IP Enclosures IP-ACIWM035.001 User Manual Download Page 11

Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 11/16

 

UMA-CDZ-IP-ACIWM035.001-00

 

Button name

 

Function

 

Action

 

 

Adjust menu and parameters 

Press it and the 
controller responds. 

 

Exit setting parameters 

Press it and the 
controller responds. 

 
Set-point adjustment 

 

1)  Press the 

Set

 button for 3 sec in status of measuring and controlling to enter user menu, the panel 

will display 

St

.  

2)  Press the 

Set

 button again to display the parameter value of 

St

, and modify the temperature set-

point by pressing 

 or  . 

WARNING:

 temperature which unit starts to work is St+C1. For example: St=31, C1=4 compressor and 

condenser fan turn on at 35°C (31°C+4°C) 
 

Parameter adjustment 

 

1)  When 

St

 shows, press 

 to display 

Po

, and press 

Set

 to display 

00

; at this moment, use the 

button 

 or   to input the password of administrator menu (

55

).  

2)  After inputting the password 

55

, press 

Set

 to display 

Po

. The controller will automatically verify 

whether the password is correct.  

3)  When it passes verification, press 

 or   to select parameter items 

St, Po, C1, C2……

 (i.e. 

any parameter item of user menu and administrator menu); otherwise, the controller will only stay at 
the parameter items St and Po without displaying other parameter items. 

4)  After selecting the menu, press 

Set

 to enter the current menu and set its parameters. Use 

 or   

to adjust parameter values, then press 

Set

 again to return to menu selection status. 

5)  Under any parameter setting status, press 

 or press no button for 30 sec to exit parameter setting 

and save the current parameter value automatically. 

 

Note: The password of administrator menu is valid for once. After exiting parameter settings by 
pressing 

, correct password must be entered again before adjusting parameters. 

 
View temperature 
 

1)  When 

U1 

(temperature display)

 =

00, the controller displays the current temperature of cabinet 

sensor.  

2) 

When 

U1

=01, the controller displays the current temperature of evaporator sensor. 

 

(WARNING: no evaporator probe available on air conditioner) 

 
Control output 

 

Cooling: 

In normal status: 
Refrigeration starts when the cabinet temperature > temperature set-point 

St

 + control differential 

C1

, and 

the indicated time must elapse between two successive minimum switch-on of the compressor. 
Refrigeration stops when the cabinet temperature < temperature set-point 

St

 
In case of cabinet sensor fault, 
When 

A1

=0, compressor start and stop time in the mode of “run/stop in a proportional time” is disabled, 

refrigeration stops. 
When 

A1

=1, compressor start and stop time in the mode of “run/stop in a proportional time” is enabled, 

refrigeration performs in cycle according to the set refrigeration start 

A2

 and stop 

A3

 time in the mode of 

“run/stop in a proportional time”. 

 

Alarm  

 

Summary of Contents for IP-ACIWM035.001

Page 1: ...001 00 USER S MANUAL PART 2 AIR CONDITIONER FOR ELECTRICAL ENCLOSURE INDOOR APPLICATION IP ACIWM035 001 Document UMA CDZ IP ACIWM035 001 00 Date Name Description Original user s manual for air conditi...

Page 2: ...enclosure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary...

Page 3: ...thermostat IP ACIWM035 001 FEATURES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 350 370 A35 A50 W 200 220 Absorbed electric power EN14511 A35 A35 W 290 320 A35 A50 W 320...

Page 4: ...ed form power supply electrical data shown on rating label pasted on air conditioner side must be guaranteed Electrical enclosure must be sized according to air conditioner dimensions and weight Elect...

Page 5: ...CONDITIONER FOR ELECTRICAL ENCLOSURE Page 5 16 UMA CDZ IP ACIWM035 001 00 2 3 FITTING 1 Make the fixing hole on the enclosure as is shown in the drilling template Deburr all sharp edges to avoid acci...

Page 6: ...unscrewing included in mounting kit 5 Connect the condensate drain pipe like is shown in picture below Put some glue on aluminium pipe before to insert it Air conditioner produces condensate because...

Page 7: ...Push the spring with a screwdriver and then insert the wire 2 Check the proper wire insertion 3 Connect the unit with the power supply Electrical data shown on rating label pasted on air conditioner...

Page 8: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 8 16 UMA CDZ IP ACIWM035 001 00 3 1 WIRING DIAGRAM 3 1 1 IP ACIWM035 001...

Page 9: ...lue hysteresis and the minimum interval of two successive switch on of the compressor parameter C2 is elapsed Compressor and condenser fan turn OFF when internal enclosure temperature decreases below...

Page 10: ...00 display cabinet sensor 01 display evaporator sensor 0 U2 Switch between Fahrenheit and Celsius 3 00 Fahrenheit 01 Celsius 01 U3 Select defrost or light relay function 00 defrost out 01 light output...

Page 11: ...o enter the current menu and set its parameters Use or to adjust parameter values then press Set again to return to menu selection status 5 Under any parameter setting status press or press no button...

Page 12: ...ted to show shown if parameter U1 1 rH when temperature A6 and alarm delay time run out controller will display rH rL when temperature A5 and alarm delay time run out controller will display rL 5 SPAR...

Page 13: ...cooling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This...

Page 14: ...UE LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2...

Page 15: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 15 16 UMA CDZ IP ACIWM035 001 00 SAA CERTIFICATE...

Page 16: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 16 16 UMA CDZ IP ACIWM035 001 00 NOTES...

Reviews: