Drawing   : - TPC445 
Issue 

: - 1 

Date 

: - 02/12/15 

ROUTINE MAINTENANCE 

To  ensure  continued  full  efficiency  of  the  dehumidifier,  maintenance 
procedures should be performed as follows: 

1.

Clean the surface of the evaporator and condenser coils by blowing
the  dirt  out  from  behind  the  fins  with  compressed  air.    Hold  the
nozzle of the air hose away from the coil to avoid damaging the fins.
Alternatively, vacuum clean the coils.

2.

Check that the fan rotates freely.

  

The fan motor is sealed for life

and therefore does not need oiling.

3.

To  check  the  refrigerant  charge,  run  the  unit  for  15  minutes  and
briefly remove the top cover.  The evaporator coil should be evenly
frost  coated  across  its  surface.    At  temperatures  above  80

°

F,  the

coil may be covered with droplets of water rather than frost.  Partial
frosting  accompanied  by  frosting  of  the  thin  capillary  tubes,
indicates loss of refrigerant gas or low charge.

4.

Check all wiring connections.

In  order  to  check  the  defrost  operation,  the  unit  needs  to  be 
operated in an ambient temperature of less than 15°C for at least 1 
hour.  When  operated  In  this  condition  the  unit  should  defrost  at 
least  once  every  hour.  The  defrost  mode  can  be  monitored  by 
observing  the  ice melting  on  the  coil face, prior  to  defrost  the face 
will show a white coating of frost, which should clear during defrost 

I

F ANY OF THE PRECEDING PROBLEMS OCCUR

,

 CONTACT THE 

E

BAC

S

ERVICE 

C

ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO

PREVENT PERMANENT DAMAGE

.  

WARNING: 

ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN 

DISCONNECTED BEFORE CARRYING OUT ROUTINE 

MAINTNENANCE 

WARNING:

 

DO NOT STEAM CLEAN REFRIGERATION COILS 

E B A C   C S - 9 0 - H    D E H U M I D I F I E R     O W N E R ' S    M A N U A L 

Pure n Natural Systems  |  purennatural.com  |  1-800-237-9199

Summary of Contents for CS90H

Page 1: ...f 12 Drawing TPC445 Issue 1 Date 02 12 15 CS90H INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL E B A C C S 9 0 H D E H U M I D I F I E R O W N E R S M A N U A L Pure n Natural Systems purennatural com 1 800 2...

Page 2: ...ONTENTS Item Description Quantity 10590GH US Dehumidifier 1 3944110 PVC tube 3 8 I D 7 8 M 3086144 Quick release hose coupling 1 TPC445 Manual 1 E B A C C S 9 0 H D E H U M I D I F I E R O W N E R S M...

Page 3: ...ergy removed during the cooling phase plus the additional heat generated by the compressor The air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute...

Page 4: ...strial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODEL CS60H HEIGHT 15 2 386mm WIDTH 14 353mm DE...

Page 5: ...quired humidity level can be set as follows Press the S button once to access the set point Press the or button to change the display to the desired Humidity level Press the S button again to save the...

Page 6: ...he unit is defrosting the Relative Humidity displayed on the digital controller may increase as a result of the ice frost melting This is quite normal and the display will return to its normal reading...

Page 7: ...an frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections 5 In order to check the defrost operation t...

Page 8: ...d and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing further loss of refrigerant gas 3 The refrigerant compressor...

Page 9: ...the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass valve 1 Contact the Factory Service Center 2 Contact the Factory Ser...

Page 10: ...Tubing 3014338 9 Feet 7 Solenoid Valve 3020837 1 8 Filter Dryer 3020901 1 9 Compressor 3022198 1 10 Defrost Relay 3030269 1 11 Solenoid Coil 3030451 1 12 Capacitor 3030908 1 13 Humidity Controller 30...

Page 11: ...SCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THIS SECTION FOR YOUR RECORDS CLIP AND RETURN THIS CARD PLEASE NOTE WARRANT...

Page 12: ...ssue 1 Date 02 12 15 E B A C C S 9 0 H D E H U M I D I F I E R O W N E R S M A N U A L Pure n Natural Systems purennatural com 1 800 237 9199 Distributed by Pure n Natural Systems Inc Streamwood IL pu...

Reviews: