IOTA ILB-CP-HE Instruction Manual Download Page 3

Page 3

4. INSTALLING THE THREADED BODY TEST SWITCH (TBTS)

  Cut a single gang switch box into the ceiling tile adjacent to the fixture within reach of the 

ILB-CP-HE

 flex conduit 

marked “B”. After mounting the switch box, connect flex to the box and route all leads inside the box. Refer to  

Illustration 1

 for typical mounting. For proper operation, use only the accessory components provided with the unit

See Page 1 of the Instruction Manual.

5. LABELS

  Attach the appropriate labels adjacent to the 

TBTS. 

Annotate Replacement Label with identical manufacturer part 

number(s). The Caution and the Replacement labels must be on the fixture in a readily visible location to anyone 

attempting to service the fixture.

6. WIRING THE A.C. INPUT

A. The 

ILB-CP-HE

 and A.C. 

driver

 

MUST 

be on the same branch circuit.

B. The 

ILB-CP-HE

 requires an 

unswitched

 A.C. power source of 120 to 277 VAC, 50/60Hz; therefore when used

with switched fixtures, the ILB input must be wired ahead of the switch.

C. Refer to the wiring diagrams on the back page for the proper wiring. For wiring diagrams not shown, consult

our customer service.

7. COMPLETING INSTALLATION

When the installation is complete, switch the A.C. power on and join the 

ILB-CP-HE

 unit connector.

OPERATION

Normal Mode

 – A.C. power is present. The A.C. driver operates the LED load as intended. The 

ILB-CP-HE

 is in the 

standby charging mode. The 

TBTS 

will be lit providing a visual indication that the battery is being charged.

Emergency Mode

 – The A.C. power fails. The 

ILB-CP-HE

 senses the A.C. power failure and automatically switches to 

the 

Emergency Mode

. One or multiple LEDs are illuminated, for a minimum of 90 minutes. When the A.C. power is  

restored, the 

ILB-CP-HE

 switches the system back to the 

Normal Mode

 and resumes battery charging. See page 1 of 

the Instruction Manual.

ILB-CP WITH TBTS TEST ACCESSORY

ILBCP_TBTS.EPS

AC (NORMAL) 

DRIVER

IOTA ILB-CP

EMERGENCY DRIVER

LED

LOAD

WHITE

WHITE

WHT/BLK

WHT/BLK

COMMON

UNSWITCHED 

24/7 POWER

BLK/ORG (120 TO 277V, 50/60HZ)

AC INPUT (120 TO 277V)

SWITCHED OR
UNSWITCHED 

HOT

TBTS

TEST ACCESSORY

RED (+)

BLUE (-)

RED/WHT (+)

BLUE/WHT (-)

 LED INPUT(+)

 LED INPUT (-)

 LED OUTPUT (+)

 LED OUTPUT (-)

UNIT

CONNECTOR

WHT/RED

RED OR RED/BLK (+)

ATTENTION: DO NOT MATE UNIT CONNECTOR UNTIL 
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.

TEST ACCESSORY LEADS-OBSERVE PROPER
POLARITY WIRING.

NO POLARITY ON WHT/BLK LEADS. USE EITHER LEAD FOR
CONNECTION TO BUILDING COMMON (SWITCHED OR UNSWITCHED) 
AND OTHER FOR CONNECTION TO AC DRIVER.

CONNECT UNSWITCHED POWER. IF A SINGLE BUILDING
COMMON IS PRESENT, CONNECT THE WHITE WIRE TO THE COMMON.
IF A SEPARATE UNSWITCHED CONDUCTOR FEED IS PRESENT, 
CONNECT THE WHITE LEAD TO THE COMMON FROM THE 
UNSWITCHED FEED.

MATE UNIT CONNECTOR AFTER INSTALLATION IS 
COMPLETE AND AC POWER IS SUPPLIED

WHT

RED

Illustration 2: Typical Wiring Diagram          