Use and maintenance manual
15.1
USER INTERFACE
LED
ON (Steady)
FLASHING
OFF
Compressor active
Delay, protection or activation blocked.
Other
Defrosting in progress
Activation manually or from D.I.
Other
Fans active
/
Other
Energy-saving active
Reduced set active
Access to level 2 parameters (Quick flashing)
Other
Presence of alarm
Alarm silenced
Other
Setting in °F (dro = 1)
/
Other
Aux Output active
Deep Cooling cycle active
Aux Output not active
Setting in °C (dro = 0)
/
Other
ALARMS
FAULT
CAUSE
E1
Probe 1
Reading of values outside the operating range
Probe faulty / Short-circuited / Open.
E2
Probe 2 (Defrost)
Reading of values outside the operating range
Probe faulty / Short-circuited / Open.
AH1
HIGH Temperature Alarm Pb1
Value read by Pb1 > HAL after time of tAO.
AL1
LOW Temperature Alarm Pb1
Value read by Pb1 < LAL after time of tAO.
EA
External Alarm
Activation of digital input (H11 = ±5)
OPd
Alarm Door Open
Activation of the digital input (H11 = ±4) for a time greater than tdO
Ad2
End of defrost due to Time-Out
End of defrost by time instead of reaching the
end of defrost temperature detected by Pb2.