 1: 

FILTER RECOMMENDATIONS

VORTEX A/C ENCLOSURE COOLER

UL TYPE 12

Models 7115, 7125, 7135, 7615, 7625, 7635

(Includes all BSP versions of models listed above)

LIT0280

Please read all instructions BEFORE 

attempting to use this product