background image

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Tumblers – 50 and 75

16

4-08-44

Figure 4 

TMB2019N

1

NOTE: Where the exhaust duct pierces a 
combustible wall or ceiling, the opening 
MUST be sized per local codes.

2

Outlet duct diameter

3

45° typical

L

K

J

I

H

G

F

E

D

C

B

A

3

1

2

ONE MANIFOLD ASSEMBLY

Duct Station

8 in. (203 mm) Duct

A

8 in. (203 mm)

B

12 in.

 

(305 mm)

C

15 in.

 

(381 mm)

D

17 in.

 

(432 mm)

E

19 in.

 

(483 mm)

F

21 in.

 

(533 mm)

G

23 in.

 

(584 mm)

H

25 in.

 

(635 mm)

I

26 in.

 

(660 mm)

J

27 in.

 

(686 mm)

K

29 in.

 

(737 mm)

L

30 in.

 

(762 mm)

Table 2 

Summary of Contents for IPD50E2-IT050E

Page 1: ...Refer to Installation manual for full instructions 4 08 44R3 June 2011 On Premise Laundry Planning Handbook 50 and 75 Pound Tumblers Through Serial No 0904002963 TMB795C TM795C ...

Page 2: ...ntents Tumblers 50 and 75 2 Introduction 2 Model Identification 2 Specifications and Dimensions 4 Cabinet Dimensions 5 Exhaust Outlet Locations 6 Gas Connection Locations 7 Electrical Connection Locations 8 Steam Connection Locations 9 Installation 10 Pre Installation Inspection 10 Tumbler Enclosure 11 Exhaust Requirements 12 Layout 12 Make Up Air 12 Venting 12 Individual Venting 13 Manifold Venti...

Page 3: ... TMB795C TMB795C Gas Steam Thermal Oil Electric 50 Pound IPD50G2 IT050L IPD50G2 IT050N IPD50S2 IT050S IPD50S2 IT050T IPD50E2 IT050E 75 Pound IPD75G2 IT075L IPD75G2 IT075N IPD75S2 IT075S IPD75S2 IT075T IPD75E2 IT075E 3V DX4 vended QT dual digital timer SD single drop 3X DX4 prep for coin RD reversing DMP OPL SX single drop prep for coin DO DMP OPL RQ reversing dual digital timer ...

Page 4: ... W 15 0 1 1 Conversion Table Multiply By To Obtain Multiply By To Obtain Btu 0 252 kCal Pounds sq inch 0 06895 Bars Btu 1055 Joules Pounds sq inch 0 070 kg sq cm Inch 25 4 Millimeters Pounds lbs 0 454 Kilograms Inches W C 0 036 Pounds sq inch Boiler Horsepower 33 479 Btu hr Inches W C 0 249 kPa Boiler Horsepower 34 5 lbs steam hr lb inch2 psi 6 895 kPa CFM 0 471 liters second ft3 28 32 Liters kW 3...

Page 5: ... 75 34 Air Outlet Diameter Inches mm 8 203 8 203 Maximum Static Back Pressure W C I mbar 0 5 1 3 0 5 1 3 Maximum Airflow C F M L sec 750 354 Gas Steam 60 Hz 920 434 Gas Steam 50 Hz 750 354 Electric 750 354 Motor Horsepower Nonreversing Reversing Fan Cylinder 1 2 1 3 1 3 3 4 1 3 1 3 Gas Models Gas Connection 1 2 in NPT 1 2 in NPT Gas Burner Rating Btu hr0 Mj hr 120 000 126 6 165 000 174 1 Electric ...

Page 6: ...n 860 mm 47 in 1194 mm 76 625 in 1946 mm 38 625 in 981 mm 33 in 838 mm 29 5 in 749 mm 50 Pound Steam 30 75 in 781 mm 28 75 in 730 mm 28 25 in 717 mm 33 87 in 860 mm 47 in 1194 mm 80 in 2032 mm 38 625 in 981 mm 33 in 838 mm 29 5 in 749 mm 75 Pound Gas and Electric 30 75 in 781 mm 28 75 in 730 mm 28 25 in 717 mm 33 87 in 860 mm 53 in 1346 mm 76 625 in 1946 mm 38 625 in 981 mm 33 in 838 mm 35 5 in 90...

Page 7: ... Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Tumblers 50 and 75 6 4 08 44 Exhaust Outlet Locations TMB811N A B C A B C 5 375 in 137 mm 8 in 203 mm 13 375 in 340 mm ...

Page 8: ...y Systems LLC DO NOT COPY or TRANSMIT Tumblers 50 and 75 4 08 44 7 Gas Connection Locations TMB812N A B Models Diameter A B 50 Pound 1 2 in NPT 15 5 in 394 mm 65 75 in 1670 mm 75 Pound 1 2 in NPT 15 75 in 400 mm 65 75 in 1670 mm ...

Page 9: ...RANSMIT Tumblers 50 and 75 8 4 08 44 Electrical Connection Locations TMB813N TMB813N GAS AND STEAM ELECTRIC A B B A Models A B Gas and Steam 9 5 in 241 mm 63 5 in 1613 mm Electric 19 in 483 mm 64 in 1626 mm NOTE These figures are approximate dimensions only ...

Page 10: ...liance Laundry Systems LLC DO NOT COPY or TRANSMIT Tumblers 50 and 75 4 08 44 9 Steam Connection Locations TMB814N C A B D Diameter A B C D 3 4 in NPT 15 25 in 387 mm 72 75 in 1848 mm 7 5 in 190 mm 64 75 in 1645 mm ...

Page 11: ...ossible and check the items listed on the packing list Advise the carrier of any damaged or missing articles as soon as possible A written claim should be filed with the carrier immediately if articles are damaged or missing IMPORTANT Warranty is void unless tumbler is installed according to instructions in this manual Installation should comply with minimum specifications and requirements detaile...

Page 12: ...le trim piece may be used to conceal the opening zero clearance allowed for trim 3 4 in 102 mm maximum header thickness 4 12 in 305 mm minimum clearance permitted for remainder 5 Guard 6 Provision for make up air 7 24 in 610 mm minimum 36 in 914 mm recommended for maintenance purposes 8 0 25 in 6 mm recommended for removal or installation purposes zero clearance allowed TMB2131N 3 1 4 5 6 7 2 WARN...

Page 13: ... and may void machine warranty For maximum efficiency and minimum lint accumulation tumbler air must be exhausted to the outdoors by the shortest possible route Proper sized exhaust ducts are essential for proper operation All elbows should be sweep type Exhaust ducts must be assembled so the interior surfaces are smooth so the joints do not permit the accumulation of lint DO NOT use plastic or th...

Page 14: ...E Static back pressure must be measured with the tumbler running The maximum allowable length venting of the same diameter as the exhaust thimble is 14 feet 4 3 m and two 90 elbows or equivalent If the equivalent length of a duct required for an installation exceeds the maximum allowable equivalent length the diameter of a round duct must be increased by 10 for each additional 20 feet 6 1 m Cross ...

Page 15: ...t be sized per local codes NOTE Inside of duct must be smooth Do not use sheet metal screws to join sections Consult your local building code for regulations which may also apply TMB2103N 1 Removable strip of panel in framing wall to permit removal of tumbler from framing wall 2 Partition or bulkhead 3 Minimum distance between exhaust opening and roof ground or other obstruction 36 in 914 mm 4 2 i...

Page 16: ...s not reduced Provisions MUST be made for lint removal and cleaning of the collector duct The vent collector system must be designed so the static back pressure measured 12 inches 305 mm from the exhaust outlet does not exceed the maximum allowable pressure specified on the installation sticker on the rear of tumbler Static back pressure must be measured with all tumblers vented into the collector...

Page 17: ...e wall or ceiling the opening MUST be sized per local codes 2 Outlet duct diameter 3 45 typical L K J I H G F E D C B A 3 1 2 ONE MANIFOLD ASSEMBLY Duct Station 8 in 203 mm Duct A 8 in 203 mm B 12 in 305 mm C 15 in 381 mm D 17 in 432 mm E 19 in 483 mm F 21 in 533 mm G 23 in 584 mm H 25 in 635 mm I 26 in 660 mm J 27 in 686 mm K 29 in 737 mm L 30 in 762 mm Table 2 ...

Page 18: ...ling the opening MUST be sized per local codes 2 Outlet duct diameter 3 45 typical 1 2 3 L K J I L K J I CONTINUE TO A CONTINUE TO A TWO MANIFOLD ASSEMBLIES Duct Station 8 in 203 mm Duct A 13 in 330 mm B 17 in 432 mm C 18 in 457 mm D 24 in 610 mm E 27 in 686 mm F 30 in 762 mm G 33 in 838 mm H 34 in 864 mm I 37 in 940 mm J 39 in 991 mm K 40 in 1016 mm L 42 in 1067 mm Table 3 ...

Page 19: ... and causing premature failure of the motor s 7 Serial Plate Rating Terminal Block Connections Required Serial Plate Amps Recommended Circuit Nonreversing Reversing Breaker Rating Wire Size AWG mm2 120V 60Hz 1ph L1 Neutral and ground 9 3 N A 15A 1 pole 14 2 08 200 208V 60Hz 1ph L1 Neutral and ground 5 1 N A 10A 1 pole 14 2 08 200 208 240V 60Hz 1ph L1 L2 and ground 5 1 N A 10A 2 pole 14 2 08 230 24...

Page 20: ...le phasing and causing premature failure of the motor s Serial Plate Rating Terminal Block Connections Required Serial Plate Amps Recommended Circuit Nonreversing Reversing Breaker Rating Wire Size AWG mm2 120V 60Hz 1ph L1 Neutral and ground 13 8 N A 20A 1 pole 12 3 31 200 208V 60Hz 1ph L1 Neutral and ground 7 6 N A 15A 1 pole 14 2 08 200 208 240V 60Hz 1ph L1 L2 and ground 7 6 N A 15A 2 pole 14 2 ...

Page 21: ...d to its own individual branch circuit breaker not fuses to avoid the possibility of single phasing and causing premature failure of the motor s Serial Plate Rating Terminal Block Connections Required Serial Plate Amps Recommended Circuit Nonreversing Reversing Breaker Rating Wire Size AWG mm2 240V 50Hz 1ph 50 Pound only L1 Neutral and Ground 93 95 125A 1 pole 1 42 4 200 208V 60Hz 3ph L1 L2 L3 and...

Reviews: