Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 10/16

 

UMA-CDZ-IP-ACOWM145-00

 

d1 

Select evaporator sensor 

[1]

 

0 : disable 

1 : enable 

d2 

Temperature calibration of evaporator sensor 

[1] 

-10 / +10°C 

0°C 

°C/°F 

-20 / +20°F 

d4 

Defrost cycle

 

0 / 60 

0: cancel defrost 

function

 

30min 

d7 

Maximum defrost time

 

1 / 99 

20 

min 

d8 

Defrost stop temperature 

0 / +45°C 

7°C 

°C/°F 

+32 / +115°F 

A1 

Compressor start and stop in the mode of “run/stop 

in a proportional time”

 

00 : disable 

01 : enable 

01 

A2 

Compressor start time in case of cabinet sensor 

fault

 

01 /60 

10 

min 

A3 

Compressor stop time in case of cabinet sensor 

fault

 

01 /60 

20 

min 

A4 

Buzzer switch 

[2] 

0 : disable 

buzzer beeping 

1 : enable 

buzzer beeping

 

A5 

Lower alarm. Min temp alarm value 

-50°C/A6

 

-50°C 

°C/°F 

58°F/A6

 

A6 

Higher alarm. Max temp alarm value 

A5/90°C 

90°C 

°C/°F 

A5/194°F 

A7 

Temperature alarm override 

0/60 

20 

min 

A8 

Power-ON alarm override 

0/60 

40 

min 

U1 

Select temperature display sensor 

[1]

 

00 : display 

cabinet sensor 

01 : display 

evaporator 

sensor 

U2 

Switch between Fahrenheit and Celsius 

[3]

 

00 : Fahrenheit 

01 : Celsius 

01 

U3 

Select defrost or light relay function 

00 : defrost out. 

01 : light output 

00 

 

[1]: 

no evaporator sensor available 

[2]: 

no buzzer available 

[3]: 

After switch between Celsius/Fahrenheit, the temperature set-point of parameter item St automatically adjusts to the 

corresponding temperature value of Celsius/Fahrenheit, and the temperature set-points of other parameter items related 
to Celsius/Fahrenheit automatically adjust accordingly.  
For example, St is set to 0

, and it will automatically adjust to 32

 after switch; C4 (calibration value of cabinet sensor) 

is set to +8

,and it will automatically adjust to +20*(8/10)=+16

Suggestion: Switch Celsius/Fahrenheit first, then adjust the value of related parameter items to ensure correct parameter 
configuration. 

 

Button name 

Function 

Action 

Set 

Set parameters 

Press it for 3 sec. 

Switch between menu and parameters 

Press it and the 
controller responds. 

 
 

Summary of Contents for IP-ACOWM145

Page 1: ... 00 USER S MANUAL PART 2 AIR CONDITIONER FOR ELECTRICAL ENCLOSURE OUTDOOR APPLICATION IP ACOWM145 IP ACOWM145 0X Document UMA CDZ IP ACOWM145 00 Date Name Description Original user s manual for air conditioner IP ACOWM145 series Language English ISSUE 23 05 2021 REV 01 REV 02 REV 03 ...

Page 2: ...nclosure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary weight of installed AIR CONDITIONER Installation position of AIR CONDITIONER must be selected to ensure good ventilation Take care that any internal external components of enclosure don t obstruct air ...

Page 3: ... IP ACOWM145 0X FEATURES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 1450 1500 A35 A50 W 1150 1200 Absorbed electric power EN14511 A35 A35 W 660 700 A35 A50 W 800 860 Rated current A 3 7 4 2 Motor circuit breaker Delayed pre fuse advised A 10 Electrical connection Three pole connector Air flow rate free blow enclosure m3 h 600 625 Operating temperature ambient C F 5 55...

Page 4: ...ly GENERAL CHECKS electrical enclosure must be disconnected form power supply electrical data shown on rating label pasted on air conditioner side must be guaranteed Electrical enclosure must be sized according to air conditioner dimensions and weight Electrical enclosure must have at least IP54 protection degree Internal and external components of electrical enclosure don t have to affect the pro...

Page 5: ...AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 5 16 UMA CDZ IP ACOWM145 00 2 3 FITTING 1 Make the fixing hole on the enclosure as is shown in the drilling template Deburr all sharp edges to avoid accidental injuries ...

Page 6: ...unscrewing included in mounting kit 5 Connect the condensate drain pipe like is shown in picture below Put some glue on aluminium pipe before to insert it Air conditioner produces condensate because the moist air inside of the enclosure meets cold heat exchanger evaporator and then it becomes water water production decreases during air conditioner working because enclosure air becomes dry The encl...

Page 7: ...Push the spring with a screwdriver and then insert the wire 2 Check the proper wire insertion 3 Connect the unit with the power supply Electrical data shown on rating label pasted on air conditioner side must be guaranteed Install the delayed fuse recommended on rating plate pasted on air conditioner side to protect the line and enclosure components against short circuit Upstream of the electrical...

Page 8: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 8 16 UMA CDZ IP ACOWM145 00 3 1 WIRING DIAGRAM 3 1 1 IP ACOWM145 IP ACOWM145 0X ...

Page 9: ...inimum interval of two successive switch on of the compressor parameter C2 is elapsed Condenser fan turns ON when refrigerant pressure rises up to pressure switch set Compressor and condenser fan turn OFF when internal enclosure temperature decreases below set point value 4 1 DIGITAL THERMOSTAT Indicator Symbol Status Meaning Set set On Set parameters Off Measuring controlling Cooling On Cooling s...

Page 10: ...ride 0 60 40 min U1 Select temperature display sensor 1 00 display cabinet sensor 01 display evaporator sensor 0 U2 Switch between Fahrenheit and Celsius 3 00 Fahrenheit 01 Celsius 01 U3 Select defrost or light relay function 00 defrost out 01 light output 00 1 no evaporator sensor available 2 no buzzer available 3 After switch between Celsius Fahrenheit the temperature set point of parameter item...

Page 11: ...ter selecting the menu press Set to enter the current menu and set its parameters Use or to adjust parameter values then press Set again to return to menu selection status 5 Under any parameter setting status press or press no button for 30 sec to exit parameter setting and save the current parameter value automatically Note The password of administrator menu is valid for once After exiting parame...

Page 12: ...1 rH when temperature A6 and alarm delay time run out controller will display rH rL when temperature A5 and alarm delay time run out controller will display rL 5 SPARE PARTS LIST REFERRED TO WIRING DIAGRAM DESCRIPTION CODE 1 Evaporator fan VCENT190D230V 2 Compressor BSD122DT 3 Condenser fan VCENT190D230V C1 Evaporator fan capacitor CON2UFS2M8F C2 Compressor capacitor CON20UFS2M8F C3 Condenser fan ...

Page 13: ...ooling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This warranty shall become null as soon as the product is altered or modified in its structure or in circuits The terms of this warranty commencement and termination dates are not modified by any repair or...

Page 14: ...UE LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2 40 2003 A1 A2 IEC 60335 2 40 2002 A1 A2 EN 60335 1 2010 A11 A13 A14 A1 A2 IEC 60335 1 A1 A2 OTHER STANDARDS APPLIED EN 55014 1 2017 EN 55014 2 2015 EN IEC 61000 3 2 2019 EN 61000 3 3 2013 Date Name Des...

Page 15: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 15 16 UMA CDZ IP ACOWM145 00 SAA CERTIFICATE ...

Page 16: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 16 16 UMA CDZ IP ACOWM145 00 NOTES ...

Reviews: