IronStrike BELLEVUE 27 Installation And Operation Manual Download Page 22

22

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Pre-Lighting Checklist

Be sure to check these items before the initial lighting of the insert:

Gas pressure has been checked carefully - see Page 20.

All gas fittings have been checked for leaks.

All clearances to combustibles have been met-see Page 14.

All combustible materials have been removed from the area 
in front of the insert.

All vented areas of the insert face are unobstructed.

House is ventilated to clear initial paint curing odors - see 
Page 23.

All packaging materials have been removed from the firebox.

Firebox liner panels and log set have been installed.

The glass door is in place and is properly sealed.

The accent light bulb has been installed.

Operating Instructions

See lighting instructions on  Page 38.

OPERATION

Intermittent/Standing Pilot Mode

This appliance can be switched from intermittent ignition to a standing 

pilot (see Figure 23). The IPI/CPI rocker switch is located at the bottom 

of the left Full Front Facade panel (OFF [o]= Intermittent Pilot Mode and 

ON [-] = Standing Pilot Mode). To save energy, switch to intermittent 

mode.  To have a standing pilot which will help startup during cold climate 

conditions by warming the flue and the glass, switch to standing pilot.  
The standing pilot mode is indicated by a pilot that comes on and remains 

lit when the fireplace is off.

Control switches and the blower speed control knob (rheostat) 

are mounted on the outside edge of the left side of the Full 

Front Facade as shown below.

ON/OFF Switch turns the burner 

on and off.

Hi-Low Switch controls the main 

burner flame height.

Pilot (IPI/CPI) Switch is for stand-

ing pilot mode [IPI -] or Intermittent 

pilot mode [CPI o].

Pair Remote (Learn Switch) is for 

programming the optional remote 

control (see instructions provided 

with the remote control).

On/Off Blower Speed Control Knob 

turns the blower on and off and 

controls the speed of the blower.

Room Air Circulation Blower

Plug in the three-prong power cord into the provided J-Box/Receptacle 

(see Figure 22). Do not cut or remove the grounding prong from the 

power cord.

The blower ON/OFF-Speed control switch is located on the left side Full 

Front Facade.  

W

GR

120 V

AC

BK

BK

R

Figure 22 - Blower / J-Box

Standard Blower

Standard J-Box

Blower ON/OFF-Speed Control 

Switch (rheostat) on Full Front Facade

Figure 23 - Control Switches on Left Side Full Front Facade

BK  = Black
R  = Red
W   = White
GR = Green

Summary of Contents for BELLEVUE 27

Page 1: ...gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety...

Page 2: ...VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude et doit tre install pour...

Page 3: ...o Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio Mantenga la ropa mobiliario gasolina y otros l quidos inflamable...

Page 4: ...eatures 12 Packaging List 12 Ratings 12 Insert and Fireplace Dimensions 13 Clearances to Combustibles 14 Insert Leveling 14 Installation 15 21 Venting Installation 15 USING THIS MANUAL Please read and...

Page 5: ...ls viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le installez une ba...

Page 6: ...r liminerlapoussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque du r cepteur mural qui contr le le foyer Figure A Choisissez la langue qui est principalement par...

Page 7: ...Collezl tiquettesurlebo tier de la t l commande Figure B Choisissez la langue qui est principalement parl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 3 Si vous ne...

Page 8: ...anemia those under the influence of alcohol and those at high altitudes Turn off gas and electrical power to the appliance and allow it to cool before cleaning or servicing the appliance If the barri...

Page 9: ...dition and will void the warranty Please carefully read the sections pertaining to these subjects and or be sure your appliance is properly equipped Never use solid fuels such as wood paper cardboard...

Page 10: ...l wood burning fireplace listed to UL 127 or ULC S610 only All exhaust gases must be vented outside the structure Combustion air is drawn from outside the structure When installing in a factory built...

Page 11: ...een tested and certified to ANSI Z21 88 CSA 2 33 Standard for Vented Gas Fireplace Heater and CAN CGA 2 17 M91 and UL 307B Gas Burning Heating Appliances for Manufactured Mobile Homes in both USA and...

Page 12: ...a specified elevation Only IHP conversion kits can be used to convert from NG to LP or LP to NG Contact your IHP dealer for details PRE INSTALLATION RATINGS Bellevue 27 Bellevue 32 NATURAL GAS LP GAS...

Page 13: ...Dim Description Bellevue 27 Bellevue 32 A Front Opening Width 27 686mm 32 813mm B Height 18 457mm 19 1 2 495mm C Rear Width 17 432mm 22 559mm D Fireplace Depth 15 381mm 16 406mm Model A B C D E F G H...

Page 14: ...and the minimum projection of the hearth extension Figure 4 Bellevue 27 32 Clearances MINIMUM CLEARANCES MINIMUM CLEARANCES TO COMBUSTIBLES Bellevue 27 32 A Mantel 32 813mm B Side Wall 4 102mm C Mante...

Page 15: ...hould be used for correct operation Liner Requirements Use 3 77 mm diameter listed gas vent liner UL1777 ONLY for the EXHAUST Use 3 77 mm diameter listed liner UL 181 or UL1777 for the AIR INTAKE Figu...

Page 16: ...mm or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship like manner This access hole must be plugged with a non combustible insulation after the gas supply l...

Page 17: ...the openings on the side mounting brackets on the appliance see Figure 9 Figure 9 A Openings where hooked brackets on Full Front Facade will hang B Side Mounting Brackets on appliance A A B B A A Inst...

Page 18: ...ure 11 4 Position the separated glowing embers over the small holes on the burner surface Figure 12 Do NOT cover the large burner slots NOTE Enough glowing ember material is provided for several appli...

Page 19: ...14B Place embers and other media see Page 18 Figure 14A Locate the log placement tabs BV27 Figure 14B Locate the log placement tabs BV32 Figure 15 Place log 1 4 Position the left front log 2 on the le...

Page 20: ...ave step down regulators to reduce the pressure to safe levels Check the taps for gas leaks with a gas leak test solution retighten if necessary LP and Natural Gas Supplies This appliance is equipped...

Page 21: ...the adjustment lever side to side see Figure 20 CAUTION The air shutter should never be set so as to make the tips of the flames sooty or create sooting on the viewing glass logs or heat exchanger If...

Page 22: ...o intermittent mode Tohaveastandingpilotwhichwillhelpstartupduringcoldclimate conditions by warming the flue and the glass switch to standing pilot The standing pilot mode is indicated by a pilot that...

Page 23: ...cessivetimesfortenminutes each time with a five minute cool down between each firing Ventilate the house during these first firings as the paint gives off an unpleasant odor It is recommended that per...

Page 24: ...odule Inlet Inlet To Pilot Igniter From Pilot Thermocouple 7 5VDC 1 Amp Adaptor Burner On Off brown Hi Lo blue IPI Cont Pilot yellow Learn black Thermocouple To S Terminal on Main Module Battery Motor...

Page 25: ...e o Checkthatthechimneyanditsoutletareopenandfreeofsoot block age or debris The venting system should be periodically examined by a qualified agency o Check gaskets once a year Gaskets must be tight R...

Page 26: ...verse order WARNING Do not attempt to substitute the materials used on these doors or replace cracked or broken glass Handle this glass with extreme care Glass is susceptibletodamage Donotscratchorhan...

Page 27: ...latest edition or the Canadian Electrical Code Part 1 CSA C22 1 latest edition see Operating Options Figure 23 Page 22 Blower Assembly Fireplace Insert Back Repair If the glass is broken in the glass...

Page 28: ...ks from the mounting slots on the unit 3 Place the Full Front Facade face down on a soft non abrasive surface to prevent damage 4 Remove barrier from Full Front Facade a Using a 3 8 nut driver remove...

Page 29: ...TLET VENTS See Firebox Liner Kit and Log Set Installation on Pages 17 19 The main Burner comes on but then goes out Gas is not reaching the appliance Loose wires to the valve or ignition module Pilot...

Page 30: ...ow RF Control Module F2694 50 Rocker Switch IPI CPI Hi Lo Burner On Off F3182 51 Rocker Switch Momentary Learn F2964 Item Description Cat No 1 Firebox Door Assembly with Glass H9174 2 Gas Train Assemb...

Page 31: ...31 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS BELLEVUE 27 50 51 18 10 11 14 14 5 8 9 19 20 1 15 6 7 21 16 17 28 41 49 13 40 25 43 32 2...

Page 32: ...4 14 Full Front Facade Mounting Bracket Kit set of two H9178 15 Refractory Panel Retaining Bracket Kit two sets one of each style J7596 16 90 Elbow Brass 3 8 Tube x 3 8 NPT J7701 17 Battery Holder J79...

Page 33: ...33 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS BELLEVUE 32 2 50 51 52 40 25 13 49 43 41 16 17 28 10 11 1 5 6 7 8 9 14 15 21 19 14 20...

Page 34: ...Surround Trimmable 46 W x 38 H Ecoflow Control Kits F2687 EF BRCK Basic Remote Control On Off IPI CPI F2660 EF WWRCK Wireless Wall Switch On Off High Low ON OFF HI LO ON OFF HI LO PILOT Continuous Ba...

Page 35: ...coflow Control Kits F2687 EF BRCK Basic Remote Control On Off IPI CPI F2660 EF WWRCK Wireless Wall Switch On Off High Low ON OFF HI LO ON OFF HI LO PILOT Continuous Basic Remote Wireless Wall Switch D...

Page 36: ...ELECTRICAL RATING 120 VAC 60 HZ LESS THAN 2 AMPS CHIMNEY USE 3 76 MM GAS VENT FLEX CHIMNEY LINER LISTED TO UL 1777 OR ULC S635 THIS APPLIANCE MUST BE PROPERLY CONNECTED TO A VENTING SYSTEM IN ACCORDAN...

Page 37: ...610 M 38 101 53 0595 UNIT FACTORY EQUIPPED FOR 0 2000 FT 0 610 M IN CANADA 0 4500 FT 0 1370 M ELECTRICAL RATING 120 VAC 60 HZ LESS THAN 2 AMPS CHIMNEY USE 3 76 MM GAS VENT FLEX CHIMNEY LINER LISTED T...

Page 38: ...t try to light the pilot by hand B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHA...

Page 39: ...cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instruct...

Page 40: ...ur IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the appliance 2 The seri...

Reviews: