background image

Page 4

68035-020
REV 1700

WIRING DIAGRAM

For additional wiring diagrams, contact Customer Service

IIS

MICRO INVERTER

IIS MICRO-INVERTER - HIGH EFFICIENCY

IIS_MICRO_HE.EPS

UNSWITCHED LINE

ORG/BLK (120-277V)

WHITE

NEUTRAL

AC 

FIXTURE

RED (POS)
WHT

TBTS TEST ACCESSORY

UNIT CONNECTOR

WHT/BLK
WHT/BLK

VIOLET/YELLOW (TO AC DRIVER/BALLAST HOT)
GRAY (TO AC DRIVER/BALLAST NEUTRAL)

MATE UNIT CONNECTOR AFTER INSTALLATION

IS COMPLETE AND AC POWER IS SUPPLIED.

AC FIXTURE - WIRE IN ACCORDANCE

WITH MANUFACTURER’S INSTRUCTIONS.

TEST ACCESSORY LEADS -

OBSERVE PROPER POLARITY.

BLACK

WALL SWITCH

(IF PRESENT)

GROUND WIRE - CONNECT UNIT GROUND IN 

ACCORDANCE WITH LOCAL AND NATIONAL CODES.

GREEN

HOT

ATTENTION:

 DO NOT MATE UNIT CONNECTOR 

UNTIL INSTALLATION IS COMPLETE AND AC 

POWER IS SUPPLIED.

SWITCHED AND UNSWITCHED LINES MUST BE 

ON THE SAME BRANCH CIRCUIT.

RED/BLK

WHT/RED

IIS-35-HE

Summary of Contents for IIS-35-HE

Page 1: ...its intended use 7 Not for use with HID loads 8 The IIS 35 HE should be mounted securely in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel 9 The use of accessory equipment not recommended by IOTA Engineering LLC may cause an unsafe condi tion will void the warranty and result in non compliance with UL specifications 10 The AC voltage rating o...

Page 2: ...al wiring diagrams consult Customer Service Wire the AC driver ballast with the lamp s in accordance with the manufacturer s installation instructions Note only emergency fixtures should be present on the load side of the IIS 35 HE Keep the output neutral isolated from all other neutrals including the input neutral Install in accordance with the National Electrical Code and local regulations 3 INS...

Page 3: ...ting shall be kept by the owner for inspection by the authority having jurisdiction SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL Consult Customer Service for current warranty information Page 3 A Once AC Power has been applied join the IIS 35 HE unit connector The TBTS will illuminate indicating the presence of AC power and that the battery is being charged B Attach the appropriate labels ...

Page 4: ...ST HOT GRAY TO AC DRIVER BALLAST NEUTRAL MATE UNIT CONNECTOR AFTER INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED AC FIXTURE WIRE IN ACCORDANCE WITH MANUFACTURER S INSTRUCTIONS TEST ACCESSORY LEADS OBSERVE PROPER POLARITY BLACK WALL SWITCH IF PRESENT GROUND WIRE CONNECT UNIT GROUND IN ACCORDANCE WITH LOCAL AND NATIONAL CODES GREEN HOT ATTENTION DO NOT MATE UNIT CONNECTOR UNTIL INSTALLATION IS C...