IronStrike Performer ST210 Installation And Operation Manual Download Page 11

11

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Chimney Connector Systems and Clearances from Combustible 

Walls for Residential Heating Appliances (NFPA 211) 

Refer to 

Figure 8

System A.

 Minimum 3.5 in. (90 mm) thick brick masonry wall 

framed into combustible wall with a minimum of 12 in. (305 mm) 

brick separation from clay liner to combustibles. Fireclay liner (ASTM 

C 315, Standard Specification for Clay Flue Linings, or equivalent), 

minimum 5/8 in. (16 mm) wall thickness, shall run from outer surface 

of brick wall to, but not beyond, the inner surface of chimney flue 

liner and shall be firmly cemented in place.
Clearance: 12 in. (305 mm)

System B

. Solid-insulated, listed factory-built chimney length of the 

same inside diameter as the chimney connector and having 1 in. 

(25.4 mm) or more of insulation with a minimum 9 in. (229 mm) air 

space between the outer wall of the chimney length and combustibles.
The inner end of the chimney length shall be flush with the inside of 

the masonry chimney flue and shall be sealed to the flue and to the 

brick masonry penetration with non-water-soluble refractory cement. 

Supports shall be securely fastened to wall surfaces on all sides.
Fasteners between supports and the chimney length shall not pen-

etrate the chimney liner.
Clearance: 9 in. (229 mm)

System C.

 Sheet steel chimney connector, minimum 24 gauge [0.024 

in. (0.61 mm)] in thickness, with a ventilated thimble, minimum 24 

gauge [0.024 in. (0.61 mm)] in thickness, having two 1 in. (25.4 

mm) air channels, separated from combustibles by a minimum of 6 

in. (152 mm) of glass fiber insulation. Opening shall be covered, and 

thimble supported with a sheet steel support, minimum 24 gauge 

[0.024 in. (0.61 mm)] in thickness.
Supports shall be securely fastened to wall surfaces on all sides and 

shall be sized to fit and hold chimney section. Fasteners used to secure 

chimney section shall not penetrate chimney flue liner.
Clearance: 6 in. (152 mm)  

System D.

 Solid-insulated, listed factory-built chimney length with 

an inside diameter 2 in. (51 mm) larger than the chimney connector 

and having 1 in. (25.4 mm) or more of insulation, serving as a pass-

through for a single wall sheet steel chimney connector of minimum 

24 gauge [0.024 in. (0.61 mm)] thickness, with a minimum 2 in. 

(51 mm) air space between the  outer wall of chimney section and 

combustibles. Minimum length of chimney section shall be 12 in. 

(305 mm). Chimney section concentric with and spaced 1 in. (25.4 

mm) away from connector by means of sheet steel support plates 

on both ends of chimney section. Opening shall be covered, and 

chimney section supported on both sides with sheet steel supports 

of minimum 24 gauge [0.024 in. (0.61 mm)] thickness.
Supports shall be securely fastened to wall surfaces on all sides and 

shall be sized to fit and hold chimney section. Fasteners used to secure 

chimney section shall not penetrate chimney flue liner.
Clearance: 2 in. (51 mm)

Additional requirements:

1. Insulation material used as part of wall pass-through system shall be 

of noncombustible material and shall have a thermal conductivity of 

1.0 Btu-in./hr-ft

2

 - ºF (4.88 kg-cal/hr-m

2

 - ºC) or less.

2. All clearances and thicknesses are minimums; larger clearances and 

thicknesses shall be permitted.

3. Any material used to close up an opening for the connector shall be of 

noncombustible material.

4. A connector to a masonry chimney, except for System B, shall extend 

in one continuous piece through the wall pass-through system and the 

chimney wall to the inner face of the flue liner, but not beyond.

Factory Built 

Chimney Length 

Air Space – 9 in. 

(228.6mm) Min. 

Chimney Length 

Flush with 

Inside of Flue 

Min. Clearance 

9 in. (229mm) 

Chimney 

Connector 

Use Chimney 

Mfrs. Parts to 

Attach 

Connector 

Solid-Insulated 

Listed Factory-

Built Chimney 

Length

Sheet Steel Supports

Sheet Steel Supports

Sheet Steel Supports

Minimum Chimney Clearance from Masonry to Sheet Steel 

Supports & Combustibles – 2 in. (51mm) 

Nonsoluble 

Refractory  

Cement

Minimum chimney clearance to sheet

steel supportrs and combustibles

2 in. (51mm)

Chimney 

Connector 

2 Air Channels, Each 1 

in. (25.4 mm) 

2 Ventilated Air 

Channels, Each 

1 in. (25.4 mm) 

Construction of 

Sheet Steel 

Minimum chimney clearance to sheet steel 

supports and combustibles 2 in. (51mm) 

Sheet Steel 

Supports 

Chimney 

Connector 

Chimney 

Section

Air Space – 2 in. 

(51mm) Min. 

Chimney connector  

Chimney length

1 in. (25.4 mm) 

air space to 

        chimney length

Min. Clearance  

2 in. (51 mm) 

Minimum

12 in. (305mm)

to combustibles

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Minimum chimney clearance to brick

and combustibles 2 in. (51mm)

Minimum clearance

12 in. (305mm)

of brick

Chimney

Chimney

flue

Chimney

flue

Chimney

flue

connector

Fire clay

liner

Figure 8 - 

Chimney Connector Systems and Clearances from Combustible Walls

System A

System B

System C

System D

Summary of Contents for Performer ST210

Page 1: ...n faire la demande Num ro de la pi ce 900132 00 This appliance must be properly installed and operated in order to prevent the pos sibility of a house fire Please read this entire installation and ope...

Page 2: ...Negative Pressure Warning 5 Creosote 5 Disposal of Ashes 5 Fuel 5 Paint Curing 6 Burn In Period 6 Clearances to Combustibles 7 8 Floor Protection 7 Reduced Clearances 7 Alcove Clearances 7 Chimney and...

Page 3: ...g season to check for soot and creosote accumulations Any accumulations over 1 8 thick should be removed by a professional chimney sweep Do not attempt to burn out heavy creosote accumulations with a...

Page 4: ...here excessive temperatures are reached beyond the design capabilities of the appliance The damage that occurs from overfiring is not covered under the manufacturer s limited warranty Also see Trouble...

Page 5: ...e heater What does Well Seasoned mean When a tree is cut down the wood is green full of sap and moisture This moisture content can exceed 80 which must be reduced to less than 20 Wood properly seasone...

Page 6: ...lace insert through a regimen of three burns The first two should last for 20 minutes each at 250 degrees the appliance should be allowed to cool completely between each burn The third should be a bur...

Page 7: ...listed above This appliance may be vented into a code approved masonry chimney with flue liner WARNING Chimney connector must be in good condition and kept clean Do not install damaged parts All of t...

Page 8: ...CAN 1048mm USA 16 CAN 450mm USA 0 CAN 200mm Footnotes 1 These dimensions to the stove body are forreferenceonly Actualdistancesshould be measured from the stove s flue collar 2 Minimum noncombustible...

Page 9: ...ure 5 Typical Installation Figure 6 Connected to a Masonry Chimney Floor Protector Floor Protector Fasten each stove pipe connection with at least 3 sheet metal screws Single wall stove pipe must not...

Page 10: ...mination All mobile home installa tions require an outside air kit see Page 29 for ordering information and the stove must be secured to the floor and grounded to the mobile home chassis Install Outsi...

Page 11: ...ll be 12 in 305 mm Chimney section concentric with and spaced 1 in 25 4 mm away from connector by means of sheet steel support plates on both ends of chimney section Opening shall be covered and chimn...

Page 12: ...t and check for any damaged or missing parts If there is hidden damage notify your freight company or IHP dealer immediately CAUTION Wear gloves during installation in case of sharp edges on the stove...

Page 13: ...in that leg as well 9 Install bricks and baffle as per instructions on Pages 15 and 16 It is highly recommended that the baffle be assembled before the chimney is installed so that the baffle blankets...

Page 14: ...chassis with a 8 AGW copper wire or equivalent 11 Install bricks as per instructions on Pages 15 and 16 It is highly recommended that the baffle be assembled before the chimney is installed so that t...

Page 15: ...dimensions on next page to be sure the correct bricks are installed in the correct location 1 Install bricks 1 26 in the numbered sequence shown in Figure 14 on Page 16 NOTE Beforeinstallingyourbaffle...

Page 16: ...y smaller to adjust for steel and firebrick tolerances beyond our control Be sure to measure and mark bricks with their numbers when removing Warning If the bricks are not installed exactly as shown b...

Page 17: ...mometer can be a helpful tool to help ensure you are not over firing your appliance and it will also ensure you are burning fuel at a rate that is most efficient Place a stove thermometer on the top o...

Page 18: ...ot enough to effectively heat the air moved by the blower If the air coming from the blower feels cool one should either decrease the blower speed or stoke the fire to build up more heat NOTE Turn blo...

Page 19: ...to load This indicates the stove is too hot to load for a long burn Also do not load wood for a long burn on a deep bed of hot coals Try stirring the coals a few minutes before loading the stove for a...

Page 20: ...pected at least once a year by a qualified service technician to ensure gaskets air tubes baffles and venting are in good repair to ensure proper performance Have degraded items replaced by a qualifie...

Page 21: ...ld up Higher burns less build up Keep freshly loaded wood away from the glass After reloading allow all the wood to catch flame before dampering down the appliance GLASS REPLACEMENT INSTRUCTIONS Step...

Page 22: ...SMOKES WHEN 1 If smoke is entering the room check to make sure your baffle boards are properly installed DOOR IS OPEN and that the baffle blankets are pushed back flush with the front of the baffle bo...

Page 23: ...for requirements in your area Carbon Monoxide Monitor Recommended Carbon Monoxide Poisoning Early signs of carbon monoxide poison ing are similar to the flu with headaches dizziness and or nausea If y...

Page 24: ...el Olympic Leg H5620 Single Brushed Gold Olympic Leg H5619 Single Brushed Nickel Olympic Leg 22 H5649 Heatshield Leg Fastener Kit 23 71115 Bottom Heatshield ST210 24 H5662 Cascade Olympic Leg Kit Outs...

Page 25: ...25 Replacement Parts Model st210 34 47 48 46 33 35 41 41 45 39 39 43 39 39 39 39 43 39 39 36 40 40 40 40 44 37 38 39 39 39 42 39 39 39 42...

Page 26: ...26 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE Door Parts Blower Parts 7 1 2 3 4 5 6 1 2 3 4 5 9 10 8 14 11 6 7 12 25 29 31 28 27 26 32 30 Replacement Parts Model ST210...

Page 27: ...27 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE Replacement Parts Model ST210 22 24 18 20 21 23 Leg and Leg Parts...

Page 28: ...28 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE Replacement Parts Model ST210 15 18 15 18 19 16 17 19 Ash Drawer Pedestal and Pedestal...

Page 29: ...ANDLE AND NAMEPLATE F1867 ARCH FPK BG Arch Faceplate Brushed Gold F1866 TRAD FPK BG SM Sm Traditional Faceplate Brushed Gold F1865 ARCH FPK G Arch Faceplate Gold F1864 TRAD FPK G SM Traditional Facepl...

Page 30: ...30 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE NOTES...

Page 31: ...a binder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly IHP stoves inserts and high efficiency EPA fireplaces are approved for burning d...

Page 32: ...pair parts always give the following information 1 The model number of the appliance 2 The Serial Number of the appliance 3 The part number 4 The description of the part 5 The quantity required 6 The...

Reviews: