9. Product description

The DALI-16B-SL module (slim-line) is an ISYGLT DALI gateway with integrated DALI power supply and is designed for space-saving installation 
in control cabinets. This module is particularly suitable for systems with many DALI groups or single circuit control. Up to 32 DALI ECGs (DALI 
standard loads) can be operated on one DALI BUS. Each of these 32 DALI devices (ECGs or electronic transformers) must be programmed 
with a unique device address (DALI short address). Each device address can be assigned one of 4, 8, 12 or 16 ISYGLT dimming groups in up 
to 3 configurations (setups) by parameterizing the DALI-16B-SL module. These dimming groups have all the properties possible in the ISYGLT 
system with regard to scene storage, fade time calculations etc. 

The module is equipped with its own mains supply, which is designed for 32 standard DALI loads. This enables a freely configurable emergency 
function for the corresponding DALI BUS. All DALI output devices are completely integrated into the possibilities of the ISYGLT system through 
our concept. Thus the functional range of the ISYGLT system is available. The module occupies 4 module addresses on the BUS. The DALI 
devices are monitored for lamp faults or ECG faults. The DALI failure level (value in case of DALI BUS failure) can be parameterised via the DALI-
16B-SL. Maintenance intervals can be easily calculated via an operating hours counter. 

According to the standard, the DALI ECGs always remain live, which ultimately leads to unnecessary energy consumption when switched off. A 
main contactor for the DALI ECGs can be controlled via a virtual output. If the mains voltage is simply switched on or off, operating devices may 
no longer operate correctly, as protocols can already be sent during the start phase. This effect is avoided by our new circuit logic.

The following functions are available for commissioning and operating the devices:

• DALI broadcast for commissioning and emergency operation
• automatic addressing of new ECGs during exchange work
• ECG addressing and control in conjunction with the IP Master and the DALI web plug-in

The following functions can be performed stand-alone by the DALI module:

• calculation of ups with time constants from 0.5 seconds to 18 hours 
• automatic dimming from current analog actual values to predefined analog target values at a predefined speed (optionally in predefined time) 
• feedback of the termination of the analog value output after the performance of time functions 
• stop function during the performance of time functions 
• OVERSAMPLING error correction (With the so-called „OVERSAMPLING“, the DALI module automatically corrects the jumps of the analog 

values caused by the cycle times of the BUS system. For this purpose, the analog values between the BUS cycles are transformed back into 
the resolution of 8 bits by linearization.)

• performance of blinking functions

Inputs / Outputs

• 1 DALI-BUS

Function displays

LED state

Meaning

1 x LED (red)

OFF

No operating voltage

ON

Operating voltage, no error

1 x LED (yellow)
Operating voltage / BUS

OFF

BUS wiring error

ON

Error BUS communication (address)

Blinking

Interference-free data transmission via the BUS line

1 x LED (green)

Blinking 1 Hz

No parameter data in the module

ON

Module works only as DALI power supply (DIP switch S1 = ON)

Blinking 2 Hz

Module works in DALI broadcast mode, sending a low fixed value for test 

purposes (DIP switch S1+S2 = ON)

Summary of Contents for DALI-16B-SL

Page 1: ...acher de Phone 49 0 80 41 77 77 6 Marktstrasse 57 83646 Bad T lz info seebacher de Fax 49 0 80 41 77 77 2 1 Technical Data Instruction Manual DALI 16B SL Article no 80027161 DALI module slim line for...

Page 2: ...e handed over to the device operator The operator will store the documents so that they can be made available if necessary 1 2 Symbols used Observe the following safety and other instructions in the m...

Page 3: ...rrors 2 Safety instructions Observe the following general safety instructions when installing and commissioning the device Assembly and installation of the ISYGLT module may only be carried out by a q...

Page 4: ...screws Assembly site The product can be installed in any position in a casing to be deter mined by the electrician distribution box switch cabinet Observe maximum ambient temperature Assembly steps Re...

Page 5: ...switched off A main contactor for the DALI ECGs can be controlled via a virtual output If the mains voltage is simply switched on or off operating devices may no longer operate correctly as protocols...

Page 6: ...the DALI function if no devi ces have been addressed yet S2 to S8 Module address ISYGLT Parameterisation In the ISYGLT ProgramDesigner there are various parameterisation possibilities grouping of the...

Page 7: ...41 77 77 6 Marktstrasse 57 83646 Bad T lz info seebacher de Fax 49 0 80 41 77 77 2 7 2 pole plug left DALI DALI BUS DALI DALI BUS 3 pole plug right PE Protective conductor L Mains voltage 230V 50 60Hz...

Page 8: ...fo seebacher de Fax 49 0 80 41 77 77 2 8 11 Wiring diagram 230V Article no ISYGLT DALI 16B SL 1 2 3 4 5 6 7 8 BUS address S ON OFF R 2 x P COM DALI max 32 Devices 80027161 L N BUS A BUS B D D PE 230V...

Reviews: