IronStrike TAHOMA 2100 Installation And Operation Manual Download Page 10

10

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Termination Cap 

with Spark Arrestor

Remove, if mobile 

home is transported

Storm 

Collar

Flashing

Support

Box

DVL Close 

Clearance 

Connector Pipe

Floor

Protector

3 Feet

Minimum

7 Feet 

Minimum

Double Wall Pipe

Using 6” Diameter Type L-Vent Connector Pipe

Manufactured (Mobile) Home Installation Shown

Figure 8 - Typical Installation

Minimum of 

12-15’ of Flue 

to achieve a 

stable draft.

Fasten each stove pipe 

connection with at least 

3 sheet metal screws.

Mobile home installations 

require a spark arrestor at the 

chimney termination.

All mobile home installa-

tions require an outside 

air kit (see 

Page 24

 for 

ordering information) 

and the stove must be 

secured to the floor and 

grounded to the mobile 

home chassis.

Install Outside 

Air Kits per 

instructions on 

Page 12

INSTALL VENTING SYSTEM PER VENT MANUFACTURERS 
INSTRUCTIONS!

Fasten stove pipe to 

flue collar using 3 

sheet metal screws.

Secure Stove

to floor (2 places)*

Grounded to Steel Chassis using a #8 

AGW copper wire or equivalent.

Chassis

Floor

CHIMNEY INSTALLATION

•  Install chimney as per manufacturer’s instructions. Some brands of 

pipe may require removal of the spacer ring in the flue collar.

•  All horizontal runs of pipe should be as short as possible and are 

required by NFPA No. 211 to have an upward pitch or rise in the same 

direction the smoke travels of no less than 1/4” to the linear foot. The 

connector pipe must meet minimum clearances in any direction to 

walls or other combustible materials. It must attach to a listed double 

wall metal chimney at least 6” in diameter or to a masonry chimney 

with a flue passage of at least 48 square inches.

•  It is required that a chimney connector pipe not extend further than 

the inner wall of the flue when it is connected to a masonry chimney 

and that it either be cemented to the masonry or be installed without 

cement in a thimble connected to the masonry wall. When the 

connector is inserted into a thimble, the joint must be tight enough 

so that it will not be dislodged in normal use. 

•  Chimney connector pipes should never pass through a floor, ceiling, 

fire wall, partition, or combustible construction of any type unless 

certain precautions are taken. The best method is to use a listed 

thimble and a listed chimney in accordance with the manufacturer’s 

directions. NFPA No. 211 gives approved methods for passing a flue 

pipe through combustible constructions 

(see 

Page 11

)

.

Manufactured Home Installations 

(ref. 

Figure 8

)

This appliance is approved for installation into a manufactured 

(mobile) home.

Installation should be in accordance with the Mobile Home 

Construction and Safety Standard, Title 24 CFR, Part 3280 (in 

Canada CAN/CSA Z240 MH), or, when such a standard is not 

applicable, the Standard for Mobile Home Installations, ANSI 

A225.1.

All mobile home installations require an outside air kit (see 

Page 24

 

for ordering information). The stove must be secured to the floor and 

grounded to the chassis of the mobile home.

WARNING:  DO NOT INSTALL IN SLEEPING ROOM OF A MOBILE 

HOME.

CAUTION:  THE STRUCTURAL INTEGRITY OF THE MOBILE HOME 

FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED.

Approved Chimney - 

Your stove is approved for use with Class A, UL 

103 HT (U.S.) / ULC-S629 (Canada) Listed Residential Type and Building 

Heating Appliance Chimney (HT chimney - 2100° Fahrenheit) and double 

wall connector pipe

.  

Approved chimney brands are Security Chimneys™,

 

Jakes Evans/GSW, Dura-vent, Metal Fab, Ameri-Tec, Metalbestos and 

Industrial Chimney (ICC).

Clearances to connector shall be measured from 6” flue collar. Restric-

tions apply! Read instructions before installing.

YOUR CHIMNEY INSTALLATION MUST COMPLY WITH LOCAL 

BUILDING AND FIRE CODES.

Stove

Side View

Rear Pedestal 

Panel

*  Remove rear pedestal panel to access 

holes (indicated by arrows) for securing 

stove to floor.

Summary of Contents for TAHOMA 2100

Page 1: ...en faire la demande Num ro de la pi ce 900189 00 This appliance must be properly installed and operated in order to prevent the pos sibility of a house fire Please read this entire installation and o...

Page 2: ...esting Information 4 Draft Requirements 4 Selecting the Proper Venting System 4 Negative Pressure Warning 5 Clearances to Combustibles 6 7 Floor Protection 6 Chimney and Connector 6 Components 6 Insta...

Page 3: ...g season to check for soot and creosote accumulations Any accumulations over 1 8 thick should be removed by a professional chimney sweep Do not attempt to burn out heavy creosote accumulations with a...

Page 4: ...sary to add additional height to the venting system Do not install an offset within the first two feet above the flue outlet on the appliance In well insulated and weather tight homes it may be diffic...

Page 5: ...d by many common household appliances which exhaust air from the home such as a furnace heat pump air conditioner clothes dryer exhaust fans fireplaces and other fuel burning appliances Also the combu...

Page 6: ...ed for mobile homes but connector pipe may be double wall single wall or single wall with shield as listed above This appliance may be vented into a code approved masonry chimney with flue liner WARNI...

Page 7: ...bile Home 12 9 1 8 19 1 2 9 5 8 8 6 15 37 5 8 46 3 4 34 7 8 16 0 84 57 1 2 305 232 495 245 200 152 381 956 1188 886 406 0 2134 1461 CANADA inches millimeters PIPE INSTALLATION A 3 B 1 C 3 D 1 E 8 F 1...

Page 8: ...rams illustrations and photographs are not to scale consult installa tion instructions Product designs materials dimensions specifications colors and prices are subject to change or discontinuance wit...

Page 9: ...6 Typical Installation Floor Protector Fasten each stove pipe connection with at least 3 sheet metal screws Single wall stove pipe must not pass through attics closets walls or ceilings It is used to...

Page 10: ...ney and that it either be cemented to the masonry or be installed without cement in a thimble connected to the masonry wall When the connector is inserted into a thimble the joint must be tight enough...

Page 11: ...n shall be 12 in 305 mm Chimney section concentric with and spaced 1 in 25 4 mm away from con nector by means of sheet steel support plates on both ends of chimney section Opening shall be covered and...

Page 12: ...Duct length should be kept to a minimum b The air intake register must not be installed more than ten 10 feet 3050 mm above the base of the stove c The fresh air must come from outside the house The a...

Page 13: ...be slightly smaller to adjust for steel and firebrick tolerances beyond our control Be sure to measure and mark bricks with their numbers when removing Warning If the bricks are not installed exactly...

Page 14: ...oards are properly installed FOR YOUR OWN PROTECTION AND INSURANCE PURPOSES HAVE YOUR CHIMNEY AND CONNECTOR PIPE INSTALLATION INSPECTED BY YOUR LOCAL BUILDING CODE AUTHORITY OR FIRE MARSHAL BEFORE STA...

Page 15: ...ly with the door shut tightly at all times except when loading wood and possibly on start up to establish a draft Never leave the unit unattended while the front door is opened 3 DO NOT contact or mov...

Page 16: ...ing appliance it is important to become familiar with how the damper control affects heat output and the overall temperature of the appliance A stove thermom eter can be a helpful tool to help ensure...

Page 17: ...chieve heat output rates that exceed heater design specifica tions can result in permanent damage to the heater Figure 22 Figure 23 OK 4 4 8 Standard Cord of Wood What does Well Seasoned mean When a t...

Page 18: ...need to have sufficient temperatures inside the firebox for thorough combustion The best method for determining if you have sufficient temperatures is to watch the brick lining in your firebox When yo...

Page 19: ...he stove is burned with the blower opening unobstructed Figure 24 The optional blower is controlled by a Dial a Temp see Figure 24 It contains an On Off line switch with variable speed control from lo...

Page 20: ...on ing are similar to the flu with headaches dizziness and or nausea If you have these signs obtain fresh air immediately Some people are more affected by carbon monoxide than others including pregnan...

Page 21: ...a chimney fire THIS WOOD HEATER NEEDS PERIODIC INSPECTION AND REPAIR FOR PROPER OPERATION IT IS AGAINST FEDERAL REGULATIONS TO OPERATE THIS WOOD HEATER IN A MANNER INCONSISTENT WITH OPERATING INSTRUC...

Page 22: ...r to cleaning glass A commercial glass cleaner designed for stoves is recommended Do not use abrasivecleaners Donotcleanwithanymaterials which may scratch or otherwise damage the glass Scratches on th...

Page 23: ...2 3 See Poor Draft section above and Cleaning Glass on Pages 4 and 22 SMOKES WHEN 1 If smoke is entering the room check to make sure your baffle boards are properly installed DOOR IS OPEN 2 Check the...

Page 24: ...ription H8890 Right side heat shield H8891 Left side heat shield H8892 Back heat shield H8893 Door back w pins H8894 Door channels w nuts H8895 Glass H5640 Glass gasket kit 8 4 H5639 Door rope kit 7 8...

Page 25: ...ND UZI UZI Outside Air Ducting Kit includes 4 insulated flex x 10 long AND H8874 OUTAIRKIT ES Outside Air Panel and Air Channel Kit includes rear pedestal panel and side and front air channels MISC H8...

Page 26: ...26 NOTES...

Page 27: ...a binder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly IHP stoves inserts and high efficiency EPA fireplaces are approved for burning d...

Page 28: ...ir parts always give the following information 1 The model number of the appliance 2 The Serial Number of the appliance 3 The part number 4 The description of the part 5 The quantity required 6 The in...

Reviews: