NOTICE:
• Either thermal contacts or thermistors are incorporated in the pump.
• Thermal contacts must never be exposed to voltages higher than 250 V, breaking current maximum
4 A. It is recommended that they are connected to 24 V over separate fuses to protect other
automatic equipment.
1. If thermal contacts are included in the pump installation, connect the T1 and T2 control conductors
to the MiniCAS II monitoring equipment.
2. If thermistors are included in the pump installation, and screened or auxiliary cable is used, then
connect T1(1) and T2(2) to thermistor relay or MAS 711, and T3(3) and T4 (4) to MiniCAS II or
MAS 711.
3. Connect the mains leads (L1, L2, L3, and earth [ground]) to the starter equipment.
For information about the phase sequence and the color codes of the leads, see
(page
20).
4. Check the functionality of the monitoring equipment:
a) Check that the signals and the tripping function work properly.
b) Check that the relays, lamps, fuses, and connections are intact.
Replace any defective equipment.
Cable charts
1 2 3 4 5 6 7
1 2
L1 L2 L3
GC
U1 W2 V1 U2
T16 T15 T2 T1
W1 V2
1
2
3
6
5
4
7
1.
Control leads
2.
Starter equipment
3.
Mains leads
4.
Motor cable
5.
Terminal blocks on pump
6.
Stator leads
7.
Control cable
Figure 7: Connection locations
L2
L1
L2
L3
L3
L1
Figure 8: Phase sequence
Colors and marking of the mains leads
Mains
SUBCAB 7GX
SUBCAB 4GX
SUBCAB AWG
SUBCAB
(screened)
L1
Black 1
Brown
Red
Brown
L2
Black 2
Black
Black
Black
L3
Black 3
Grey
White
Grey
L1
Black 4
-
-
-
Installation (Continued)
20
Flygt 5150.350, 5150.360 Installation, Operation, and Maintenance Manual