INVT IVC1L User Manual Download Page 3

 

 

As a terminal dedicated to user programming, PORT0 can be 
converted to programming protocol through the mode selection switch. 
The relationship between PLC operation status and the protocol used 
by PORT0 is shown in the following table.   

Mode selection 

switch position 

status 

PORT0 operation protocol 

ON 

Running   

Programming protocol, or Modbus protocol, 
or free-port protocol, or N: N network 
protocol, as determined by user program and 
system configuration 

ON

TM 

Running 

Converted to programming protocol   

OFF

TM 

Stop   

OFF 

Stop   

If the system configuration of user program is 
free-port protocol, it converts to programming 
protocol automatically after stop; or system 
protocol keeps unchanged 

 

PORT1

PORT2 are ideal for connection with equipment that can 

communicate (such as inverters). With Modbus protocol or RS485 
terminal free protocol, it can control multiple devices through the 
network. Its terminals are fixed with screws. You can use a shielded 
twisted-pair as the signal cable to connect communication ports by 
yourself. 

 

5    Installation 

PLC is applicable to Installation category II, Pollution degree 2. 

5.1    Installation Dimensions 

型号

 

 

 

 

净重

 

IVC1L-0806MAR

IVC1L-0806MAT   

135mm 

90mm 

71.2mm 

440g 

IVC1L-1208MAR

IVC1L-1208MAT 

440g 

IVC1L-1410MAR

IVC1L-1410MAT

 

470g 

IVC1L-1614MAR

IVC1L-1614MAT 

150mm 

90mm 

71.2mm 

650g 

IVC1L-2416MAR

IVC1L-2416MAT

IVC1L-1614MAR1

IVC1L-1614MAT1

 

182mm 

90mm 

71.2mm 

750g 

IVC1L-3624MAR

IVC1L-3624MAT 

224.5mm 

90mm 

71.2mm 

950g 

5.2    Installation Method 

DIN rail mounting 

Generally you can mount the PLC onto a 35mm-wide rail (DIN), as 
shown in the following figure. 

 

Screw fixing 

Fixing the PLC with screws can stand greater shock than DIN rail 
mounting. Use M3 screws through the mounting holes on PLC 
enclosure to fix the PLC onto the backboard of the electric cabinet, as 
shown in the following figure. 

 

5.3    Cable Connection And Specification 

Connecting power cable and grounding cable 

The connection of AC power and auxiliary power is demonstrated in the 
following figure. 

We suggest you wire a protection circuit at the power supply input 
terminal.See the figure below. 

 

COM

 

24V

 

N

 

PG

 

L

 

开关电源

 

S/S

 

X0

 

X7

 

IVC1L-1614MAR

 

Xn

 

Xm

 

S/S

 

IVC1-

 

0808ERN

 

AC - L

 

+24V

 

+5V

 

GND

 

COM

 

24V

 

PG

 

IVC 1-4AD

 

IVC 1-4DA

 

IVC 1-5AM

 

IVC 1-4TC

 

AC - N

 

 

Connect the PLC 

  terminal to the grounding electrode. To ensure 

reliable grounding cable connection, which makes the equipment safer 
and protects it from EMI.use AWG12~16 cable, and make the cable as 
short as possible. Use independent grounding. Avoid sharing route with 
the grounding cable of other equipment (particularly those with strong 
EMI). See the following figure.   

 

Cable specification 

When wiring a PLC, use multi-strand copper wire and ready-made 
insulated terminals to ensure the quality. The recommended model and 
the cross-sectional area of the cable are shown in the following table. 

Wire 

Cross-sectional 

area 

Recommended 

model 

Cable lug and 

heat-shrink tube 

AC power 
cable (L, N) 

1.0~2.0mm

²

 

AWG12, 18 

H1.5/14 round insulated 
lug, or tinned cable lug 

Earth cable 
(

2.0mm

²

 

AWG12 

H2.0/14 round insulated 
lug, or tinned cable end 

Input signal 
cable (X) 

0.8~1.0mm

²

 

AWG18, 20 

UT1-3 or OT1-3 
solderless lug

 

Φ3 or Φ

heat shrinkable 

tube 

Output signal 
cable (Y) 

0.8~1.0mm

²

 

AWG18, 20 

 

Fix the prepared cable head onto the PLC terminals with screws. 
Fastening torque: 0.5~0.8Nm.   

The recommended cable processing-method is shown in the following 
figure. 

PLC

PLC

Other

equipment

Other

equipment

PLC

Other

equipment

Best

Good

Bad