Page 10 

    Installation and Operation Manual 

 

Figure 5 - Wiring for RS-232 Communications

 

A

B

DATA SEND

SIGNAL GROUND

DATA RECEIVE

C

All manuals and user guides at all-guides.com

Summary of Contents for Neo-Dyn 801P5

Page 1: ...NEO DYN 801P5 SMART SWITCHTM INSTALLATION AND OPERATION MANUAL PN 610 0002 Rev D ECO 71349 All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 2: ...to 3 30 pm Pacific Time Before installing the Smart SwitchTM become familiar with the installation instructions in Chapter 2 Indicates a hazard which can cause severe personal injury death or substantial property damage if the warning is ignored Indicates a hazard which will or can cause minor personal injury or property damage if the caution is ignored Indicates additional information about a par...

Page 3: ... 11 FRONT PANEL CONTROLS 12 INPUT CONTROLS 13 DISPLAYING PRESSURE 13 DISPLAYING SET POINTS 14 STANDARD VS WINDOW MODE 15 PROGRAMMING MODE 17 ENTER PROGRAMMING MODE 17 CHANGING THE SET POINTS 19 ADDITIONAL FEATURES 20 CHAPTER 4 ANALOG OPTION 25 ANALOG OPTION WIRING 25 TURNING ANALOG OUTPUT ON AND OFF LOOP 25 4 20 MILLIAMPERE OUTPUT CALIBRATION 4CAL 26 4 20 MILLIAMPERE OUTPUT SCALING 27 CHAPTER 5 TR...

Page 4: ...TM Page iii TABLE OF CONTENTS PAGE CHAPTER 6 SERIAL COMMUNICATIONS Z Option 35 GENERAL 35 WIRING 35 CHAPTER 7 SPECIFICATIONS 37 STANDARD 37 OPTIONS 40 WARRANTY INFORMATION 41 All manuals and user guides at all guides com ...

Page 5: ...nfigured on site using the front panel keypad and 4 digit display or remotely via the optional RS 232 connection The 4 20 mA output option offers remote monitoring capabilities A built in password security system prevents unauthorized adjustments When locked pressure can be monitored and set points may be viewed but no adjustments can be made without entering the correct password The Smart SwitchT...

Page 6: ...l 801P5 Smart SwitchTM Mounting Brackets not Shown Conduit Connection 1 2 14 NPT Pressure Port 1 4 18 NPT Std 4 20 mA Output RS232 COM Port 18 free leads 22 AWG Status Indicators Keypad All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 7: ...ailable as Option E Output options available for the Smart SwitchTM include a 4 20 mA analog output Option V scalable display units Option Q and RS232 communications Option Z The RS232 option can be used to configure and monitor the unit remotely This option includes Windows based software Chapter 7 on page 37 contains complete specifications for the 801P5 Smart SwitchTM All manuals and user guide...

Page 8: ...uded in instructions the keys are shown in brackets as STORE DISPLAY When shown in the text the LED displays are formatted as 279 3 CUSTOMER SERVICE If you have any questions about the 801P5 Smart SwitchTM that are not covered in this manual you can contact Neo Dyn in several ways The customer service phone number is 661 295 4000 Our customer service department is open from 7 00 am to 3 30 p m Pac...

Page 9: ...he pressure connection or it can be attached to a flat surface such as a wall near the connection to be monitored For surface mounting slide the two mounting brackets into the slots on the back of the Smart SwitcTM and use 10 190 in dia fasteners PRESSURE CONNECTION The standard pressure connection for the 801P5 Smart SwitchTM is a 18 NPT female pipe thread A 7 16 20 SAE boss is also available as ...

Page 10: ...ector This mating connector has solder cups that will take wires as large as 18 AWG See Chapter 4 for operating instructions The RS232 communications option letter Z are connected to the 3 pin connector on the top left of the unit See Figure 5 using the supplied mating connector This mating connector has solder cups that will take wires as large as 18 AWG Cable length must not exceed 50 feet See C...

Page 11: ...Page 7 801P5 Smart SwitchTM Figure 2 Schematic for AC Operation All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 12: ...Page 8 Installation and Operation Manual Figure 3 Schematic for DC Operation All manuals and user guides at all guides com ...

Page 13: ...Page 9 801P5 Smart SwitchTM Figure 4 Wiring for 4 20 mA Analog Output A B 4 20 Ma RETURN All manuals and user guides at all guides com ...

Page 14: ...Page 10 Installation and Operation Manual Figure 5 Wiring for RS 232 Communications A B DATA SEND SIGNAL GROUND DATA RECEIVE C All manuals and user guides at all guides com ...

Page 15: ... power to the appropriate free leads there is no on off switch In normal operation mode the display shows Online LED green indicates operation mode S1 and S2 LED s red indicate the switch status illuminated when the relay coil is energized or the solid state switch is actuated System pressure is displayed You can also check the set points in operating mode all other actions are done in programming...

Page 16: ...ssure in normal operation S1 and S2 Switch Indicators The S1 and S2 red LED s indicate switch status illuminated with the relay coil energized or the solid state switch actuated Online Indicator The Online indicator green LED is lit when the unit is online and active If the indicator is not lit the unit is offline All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 17: ...d to move into the desired submenu STORE The STORE key is used to temporarily save changes made to the current submenu and return to the main menu RUN The RUN key is used to lock in the programming changes made After pressing RUN to return to operation mode go back online you must press SELECT Otherwise any programming changes will be lost after 2 minutes DISPLAYING PRESSURE When the Smart SwitchT...

Page 18: ...the increasing value for Switch 1 press S1 INCR To view the decreasing value for Switch 2 press S2 DECR Figure 7 Press the Incr Decr Buttons to Display Set Points for S1 S2 After 5 seconds of keypad inactivity the display automatically changes back to the system pressure display While viewing set points the output functions remain active All manuals and user guides at all guides com ...

Page 19: ...et value At this point the Smart SwitchTM might turn off whatever electrical power is being applied to a pump for example which is increasing or maintaining the pressure The switch de actuates or resets when the pressure drops below the preset decreasing set point SP1d or SP2d At this time the electrical power to the pump would be turned back on Figure 8 Standard Mode INCREASING SET POINT DECREASI...

Page 20: ...w that range In Window Mode the Smart Switch starts out actuated then deactuates when it reaches its lower set point SP1d or SP2d As pressure continues to increase the switch actuates again when it reaches the upper set point SP1i or SP2i This range between the lower and upper set points is the window When pressure decreases the sequence reverses with a deadband of 1 of F S O at each of the set po...

Page 21: ...t If your unit includes the RS232 option you can Set the BAUD rate The unit will not function as a switch while in programming mode ENTER PROGRAMMING MODE To access the programming mode press the MENU key See Figure 7 On the initial startup no password is required If you have previously set up a password you must enter it at this time 1 When the displays show O press the UP DOWN ARROW keys to set ...

Page 22: ...fter you are done press the RUN key to lock in the changes Then press the SELECT key to return online You must press the SELECT key when RUN is displayed to permanently save any changes you have made If you do not all changes will be lost after two minutes of inactivity When RUN is displayed you have two additional choices REDO and UNDO Use the UP DOWN ARROW keys to scroll through the menu Press t...

Page 23: ...RROW keys to change the value of the digit 4 When the value is correct press the SELECT key to move to another digit Repeat this until you have the correct value for this set point 5 Use the STORE key to temporarily save the changes and return to the main menu 6 Press RUN and then SELECT to permanently save the setting and return to On Line operation If you have set an invalid set point the error ...

Page 24: ...porarily save your settings Display DISP This item sets how often the pressure display is updated This can be useful when there is a lot of fluctuation in the pressure reading After DISP appears use the SELECT key to enter the submenu Use the UP DOWN ARROW keys to cycle through the available display settings This option can be set at OFF 0 5 1 0 2 0 3 0 4 0 or 5 0 seconds Press the STORE key to te...

Page 25: ...present the pressure in millibars The standard conversion unit is 1 psi 68 95 millibars You want to read zero for zero pressure therefore r Lo 0 Full scale output pressure for the 801P5 for this example is 15 psig So r Hi 68 95 x 15 1034 25 millibars which rounds to 1034 Therefore r Hi should be set to 1034 The unit now reads from 0 to 1034 millibars for 0 to 15 psig pressure The accuracy is 2 mil...

Page 26: ...hanges and return to the main menu 6 Press RUN and then SELECT to permanently save the setting and return to On Line operation 7 Repeat steps 1 through 6 for r Hi The setting should be at least 2 display counts higher than r Lo Decimal Location Loc You can change the location of the decimal point thereby changing the scale of the display by using this function After Loc displays press SELECT to mo...

Page 27: ...ORE key to return to the main menu A pressure source is required for this operation In addition calibration equipment used must have an accuracy of at least 0 02 F S O of the switch being calibrated If re calibration results in zero or Full Scale readings that have shifted by 4 F S O or more from the factory calibration an error code of EROR will be displayed Reset rSET This command resets the Sma...

Page 28: ...e the 4 20 mA analog option there are three additional menu items that are reset These are LooP is set to on ScHi is set to F S O ScLo is set to zero These three menu items are discussed in Chapter 4 Analog Option All manuals and user guides at all guides com ...

Page 29: ...s the negative output The 801P5 generates its own loop power and it can operate with a load resistance of 600 ohms maximum TURNING ANALOG OUTPUT ON AND OFF LOOP Current Loop LOOP This menu item enables or disables the current 4 20 mA output To use this item 1 Press MENU 2 Press the UP DOWN ARROW key until LOOP displays the press the SELECT key to enter the submenu 3 Press either ARROW key to chang...

Page 30: ... output 2 Press MENU then press the UP DOWN ARROW key until 4CAL is displayed 3 Press SELECT The display will show LO C 4 While reading the milliammeter use the UP DOWN ARROW keys to adjust the output to 4 milliamperes 5 Press the STORE key The display will read HI C 6 Use the UP DOWN ARROW keys to adjust the output to 20 mA then press the STORE key to temporarily save the calibration data and ret...

Page 31: ... the UP DOWN ARROW keys until SCLO is displayed Press SELECT to enter the submenu Use the SELECT key to move from digit to digit and use the UP DOWN ARROW keys to adjust each digit Once you have set the pressure press STORE to save your setting The range of adjustment for this function is zero psig to 66 of F S O The difference between the SCLO setting and the SCHI setting must be at least 33 of F...

Page 32: ...Page 28 Installation and Operation Manual All manuals and user guides at all guides com ...

Page 33: ...ith brief descriptions of how to correct them If you see an error that is not listed here contact Neo Dyn Customer Service The contact information is located in Chapter 1 Display Shows 0 The MENU key has been pressed and the unit has a password other than 0000 Use the UP DOWN ARROW keys to set the first digit at the correct value Use the SELECT key to move to the next digit Repeat this process unt...

Page 34: ...ch set points You have entered incompatible set points Switch 1 and Switch 2 are independent of each other however the following rules apply to each switch The increasing set point must be at or below the Full Scale Output F S O value it cannot be less than 2 of F S O and it must be at least 1 of F S O above the decreasing set point The decreasing set point must be no lower than 1 of F S O it can ...

Page 35: ... online and monitoring pressure but the pressure is at or greater than 110 of F S O When the pressure returns to less than 110 of F S O the display will return to its normal pressure display Display shows LLLL This indicates that the unit is online and monitoring pressure but the pressure is less than 4 of the F S O below zero psig pulling a vacuum When the pressure returns to greater than 4 of th...

Page 36: ...een broken In this case repair the broken connection or turn the loop off using the method described in the previous paragraph Load resistance exceeds 600 ohms In this case reduce the resistance Display is blank Press the S1 INCR key If the display illuminates and displays the increasing set point for Switch 1 then the Disp display update option has been set to OFF If the display does not react th...

Page 37: ...se is vacuum once the pressure returns to near zero the unit will return to monitoring and controlling If the cause is internal component failure contact Neo Dyn Customer Service for assistance Display shows E 97 This error indicates that the internal user data saved in the nonvolatile RAM has become corrupt Press the SELECT key to cause the unit to reboot If the unit continues to show E 97 contac...

Page 38: ...Page 34 Installation and Operation Manual All manuals and user guides at all guides com ...

Page 39: ...te monitoring and programming of the Smart Switch as well as data tracking functions To install the software follow the Setup instructions on the diskette label Once it is installed the Help menu provides detailed operating instructions The default BAUD rate is 9600 but it may be set to 2400 BAUD for noisy environments WIRING Smart Switch Connector Pin Function DB9 Connection Pin DB25 Connection P...

Page 40: ...Page 36 Installation and Operation Manual All manuals and user guides at all guides com ...

Page 41: ...Smart SwitchTM weighs approximately 6 pounds 2 7 kg 14 NPT Conduit Connection with 22 AWG Free Leads 18 NPT Female Pressure Port Two independent Solid State or Relay Switches Temperature Range Operating 15 F 26 C to 140 F 60 C Storage 30 F 34 C to 170 F 72 C Input power 115 VAC 50 60 Hz 230 VAC 50 60 Hz 18 30 VDC All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 42: ...ut Power Switch Type Options Figure 10 Part Number Breakdown Pressure Rating Information Range No Operating Range psig Increasing Range psig Deadband Percent of Full Scale Minimum Decreasing Setpoint psig Max Operating Pressure psig Proof Pressure psig 02 0 5 10 5 1 99 05 12 5 25 04 0 15 30 15 1 99 15 37 5 75 05 0 30 60 30 1 99 30 75 150 07 0 100 2 100 1 99 1 250 500 09 0 250 5 250 1 99 2 5 625 75...

Page 43: ... 6 5 1 99 0 065 17 2 34 4 29 0 17 0 34 17 1 99 0 17 43 1 51 7 31 0 35 0 7 35 1 99 0 35 103 103 32 0 65 1 3 65 1 99 0 65 172 206 34 0 200 4 200 1 99 2 206 344 Range No Operating Range inH2O Increasing Range inH2O Deadband Percent of Full Scale Minimum Decreasing Setpoint inH2O Max Operating Pressure psig Proof Pressure psig 72 0 100 2 100 1 99 1 12 5 25 74 0 415 8 3 415 1 99 4 15 37 5 75 Total Accu...

Page 44: ...te SPDT 12 140 VAC 3 Amp Resistive 5 mA max D Solid State SPDT 5 60 VDC 3 Amp Resistive 1 mA max R Relay SPDT 115 VAC 24 VDC 3 Amp Resistive N A OPTIONS The 801P5 options are listed below You can combine these options but every option ordered should be indicated in the part number of the unit Option Description E 7 16 20 SAE Pressure Port Q Scalable Readout V Analog Output 4 20 mA Z RS232 Communic...

Page 45: ...om Warranty THE FOREGOING WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER EXPRESSED OR IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS OR OTHERWISE Components manufactured by any supplier other than ITT shall bear only the warranty made by the manufacturer of that product and ITT assumes no responsibility for the performance or reliability of the unit as a whole In no event shall ITT be liable for ...