iO HVAC Controls iO-WR-XR Quick Start Manual Download Page 3

ON

1   2  3  4   5   6 

MODE

DIP SWITCHES:

SWITCH 1 - Pairing mode when ON and 

Normal operating mode when OFF.
SWITCH 2 through 6 - Not used.

PROG/TEST

PROGRAM/TEST BUTTON:

Used with MODE DIP SWITCH 1 to field-pair 

transceivers.
Functions as a Test/Transmit button during 
normal operation. When pressed, transceiver 

sends a radio test packet and the RED 
TRANSMIT LED will illuminate. Paired 
transceiver will acknowledge the packet was 
received with a radio test packet indicated by a 

momentary GREEN RECEIVE LED.

FIELD-PAIRING TRANSCEIVERS:

1. Put MODE DIP SWITCH 1 in the ON
position for both transceivers.
2. Press the PROG/TEST button on either
transceiver. Observe that the STATUS/PROG

LED flashes.
3. Put MODE DIP SWITCH 1 in the OFF
position for both transceivers.

4. Press PROG/TEST on either transceiver and
observe that TRANSMIT and RECEIVE LEDs
operate normally.

Pairing procedure overwrites any previous 
pairing. For example, if replacing only one 
transceiver, simply follow the above 

procedure with both the existing and 
replacement transceiver. 

COMPLIANCE:

The iO-WR-XR Wireless Transceiver has been 
tested and found to comply with the limits for a 
Class B digital device, pursuant to part 15 of the 

FCC Rules. These limits are designed to 
provide reasonable protection against harmful 
interference in a residential installation. This 
equipment generates, uses and can radiate 

radio frequence energy, and if not installed and 
used in accordance with the instructions, may 
cause harmful interference to radio 

communications. There is no guarantee that 
interference will not occur in a particular 
installation. If this equipment does cause 
harmful interference to radio or television 

reception, which can be determined by turning 
the equipment off and on, the user is 
encouraged to try to correct the interference by 

one or more of the following measures.
- Reorient or relocate the receiving antenna.
- Increase the separation between the
equipment and receiver.

- Connect the equipment into an outlet or circuit
different from that to which the receiver is 
connected.

SPECIFICATIONS: 

Dimensions:   

Power Input:  

Channels: 

Contact Rating: 

Addresses:  

Frequency:

Range: 

Operating Temp: 

Operating RH: 

3.75” H x 5.25” W x 2” D 
12 or 24 Volts AC or DC 
2 Send, 2 Receive
10A per channel
Factory-paired
Multiple units can be used 
in same location
902-928 MHz
1/2 mile 

line of sight

-40°F to 185°F
0 to 95% (non-condensing)

OFF

Reviews: