background image

SfAR-1M-1AI1DO User Manual

www.ismacontrolli.com

DMP264en | 3rd Issue rev. 1 | 05/2022

page 4 of 19

2  Safety Rules

Improper wiring of the product can damage it and lead to other hazards. Make sure 

that the product has been correctly wired before turning the power on.

Before  wiring  or  removing/mounting  the  product,  make  sure  to  turn  the  power  off. 

Failure to do so might cause an electric shock.

Do not touch electrically charged parts such as power terminals. Doing so might cause 

an electric shock.

Do  not  disassemble  the  product.  Doing  so  might  cause  an  electric  shock  or  faulty 

operation.

Use the product only within the operating ranges recommended in the specification 

(temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure 

to do so might cause a fire or faulty operation.

Firmly tighten the wires to the terminal. Failure to do so might cause a fire.

Avoid  installing  the  product  in  close  proximity  to  high-power  electrical  devices  and 

cables, inductive loads, and switching devices. Proximity of such objects may cause an 

uncontrolled interference, resulting in an instable operation of the product.

Proper arrangement of the power and signal cabling affects the operation of the entire 

control system. Avoid laying the power and signal wiring in parallel cable trays. It can 

cause interferences in monitored and control signals.

It  is  recommended  to  power  controllers/modules  with  AC/DC  power  suppliers.  They 

provide better and more stable insulation for devices compared to AC/AC transformer 

systems, which transmit disturbances and transient phenomena like surges and bursts 

to  devices.  They  also  isolate  products  from  inductive  phenomena  from  other 

transformers and loads.

Power supply systems for the product should be protected by external devices limiting 

overvoltage and effects of lightning discharges.

Avoid  powering  the  product  and  its  controlled/monitored  devices,  especially  high 

power and inductive loads, from a single power source. Powering devices from a single 

power source causes a risk of introducing disturbances from the loads to the control 

devices.

If an AC/AC transformer is used to supply control devices, it is strongly recommended 

to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects, 

which are dangerous for devices.

Long  monitoring  and  control  lines  may  cause  loops  in  connection  with  the  shared 

power  supply,  causing  disturbances  in  the  operation  of  devices,  including  external 

communication. It is recommended to use galvanic separators.

To  protect  signal  and  communication  lines  against  external  electromagnetic 

interferences, use properly grounded shielded cables and ferrite beads.

Switching the digital output relays of large (exceeding specification) inductive loads can 

cause interference pulses to the electronics installed inside the product. Therefore, it 

is recommended to use external relays/contactors, etc. to switch such loads. The use 

of controllers with triac outputs also limits similar overvoltage phenomena.

Many  cases  of  disturbances  and  overvoltage  in  control  systems  are  generated  by 

switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they 

do  not  have  appropriate  built-in  noise  reduction  circuits,  it  is  recommended  to  use 

external circuits such as snubbers, varistors, or protection diodes to limit these effects.

Summary of Contents for SfAR-1M-1AI1DO

Page 1: ...www ismacontrolli com DMP264en 3rd Issue rev 1 05 2022 SfAR 1M 1AI1DO User Manual Expansion Module 1 Analog Input 1 Digital Output ...

Page 2: ...nctions 8 4 4 Communication Settings 9 4 5 Default Settings 9 4 6 Configuration Registers 9 5 Indicators 11 6 Connections 12 6 1 Block Diagram 12 6 2 Power Supply Connection 12 6 2 1 DC Power Connection 12 6 2 2 AC Power Connection 12 6 3 Communication Bus Connection 13 6 4 Connection of Analog Inputs 13 6 4 1 Connection of Voltage Measurement 13 6 4 2 Connection of Current Measurement 13 6 5 Conn...

Page 3: ...of the product without incurring any liability for the purposes of commercial law This information does not discharge you from the liability of your own judgement and verification We reserve the right to change product specifications without notice Please read the instructions carefully and follow the recommendations concluded therein 1 1 Revision History Rev Date Description 3 1 25 May 2022 Rebra...

Page 4: ...phenomena like surges and bursts to devices They also isolate products from inductive phenomena from other transformers and loads Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges Avoid powering the product and its controlled monitored devices especially high power and inductive loads from a single power source Pow...

Page 5: ...s with a twisted pair wire Communication is via Modbus RTU or Modbus ASCII The use of 32 bit ARM core processor provides fast processing and quick communication The baud rate is configurable from 2400 to 115200 The module is designed for mounting on a DIN rail in accordance with DIN EN 5002 The module is equipped with a set of LEDs to indicate the status of inputs and outputs which is useful for d...

Page 6: ...mV Absolute maximum input current 35 mV Current input impedance 100 Ω Current measurement accuracy 0 1 Current input mode 0 20 mV 20 20 mV Max current 20 048 mV Resolution 1 µA Current input mode 4 20 mV Max current 20 048 mV Resolution 1 Measurement resolution 16 bits ADC processing time 70 ms channel Digital Outputs Maximum current and voltage 250 mA 50 V Temperature Work 20 C to 65 C Storage 40...

Page 7: ...ssue rev 1 05 2022 page 7 of 19 Interface RS485 Up to 128 devices Table 2 Technical specification 3 3 Dimensions The appearance and dimensions of the module are shown below The module is mounted directly to the rail in the DIN industry standard Figure 1 Dimensions ...

Page 8: ... signals cable shields should not be interrupted by intermediate terminals the shielding should be earthed directly after the cable enters the cabinet It is recommended to install interference suppressors when switching inductive loads e g coils of contactors relays solenoid valves RC snubbers or varistors are suitable for AC voltage and freewheeling diodes for DC voltage loads The suppressing ele...

Page 9: ...ry is given in the 16 bit registers The access to registers is via Modbus RTU or Modbus ASCII 4 5 Default Settings Parameter Name Value Address 1 Baud rate 19200 Parity No Data bits 8 Stop bits 1 Reply delay ms 0 Modbus type RTU Table 4 Default settings 4 6 Configuration Registers Modbus Address Decimal Address Hex Address Name Values 40002 1 0x01 Address From 0 to 255 40003 2 0x02 Baud rate 0 240...

Page 10: ...page 10 of 19 Modbus Address Decimal Address Hex Address Name Values 40004 3 0x03 Stop Bits 1 one stop bit 2 two stop bits 40004 3 0x03 Data Bits 7 7 data bits 8 8 data bits 40006 5 0x05 Response delay Time in ms 40007 6 0x06 Modbus Mode 0 RTU 1 ASCII Table 5 Configuration registers ...

Page 11: ... Indicator Description ON The LED indicates that the module is correctly powered TX The LED lights up when the unit received the correct packet and sends the answer VIN IIN The LED indicates that the signal to input is connected and is different from 0 DO The LED indicates that the output is on Table 6 Description of indicators ...

Page 12: ...i com DMP264en 3rd Issue rev 1 05 2022 page 12 of 19 6 Connections 6 1 Block Diagram Figure 3 Block diagram 6 2 Power Supply Connection 6 2 1 DC Power Connection Figure 4 DC power connection 6 2 2 AC Power Connection Figure 5 AC power connection ...

Page 13: ...Figure 6 Communication bus connection 6 4 Connection of Analog Inputs 6 4 1 Connection of Voltage Measurement Figure 7 Connection of voltage measurement 6 4 2 Connection of Current Measurement Figure 8 Connection of current measurement 6 5 Connection of Digital Output 6 5 1 PNP Type Figure 9 Connection of PNP type digital output ...

Page 14: ...SfAR 1M 1AI1DO User Manual www ismacontrolli com DMP264en 3rd Issue rev 1 05 2022 page 14 of 19 6 5 2 NPN Type Figure 10 Connection of NPN type digital output ...

Page 15: ...rupted it is possible to eliminate the disruptions by switching the lowpass filter on It is possible to configure the filter for all inputs it is not possible to enable the filter for only one input The filter parameter corresponds to the filter time constant Step response of the filter is shown in the graph below Figure 11 Analog filtering chart ...

Page 16: ... 40010 9 0x09 Filter Read write Measurement filtering value from 1 to 10 40033 32 0x20 Received packets LSR Least Significant Register Read write No of received packets 40034 33 0x21 Received packets MSR Most Significant Register Read write 40035 34 0x22 Incorrect packets LSR Read write No of received packets with error 40036 35 0x23 Incorrect packets MSR Read write 40037 36 0x24 Sent packets LSR ...

Page 17: ...40052 is set 40059 58 0x3A Voltage Alarm Configuration Read write Alarms configuration 0 alarms state depends on actual values 1 alarms state need to clear by master 40060 59 0x3B Current Alarm Configuration Read write 40061 60 0x3C Voltage Input Configuration Read write 0 OFF 1 0 10 V 2 10 10 V 3 0 1 V 4 1 1 V 40062 61 0x3D Current Input Configuration Read write 0 OFF 1 0 20 mA in μA 2 4 20 mA in...

Page 18: ... alarm Table 7 Registered access 8 2 Bit Access Modbus Address Dec Address Hex Address Register Name Access Description 801 800 0x320 Voltage Input Read Voltage input state 802 801 0x321 Current Input Read Current input state 10817 816 0x330 Voltage Alarm Read write Voltage alarm state 10818 817 0x331 Current Alarm Read write Current alarm state 10819 818 0x332 Digital Output Read write Digital Ou...

Page 19: ...dbus network as well as to read and write the current value of other registers of the module It is a convenient way to test the system as well as to observe real time changes in the registers Communication with the module is via the USB cable The module does not require any drivers Figure 12 PC connection The SfAR Configurator is a universal software where it is possible to configure all available...

Reviews: