Installation

Drainage connection

The cabinet should be placed so that the discharge water 
can flow freely from the discharge pipe to the floor drain 
or some other drainage system.

Refrigerant connection

Connect Refrigerant pipes to the central cooling system
or compressor pedestal (S501400001). The coolant
used should be R134a. Pipe dimensions, suction pipe
Ø5/8” and fluid pipe Ø1/4”. The evaporation temperature
should be between –5 and –10°C, overheating 3-
8°C. The cooling components are pressure tested at
1820 kPa (18.2.bar).

Testing

The Selector switch in position 1:

·  Both fans start at low speed..
·  The steam generator is emptied, before being refilled.
·  After 5 min. voltage is supplied to the cooling circuit’s 

solenoid valve and the cabinet temperature is lowered 
to 36°F(+2°C).

The Selector switch in the cleaning position: 

·  Both fans start at high speed.
·  The steam generator is emptied, before being refilled.
·  The steam generator and the air heater start to give off 

heat.

Note! The Selector switch should be allowed to stand for 

at least 3 min. in one position before being changed to 
the other. (See Operation manual)

Accessories

See the Operation manual.

Other documentation

Manufacturer’s Declaration 
Operation manual
Electrical diagram
Refrigeration flow chart 
Service Instructions* 
Spare Parts Catalogue*

* Not supplied. May be ordered from the manufacturer or manufacturer’s 
representative.

Placement

Leave the packaging on the cabinet during handling until 
the cabinet is in place. (This is to reduce the risk of dam-
age to the large side panels.) The floor under the cabinet 
may have a drop of max. ±1°. The cabinet should be po-
sitioned so that the waste water can flow freely from the 
discharge pipe to the drain in order to minimise the risk of 
slipping. Check that the cabinet is stable. 
Note: the cabinet shall be welded on to a foundation. 
Make sure that the cabinet is installed in level and that 
the door closes in a proper way after welding.

 

Electrical connection

Electrical connection work must be carried out in ac-
cordance with all relevant standards and regulations. 

 

On installation, the machine must be connected via a main 
circuit breaker to keep it separate from the mains, with a 
break length of at least 3 mm. Not included in the delivery.
·  Check the rating plate to ensure that the machine’s op-

erating voltage matches the mains voltage.

·  Check that the distribution box is capable of carrying the 

required current and that it is adequately earthed.

·  Both the power and pilot circuit (where appropriate) 

should be fused. The fuses should have the required 
rated current in order to deliver the required power to 
the cabinet.

·  The connection cable must have suffitient length in order 

to be able to fold the electrical box forward.

·  If you are in any doubt about the effectiveness of the 

earthing provisions then the installation must be checked 
by a qualified electrician.

·  Connect the electrical cables as indicated by the cable 

markings and wiring diagram.

·  The connection cable must be oil resistant, class:
 H07RN-F.
·  Once the machine has been connected and switched 

on, you should check that the mains voltage does not 
fluctuate more than 10% from the rated voltage.

Water connection

Cold water with min. pressure 100 kPa (1 bar), max. pres-
sure 700 kPa (7 bar) and min. flow capacity 0.1 m

3

/h. DN15 

(G 1/2”) int. thread. Incoming water pipe should be fitted 
with a shut off valve. Connected water should be decalci-
fied.
Basic adjustment of the radiator coupling
Open the valve extremely little. The flow have to be 1 l /
min. 

Summary of Contents for Tina 1200RU

Page 1: ...Thawing cabinet Tina 1200RU Installation Instructions Made in Sweden by DOC NO STO 9170 02 EDITION 1 2014 11 ...

Page 2: ...ngsås Sweden Phone 46 322 668930 Fax 46 322 10870 E mail info steeltech se www steeltech se Contents Page General instructions 3 Installation 4 Electrical connection 4 Water and drainage connection 4 Refrigerant connection 4 Testing 4 Technical specification 5 6 ...

Page 3: ...the rear of the electrical cabinet as well as on the EU declaration which accompanies the machine on delivery Noise level 70 dB A Enclosure class IPX4 General instructions If the instructions in this and other documentation for the equipment are not followed it could endanger safety and void the supplier s guarantee and liability for the product Read the instructions in this document carefully sin...

Page 4: ... can flow freely from the discharge pipe to the drain in order to minimise the risk of slipping Check that the cabinet is stable Note the cabinet shall be welded on to a foundation Make sure that the cabinet is installed in level and that the door closes in a proper way after welding Electrical connection Electrical connection work must be carried out in ac cordance with all relevant standards and...

Page 5: ...nnection DN20 G 3 4 ext thread Electrical connection Drainage Refrigerant connection suction pipe Ø 5 8 1 2 3 4 5 Display Target temperature 6 7 Selector switch Cleaning 0 Thawing Deliming tube 8 9 Display Cabinet temperature 1 2 3 5 8 6 7 1 2 4 5 4 9 ...

Page 6: ...Cooling system Remote Central cooling Total Power kW 4 Compressor output kW Max phase current A 9 1 Productivity per cycle kg 150 Refrigerant R134a Refrigerant weight g _ Cooling Power kW 1 5 Evaporation temperature C _ Total weight kg 250 Volume litre 1200 Door hung Right ...

Page 7: ...7 ...

Page 8: ...8 iPinium AB Box 2105 S 612 22 Finspång Sweden Tel 46 122 135 84 Fax 46 122 444 001 E post info iPinium se www iPinium se ...

Reviews: