3.1 Configuration example 1
The machine protective area requires: one field (a protective field and a warning field), the response time of
80ms, automatic reset, external device monitoring (EDM) is disabled.
A new project will be established automatically after the software has been opened. Its default configuration
is: one field (a protective field and a warning field), the response time of 80ms, automatic reset, external
device monitoring (EDM) is disabled.
User only needs to finish the field boundary (ie, guarding field) configuration according to the needs in this
example.
3.1.1 Establish connection between scanner and software
Finish the configuration preparations as described earlier in chapter
3.1
. USB driver only needs to be installed
for the first connection, the scanner can be identified automatically after.
3.1.2 Guard field configuration
3.1.2.1 Switch to Field sets
Switch to the corresponding drawing area through the tree diagram or Field sets tab, as shown in Fig.3.1.2.1.
Fig.3.1.2.1 Drawing area
3.1.2.2 Guarding field setting
3.1.2.2.1 Example 1 of a guarding field
Make a sketch, including measurements, of the area around and in front of the machine that is to be guarded.
Then draw the field boundary in the configuration software according to the actual measurement data.
Drawing tools include Free points, Straight line, Sector, Rectangle and
point editing. Their functions and detailed description can be found in chapter
2.5.5.2.