Adjustment and programming
On delay:
1. Connect the sensor with the M12-
socket of the
time module and switch on the operating voltage.
The connection can be made by a 4-wire cable socket, e.g. VK200321.
2. Connect the teach input A (PIN 2, white) to +U
B
(PIN 1, brown).
3. Activate the sensor. The time the sensor is activated corresponds to the delay at a later time.
4. Release the teach-
input from +U
B
.
Off delay:
1. Connect the sensor with the M12-
socket of the
time module and switch on the operating voltage.
The connection can be made by a 4-wire cable socket, e.g. VK200321.
2. Activate the sensor.
3. Connect the teach input A (PIN 2, white) with +U
B
(PIN 1, brown).
4. Disconnect the sensor. The time the sensor is not activated corresponds to the delay at a later
time.
If you wish an off delay of 4s
, disconnect
the sensor for
4s and activate it again.
5. Disconnect the teach-
input from +U
B
.
Reset to factory settings:
Connect the teach input A (PIN
2, white) for at least 10s to
+U
B
(PIN 1, brown). During this time
the sensors’s state must not be changed! The device operates now with an off delay
of
100ms.