IOTA ILBHI CP HE SD Instruction Manual Download Page 3

Page 3

ILB-LP INPUT WIRING

ilbcp_tspl_input

IOTA ILBHI

EMERGENCY DRIVER

WHITE

NEUTRAL

UNSWITCHED

24/7 POWER

BLACK/ORANGE (347 TO 480V, 50/60HZ)

STEP 4 - 

WIRING THE AC INPUT

The 

ILBHI CP HE SD 

requires an 

unswitched AC input 

of 347-480 volts. Connect the 

BLACK/ORANGE 

wire to the 

347-480 

Line

, and the 

WHITE 

wire to the 

Neutral

CAUTION: The case must be grounded.

COMPLETING INSTALLATION

STEP 5 - 

APPLY AC POWER

A.  

Apply continuous AC power to the unit, and allow the unit to charge for at least 1 hour before performing a 

functional test

.

B.  Verify that the TCTS light is on. The lamp will flash Amber while the battery is charging and be Green when the battery is 

fully charged.

C.  Press and hold the TCTS button for two seconds. The pilot light will blink. Within five seconds, the LED Module should be 

operating at a reduced light output.  The test mode runs for 60 seconds.  To exit the test mode earlier, press and hold the 

TCTS button for two seconds.  If the LED Module in the fixture returns to normal operation, the unit is ready for normal and 

emergency service. If not, see the Troubleshooting section.

This unit features 

AC Activate 

technology which detects the presence of AC power and automatically engages the battery 

charging circuit. 

No manual unit (or “go”) connector needs to be joined

. Instead, connecting the TCTS and applying 

continuous AC power to the unit will enable battery charging and emergency operation.

OPERATION

Normal Mode

 

A.C. power is present. The A.C. Driver operates the LED Module as intended. The 

ILBHI CP HE SD 

is in the standby charg-

ing mode. The 

TCTS 

will be lit providing a visual indication that the battery is being charged.

Emergency Mode

 

The A.C. power fails. The 

ILBHI CP HE SD 

senses the A.C. power failure and automatically switches to the 

Emergency 

Mode

. The LED Module is illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power is restored, the 

ILBHI CP HE SD 

switches the system back to the 

Normal Mode

 and resumes battery charging.

TROUBLESHOOTING

Problem

Possible Cause

Emergency LED Module does 
not operate when the TCTS 
Button is pressed.

TCTS Charging LED 
not on

Fixture does not operate in the 
Normal Mode

1. Incorrect wiring of the Emergency Driver and/or AC Driver.
2. The LED Module is not compatible with the Emergency Driver.
3. Battery has not charged for at least one hour.
4. TCTS is not inserted properly into the Emergency Driver socket.
5. The wrong test accessory is being used.

1. AC Power is Off
2. TCTS is not inserted properly into the Emergency Driver socket.
3. The wrong test accessory is being used.

1. Battery is not fully charged.
2. The LED Module is not within the Emergency Driver specifications.
3. Battery is at end of life.

1. Incorrect wiring of the Emergency Driver and/or AC Driver.
2. AC power is off to the AC Driver.

Emergency Driver does not 
operate lamps in the emergen-
cy mode for at least 90 minutes.

Summary of Contents for ILBHI CP HE SD

Page 1: ...ILBHI CP HE SD is for use with grounded LED luminaires listed to UL standards Not for use in heated air outlets or hazardous locations 8 The ILBHI CP HE SD and A C driver must be on the same branch ci...

Page 2: ...nto the hole so that the LED test button is located outside of the fixture Remote Mounting The TCTS may be remote mounted from the fixture up to 25 feet Before extending the TCTS wires ensure that AC...

Page 3: ...C power to the unit will enable battery charging and emergency operation OPERATION Normal Mode A C power is present The A C Driver operates the LED Module as intended The ILBHI CP HE SD is in the stan...

Page 4: ...Calibration is required whenever the LED load connected to the ILBHI CP HE SD is changed Note Load Calibration happens automatically 48 hours after the ILBHI CP HE SD is first installed If after insta...

Page 5: ...e ILBHI CP HE SD et c a doit tre sur le m me circuit de d rivation 9 Ne pas installer proximit d appareils de chauffage au gaz ou lectriques 10 L ILBHI CP HE SD doit tre install des endroits et des ha...

Page 6: ...l ext rieur du luminaire Percez ou d foncez un trou d un diam tre de 1 2 po dans la paroi du luminaire ou dans le couvercle du chemin de c bles Ins rez la TCTS dans le trou de sorte que le bouton de...

Page 7: ...t et le fonctionnement d urgence UTILISATION Mode normal L alimentation secteur est fournie Le pilote de l alimentation secteur fait fonctionner le module DEL comme pr vu L ILBHI CP HE SD est en mode...

Page 8: ...tion par les autorit s comp tentes TOUT ENTRETIEN DOIT TRE EFFECTU PAR DU PERSONNEL COMP TENT Contactez le service la client le ou rendez vous sur le site www iotaengineering com pour obtenir des info...

Reviews: