background image

1. Chimney Installation and Draft

 

Chimney systems will only draft properly when they 

are installed according to the instructions, in an appropriate 

location and with the proper chimney height. Installing 

the fireplace according to the instructions, choosing 

an appropriate location, and choosing an appropriate 

chimney height are the responsibility of the designer and 

the building contractor.

 

Tightly insulated and sealed homes, two story interior 

spaces and high vaulted ceilings can cause negative air 

pressures within the house which can impair drafting 

performance. HVAC return air ducts near the fireplace 

opening will adversely affect the fireplace drafting 

performance.

 

It is the responsibility of the designer, the 

building contractor and their mechanical contractor 
to determine that the building’s internal air pressures 
are conducive to positive fireplace drafting.

 

Avoid placing any fireplace in an area near tall trees, 

tall buildings, or high land masses. These structures can 

reduce ambient air flow pressure as well as produce 

down drafts, either of which can impair fireplace drafting 

performance.

 

Earthcore Industries L.L.C. does not warrant 

drafting and is not responsible for it.

2. Fireplace Curing Instructions

 

It is critical that the Isokern masonry elements in the

firebox and smoke dome assembly be dry before firing of 

the unit. Moisture left in the components from exposure 

during storage and shipping, as well as moisture from the 

installation phase, must be eliminated before the unit is 

put to its intended use.

 

The first step in reducing the ambient moisture is to 

be sure that the completed fireplace rest totally in a dried-

in setting for a minimum of 28 days after construction of 

the unit is complete.

 

The next step in curing the fireplace is to be sure that 

the first five or six fires are of short duration.

 

The first fire of the unit can take place once the 

minimum twenty-eight day drying period has passed. This 

fire should be especially short.

 

Start the first fire slowly with a small amount of 

paper and kindling (small dry wood splits or twigs) and 

a maximum load of four to six pounds of dry firewood, 

estimated to be no more than two or three logs each of 

about three inches (3”) to four inches (4”) diameter.

 

The first fire should burn for no more than thirty to 

sixty minutes and then allowed to go out. Do not refuel 

the fireplace during the first lighting.

  A cooling off period of twenty-four hours, at a 

minimum, should follow the first fire.

 

The second fire should be the same as the first fire. It  

should burn for no more than thirty to sixty minutes and 

allowed to go out. Do not refuel the fireplace during the 

second lighting.

Summary

  A twenty-four hour cooling off period must be 

observed following second lighting.

 

After first and second fire, continue use of the unit 

with three or four small fires of short duration (sixty 

minutes or so) and small fuel load.

 

After these first five or six small fires of short duration 

normal use of the fireplace can proceed. For normal 

use the maximum recommended fuel load is twelve to 

sixteen pounds of dry firewood at a time. This fuel load 

is considered to be approximately three to five cured 

hardwood logs of about three inches (3”) to six inches 

(6”) in diameter. As the fire burns down, refueling should 

be only one or two logs added at a time.

IMPORTANT:

 Do not burn construction debris or trash of 

any kind in the fireplace. Whereas it is not uncommon for 

construction debris and refuse to be burned in a fireplace 

by site personnel on a project that is under construction, 

this activity must be avoided. It is the responsibility of 

the building contractor to insure that the required dry-in 

period is met and that the required lighting sequence is 

performed by the owner or by the owner’s agent.

3. Log Grates

  Log grates are required for burning solid fuel in 

the Isokern fireplace. Grates allow for easy air flow up 

through the burning logs thus creating a more complete 

and efficient burning of the fuel.

4. How to Build a Fire

 

First set the fireplace damper in the full open position. 

Begin laying the fire by placing several pieces of wadded 

up paper directly on the log grate. Place kindling (small 

splits of dry pine or other dry softwood) on top of the 

paper, enough to loosely cover the paper. Next arrange 

several small, dry hardwood or softwood logs or log splits 

on top of the kindling layer.

 

Finally, arrange two or three larger hardwood logs 

(oak, hickory, etc.) or log splits on top of the stack.

Ignite the paper at the bottom of the stack. The burning 

paper will ignite the kindling which will, in turn, set the 

remaining fuel on fire.

 

Be sure to stack all firewood in such a way that it will 

settle into the log grate as the paper and kindling layers 

are burned away. Additional logs can be set onto the fire 

as each fueling burns down.

 

Ideally, fuel logs should be of a hardwood species that 

have been air dried for one year or longer. Use of cured 

or uncured pine logs and uncured hardwood logs for fuel 

should be avoided. Pine logs and uncured hardwood 

logs will tend to smolder and burn at relatively low 

temperatures producing high levels of soot and creosote.

IMPORTANT:

 Do not throw, toss, jam, kick or otherwise 

force logs into the Isokern fireplace. 

47

47

Earthcore Industries

 MAGNUM 

 Series Fireplace

Summary of Contents for MAGNUM 82084

Page 1: ...MAGNUM Series Fireplace in a manufactured home or mobile home or recreational vehicle Important This manual contains assembly rules installation steps guidelines use and maintenance instructions for...

Page 2: ...08 28 Assembled MAGNUM 120 29 2 Earthcore Industries MAGNUM Series Fireplace Table of Contents ECO STEEL ECO STEEL Metal Chimney Flue 30 Components List ECO STEEL ECO STEEL Metal Chimney Flue 31 Compo...

Page 3: ...the Isokern fireplace ECO STEEL ECO STEEL chimney system for an indoor application is 18 0 when the chimney is straight and 21 0 when a chimney is offset Earthcore Industries MAGNUM Series Fireplace G...

Page 4: ...nces Always maintain the stated minimum clearances to combustible materials Do not violate any specific installation requirements SEISMIC CODE If you are installing the MAGNUM Series Fireplace in a lo...

Page 5: ...with the MAGNUM Series fireplace system unless written authorization is given by Earthcore Earthcore Industries MAGNUM Series Fireplace Safety Instructions Industries LLC Failure to heed this warning...

Page 6: ...the appliance Toddlers youngchildrenandothersmaybesusceptibletoaccidental contact burns A physical barrier is recommended if there are at risk individuals in the house To restrict access to the firepl...

Page 7: ...nning installation contact your local building official to determine the need to obtain a permit PFS Magnum Listing Label NA PFS EARTHCORE INDUSTRIES MADE IN USA CHESAPEAKE VA 23323 HEADQUARTERS JACKS...

Page 8: ...1 2 A A 710 27 15 16 681 5 26 13 16 533 5 21 640 25 3 16 70 2 3 4 272 5 10 3 4 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 710 27 15 16 533 5 21 681 5 26 13 16 345 13 9 16 FLUE OUTLET 2110 5 83 1...

Page 9: ...MAGNUM Damper Beam Qty 2 75 Isokern MAGNUM Damper Beam Qty 2 25 4 26 25 26 4 35 8 77 8 8 38 77 8 36 4 16 18 Isokern MAGNUM Smoke Dome Qty 2 Isokern MAGNUM Backwall Qty 5 160 Isokern MAGNUM Base Plate...

Page 10: ...5 16 517 20 3 8 571 5 22 1 2 571 22 1 2 571 5 22 1 2 517 20 3 8 640 25 3 16 70 2 3 4 272 5 10 3 4 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 710 27...

Page 11: ...Damper Beam Qty 2 22 1 2 25 1 4 4 25 4 221 2 35 8 77 8 8 38 77 8 18 5 8 4 16 110 SMOKE DOME MIDDLE SMALL 8 MAGNUM QTY 2 18 5 8 4 16 110 Isokern MAGNUM Smoke Dome Qty 2 Isokern MAGNUM Backwall Qty 5 1...

Page 12: ...666 5 26 1 4 533 5 21 653 5 25 3 4 533 5 21 666 5 26 1 4 640 25 3 16 70 2 3 4 272 5 10 3 4 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 345 13 9 16 FLUE OUTLET 710 27 15 16...

Page 13: ...sokern MAGNUM Backwall Qty 5 73 Isokern MAGNUM Backwall Qty 5 114 Isokern MAGNUM Smoke Dome Qty 2 168 Isokern MAGNUM Damper Beam Middle Qty 2 114 SMOKE DOME MIDDLE LARGE 9 MAGNUM QTY 2 30 7 8 4 16 161...

Page 14: ...679 5 26 3 4 645 25 3 8 679 5 26 3 4 670 5 26 3 8 640 25 1 4 70 2 3 4 272 5 10 3 4 345 13 5 8 FLUE OUTLET 345 13 5 8 FLUE OUTLET 345 13 5 8 FLUE OUTLET 345 13 5 8 FLUE OUTLET 3026 119 1 8 528 20 3 4 5...

Page 15: ...Backwall Qty 5 73 Isokern MAGNUM Backwall Qty 5 116 Isokern MAGNUM Smoke Dome Qty 2 170 Isokern MAGNUM Damper Beam Middle Qty 2 116 SMOKE DOME MIDDLE LARGE 10 MAGNUM QTY 2 42 1 2 4 16 162 BACKWALL MID...

Page 16: ...learances to combustible framing and to insulation are maintained throughout the construction of the project subsequent to the installation of the Isokern unit To avoid causing a fire resulting in dam...

Page 17: ...de required non combustible hearth extension finish materials Figures 4 All MAGNUM Series fireplaces shall have hearth extensions of approved non combustible material such as brick tile or stone that...

Page 18: ...s for off grade slabs must be concrete or steel and capable of supporting the slab Isokern unit and the chimney For multi floor and back to back installations proper weight computation on an individua...

Page 19: ...f the Fireplace 4 Rough framing dimension for depth C allows for the required 1 clearance at the back of the Fireplace 29 1 2 is only for an interior wall as most exterior wall framing have insulation...

Page 20: ...int as a sign of complete and proper sealing of the joint On broader contact surfaces it is advisable to apply several additional 1 2 beads of the Earthcore Adhesive to the area to assure proper seali...

Page 21: ...d raised hearth height on the concrete support slab See page 18 When calculating raised hearth height be sure to allow for the three inch 3 thick base plate plus the one and one half inch 1 1 2 thick...

Page 22: ...ox assembly for level by inserting a shim supplied with the unit between the lowest wall component and the top surface of the base plate Any gap created under the wall components during the Shim level...

Page 23: ...it sits on Figure 20 The six 6 lintels when they are put together they will be equal to the width of the fireplace model that they serve Properly placed the lintel is to sit on top of the firebox back...

Page 24: ...ont and rear smoke dome components Earthcore adhesive all contact surfaces thoroughly The smoke dome sloping sidewalls have a beveled bottom edge so that they will sit tight onto the flat top of the d...

Page 25: ...oke dome sloping sidewalls have a beveled bottom edge so that they will sit tight onto the flat top of the damper beam assembly Figure 24 11 Set the top plates into position and Earthcore adhesive on...

Page 26: ...ssembled MAGNUM 84 Part 79L Part 79R Part 34 Part 34 Part M94R Part 162 Part M96 Part 177 Part M90 Part M93 Part 191 Part 162 Part 162 Part 162 Part 17 Part 18 Part 16 Part 17 Part 112 Part 160 Part 1...

Page 27: ...MAGNUM 96 Part 136 Part 36 Part 34 Part 34 Part M94R Part 162 Part 191 Part 36 Part M90 Part M91 Part M93 Part 162 Part 162 Part 162 Part 16 Part 17 Part 16 Part 17 Part 113 Part 160 Part 160 Part 73...

Page 28: ...UM 108 Part 79L Part 177 Part 34 Part 34 Part M94R Part 161 Part M92 Part 177 Part M90 Part M92 Part 192 Part 161 Part 161 Part 161 Part 16 Part 16 Part 16 Part 16 Part 114 Part 72 Part 72 Part 73 Par...

Page 29: ...rt 79R Part 34 Part 34 Part M94R Part 162 Part M93 Part 79L Part M90 Part M92 Part M96 Part 162 Part 162 Part 162 Part 16 Part 16 Part 16 Part 16 Part 116 Part 73 Part 73 Part 71 Part 71 Part 83 Part...

Page 30: ...king tab design DURAVENT A lightweight venting solution created so each section connects securely together This versatile system has a 13 inner diameter and 16 outer diameter and is available in two o...

Page 31: ...ated 30 Degree Offset Stainless Steel 13ACECO30OS 30 Degree Offset 13ACECOFC Chase Top Flashing 13ACECOSC Storm Collar 13NECOAP Insulated Anchor Plate w Damper Stainless Steel 13ACECO12 12 Chimney Sec...

Page 32: ...OP13 WS ECOP13WS SS Wall Band ECOP13 CTC Chase Top Collar ECOP13AC E30 30 Degree Offset ECOP13 CTF Chase Top Flashing ECOP13 CTC Storm Collar ECOP13AC 12 12 Chimney Section ECOP13AC 18 18 Chimney Sect...

Page 33: ...Chimney Section Stainless Steel Component Part Description ECOP13IN KAP Insulated Anchor Plate ECOP13IN KAPD Insulated Anchor Plate w Damper ECOP13IN E15K ECOP13IN E15KSS ECOP13IN E30K ECOP13IN E30KSS...

Page 34: ...the chimney cap can be painted with a high temperature rust proof paint Wash the metal surface with a vinegar and water solution to remove any residue before painting Painting the chimney will help to...

Page 35: ...amper plate in the closed horizontal position Determine and mark the position of the lintel hook The lintel hook should be mounted in a position so as to provide a small amount of tension in the sprin...

Page 36: ...ectly above the opening below The cut opening must be 4 inches larger than the chimney s outside diameter to provide at least a 2 inch clearance all around the chimney The chimney must be centered in...

Page 37: ...nails or screws per bracket A Support Band may be required by some fireplace manufacturers to keep the chimney vertical and help maintain clearances to combustibles within a chase Clamp the Support B...

Page 38: ...8 Elbow Installation 15 and 30 elbows are provided to allow chimneys to avoid framing members or roof peaks A maximum of 30 from vertical is allowed and a total of two elbows for each chimney install...

Page 39: ...ed Figure 37 11 Termination NFPA 211 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appliances states that chimneys shall extend at least three feet above the highest point where it pas...

Page 40: ...when the fireplace is not in use It eliminates the need for glass doors opening up many new design options while allowing for a larger view area of the fire and a more natural look The system consists...

Page 41: ...n air as directly as possible from the fireplace The duct cannot rise vertical higher than the finished opening of the firebox We recommend not to exceed twenty feet 20 of four inch 4 pipe If you requ...

Page 42: ...h a damp sponge to remove dust and loose particles from the interior before installing firebrick Keep the fireplace damp while installing firebrick For Best Results 1 After wet sponged interior of fir...

Page 43: ...stible finished facings are applied Flush Wall Finish Detail This alignment of firebrick application as shown below Figure 45 allows the firebrick lining to be in the same plane with the room s wall f...

Page 44: ...projection Combustible projecting mantles up to twelve inches 12 of projection shall not be placed less than twenty four inches 24 from the top of the fireplace opening Combustible mantles which proje...

Page 45: ...e vents properly upward through the chimney and doesn t create a downdraft that will push the smoke back out of the hearth The use of ECO STEEL ECO STEEL Chimney flue are the flue types for the MAGNUM...

Page 46: ...Sidewall Cavity of Firebox Fill Cavity with f c 2000psi Concrete or Grout PROCEDURE 1 DRILL HOLE OF PROPER DIAMETER AND DEPTH USING A CARBIDE TIPPED DRILL OR CORING BIT AVOID ANY EXISTING REINFORCING...

Page 47: ...urn for no more than thirty to sixty minutes and allowed to go out Do not refuel the fireplace during the second lighting Summary A twenty four hour cooling off period must be observed following secon...

Page 48: ...fire to go out and the ashes to cool for at least six to eight hours After the cooling period carefully pick up the ashes from the firebox with a small metal fireplace shovel or other metal scoop and...

Page 49: ...cal fireplace and chimney cleaners that are poured on a hot fire These can be Summary 49 dangerous and generally work only on the flue section nearest the fire leaving the rest of the flue unaffected...

Page 50: ...ype Circle One Solid Wood Natural Gas Propane Fireplace Serial Number ________________________________________________________________________________ Located on Rating Plate Inside Fireplace Buyer __...

Page 51: ..._______________________ ________________________________________________________________________________________________________ _______________________________________________________________________...

Page 52: ...name address and phone number of the owner and 5 a brief description of the defect Earthcore or any division thereof is not responsible for any labor costs or indirect costs incurred for the replaceme...

Reviews: