3 Remote control via interface
3.1 Description of the AIO interface
WARNING!
WARNING!
Before connecting or disconnecting the interface cable, the device must be switched off or disconnected from
the mains.
All analog and digital inputs and outputs are located on the D-SUB 9 connector. This connector has the following pin assignment:
AIO, D Sub 9 Connector
Pin 1
GND
Return of pins 2-9
Pin 2
I
mon
Monitor output current
Pin 3
INHIBIT
Digital input signal
Pin 4
I
set
Nominal value Output current
Pin 5
ON
Digital input signal
Pin 6
Standard version
GND
Return of pins 2-9
Option ARC
ARC
Digital output signal
Pin 7
V
mon
monitor output voltage
Pin 8
V
set
Nominal value Output voltage
Pin 9
V
ref
Reference
Notes:
1)
optional AIO with V
set/mon
and I
set/mon
= 0 to 10V and V
ref
= 10,2V
Table 13: AIO