Anzeigen und Bedienelemente
H1:
Schaltzustands- / Senderfehler-Anzeige
- gelb
H2:
Empfindlichkeits- / Empfängerfehler-Anzeige
- grün
H3:
Alarmanzeige
- rot
H4:
Sensor-Fehleranzeige
- rot
H5:
Betriebsanzeige
- grün
P1:
Empfindlichkeitseinsteller für Manuell-Betrieb
S1 - S4: DIP-Schalter
S5:
Test / Reset-Taster
•
Display content and operating elements
H1:
Switching indicator / Transmitter error display
- yellow
H2:
Sensitivity display / Receiver error display
- green
H3:
Alarm display
- red
H4:
Sensor Error display
- red
H5:
Power ON display
- green
P1:
Manual Gain control
S1 - S4: DIP-switch
S5:
Test / Reset-Taster
H1
H2
H3
H4
P1
S5
S1 - S4
TEST/RESET
OUTPUT-
STATUS
GAIN-
CONTROL
ALARM
ON
high
manual
low
automatic
dark
f1
light
f2
MANUAL
GAIN
SENSOR
ERROR
AMPLIFIER MODE
IT
IR
1-CHANNEL
INFRARED-AMPLIFIER
H5
•
Inbetriebnahme
Vor Inbetriebnahme DIP-Schalter S1 - S4 am Gerät passend einstellen. Sensoren auf-
einander ausrichten. Nach Anlegen der Betriebsspannung und automatischem Reset,
stellt sich in der Betriebsart
Automatik
die Sendeleistung selbstständig ein. Bei fehler-
freiem Betrieb leuchtet H2 auf (Automatik aktiv). Gleichzeitig leuchtet in Hellschaltung
H1. In der Betriebsart
Manuell
muss der Anwender die Sendeleistung mit P1 auf die
erforderliche Höhe bringen, sodass bei Sichtverbindung H2 leuchtet. In Hellschaltung
leuchtet auch hier gleichzeitig H1 (siehe
Tabelle: Schaltlogik
).
•
- Alarm - mit Alarmausgang
Der Alarmzustand tritt ein, wenn die Sendeleistung im Manuell-Betrieb nicht ausreichend
ist, oder im Automatik-Betrieb der Prozessor nicht mehr nachregeln kann. Ursache
ist z. B. eine Verschlechterung der Sicht, eine zu große Distanz oder Dejustage der
Sensoren. Nach Beseitigung des Fehlers erlischt die Anzeige.
•
Analogausgang
Am Ausgang liegt, je nach Übertragungsqualität eine Spannung 0...10 V DC an. So
lassen sich z. B. die Sensoren ausrichten, oder Veränderungen messbar machen.
•
Testeingang und - Test -
(unterschiedliche Funktionen)
Legt man an den Testeingang 24 V DC an, so schaltet der Sender ab. So kann die
Funktion der Lichtschranke überprüft werden. Durch kurzes Drücken von S5 - Funktion
Test - wird die Streckenqualität durch Blinken von H2 (1x - schlecht bis 10x - sehr gut)
angezeigt. Ist keine Sichtverbindung vorhanden, blinkt lediglich H4.
•
- Reset -
Nach Anlegen der Betriebsspannung oder durch Drücken von S5 führt das Gerät einen
Reset durch. Der Reset beinhaltet einen Lampentest. Alle Anzeigen erlischen und
leuchten danach kurz auf. Zusätzlich findet im Automatik-Betrieb eine automatische
Neuregelung der Sendeleistung vom Maximalwert auf den Sollwert statt.
•
- Sensor Error -
Mit der Sensor Error-Funktion überwacht das Gerät den elektrischen Zustand der Sen-
soren auf Kurzschluss und Unterbrechung. Tritt ein Fehler auf, so meldet dies das Gerät
durch die Anzeigeelemente. Schnelles Blinken bedeutet Kurzschluss und langsames
Blinken bedeutet Unterbrechung (siehe Tabelle
Logik Sensor Error
).
•
Operating procedure
Before operating procedure you have to choose the DIP switch setting S1 - S4 for your
application. Sensor heads adjusts one on top of the other. After switch on the power
supply and automatic Reset, the transmit power will be turned to the optimum (Automatic
mode). When there is no error LED H2 lights (automatic active) and H1 lights (in light
switching mode). In the Manual mode you have to adjust the transmit power with P1
until H2 signals sufficient power. In light switching mode H1 lights too (see also table:
Switching logic
).
•
- Alarm - with Alarm output
Alarm is active, when the transmit power is not sufficient in the Manual mode or the
automatic adjustment is interrupted. The cause can be e. g. deterioration of the beam,
too large distance or misadjustment of sensor heads. Is the cause removed, the alarm
is no longer active.
•
Analog output
In dependence of received power, a voltage between 0...10 V DC is at the analog output.
So you can adjust the sensor heads or measure change of the system.
•
Test input and -Test -
(different features)
A voltage with a value of 24 V DC at test input switches off the transmitter beam. With
this feature you can test the system. Short-time pressing of button S5 - test - results
flashes between 1 and 10 times of H2. They are proportional to the received signal. If
there is no received signal, then flashes H4 only.
•
- Reset -
After connecting the device with power supply or pressing of button S5 for longer time
a Reset will done. This means a test of all displays. All LEDs lights down and up for
a short time. Additionally in Automatic mode a new adjustment of the transmit power
starts from maximum to the nominal value.
•
- Sensor Error -
This function controls the electrical state of the sensor heads. If there is an error
(short-circuit or too high resistance resp. disconnection) H4 lights up. Additionally H1
(transmitter error) or / and H2 (receiver error) flashes slowly (high resistance) or fast
(short-circuit). See for this table
Logic Sensor Error
.
35,8
9,5
89,6
95
58
Maßzeichnungen
in mm
| Dimensions
in mm
Technische Daten
(bei 20 °C U
b
= 24 V DC)
OV620810
Technical data
(at 20 °C (68 °F), V
s
= 24 V DC)
Betriebsspannung
24 V DC / ± 20% / 2,4 W
Supply power
Messverfahren
moduliertes IR-Licht
modulated IR-light
Operating basis
max. Reichweite (Einweg)
Max. range (Through beam)
Sender
Empfänger / Receiver
OE 12 63...
Empfänger / Receiver
OE 10 60 ..., 12 60 ..., 13 60 ...
Transmitter
OS 10 60 ..., 12 60 01, 12 60 03, 12 60 20, 13 60 ...
7 m (23 ft)
15 m (49 ft)
OS 10 60 ..., 12 60 01, 12 60 03, 12 60 20, 13 60 ...
OS 12 60 08, 12 60 26
10 m (33 ft)
25 m (82 ft)
OS 12 60 08, 12 60 26
OS 10 61 ..., 12 63 ...
20 m (66 ft)
55 m (182 ft)
OS 10 61 ..., 12 63 ...
Sendefrequenz
3,7 kHz / 4,3 kHz
Transmit frequency
Sendeleistung
manuell / automatisch
manual / automatic
Transmit power
Schaltfunktion bzw. Schaltverhalten
hell / dunkel
light / dark
Switching behavior
Grundleistung
high / low
System power manual mode
Schaltverzögerung / Impulsbreite
—
Switching delay / impulse period
Schaltausgang (kurzschlussfest)
Schließer (Halbleiter-Relais)
NO (Semiconductor-Relay)
Switching output (short-circuit proof)
Schaltwerte
100 mA / 60 V AC (DC)
values (max.)
Reaktionszeit
24 ms
reaction time
Alarm-/Errorausgang (kurzschlussfest)
pnp: 100 mA / 24 V DC
Alarm / Error output (short-circuit proof)
Analogausgang
0...10 V DC
Analog output
Testeingang
Activ HIGH (L= 0...5 V DC, H= 15...30 V DC)
Test input
Gehäusewerkstoff
NORYL RAL 7035 (grau / grey)
Housing material
Schutzart
IP 20
Protection class
Anschluss-Querschnitt
0,14 - 2,5 mm²
Terminal size
Betriebstemperatur
-25 °C...+50 °C (-13 °F...+122 °F)
Operating temperature
Gehäuseabmessungen
siehe Maßzeichnung
see dimensions
Housing measurements
Logik Sensor Error | Logic Sensor Error
BEDIENUNGSANLEITUNG • Änderungen vorbehalten! Stand:
Juli 2022
ipf electronic gmbh • Rosmarter Allee 14 • 58762 Altena
│
Tel +49 2351 9365-0 • Fax +49 2351 9365-19
│
[email protected] • www.ipf.de