Goodrive20-EU Series VFD
Function parameters
-88-
P10 group Simple PLC and multi-step speed control
Function
code
Name
Description
Default Modify
P10.00
Simple PLC
mode
0: Stop after running once; the VFD stops
automatically after running for one cycle, and it
can be started only after receiving running
command.
1: Keep running in the final value after running
once. The VFD keeps the running frequency and
direction of the last section after a single cycle.
2: Cyclic running; the VFD enters the next cycle
after completing one cycle until receiving stop
command and stops.
0
○
P10.01
Simple PLC
memory
selection
0: No memory after power-off
1: Memory after power-off; PLC memories its
running step and frequency before power-off.
0
○
P10.02
Multi-step
speed 0
100.0% of the frequency setting corresponds to
the max. frequency P00.03.
When selecting simple PLC running, set
P10.02
–P10.33 to define the running frequency
and direction of all stages.
Note:
The symbol of multi-step determines the
running direction of simple PLC. The negative
value means reverse rotation.
P10.04
P10.02
P10.03
P10.05
P10.07
P10.06
P10.31
P10.33
P10.32
ACC time
2 stages
DEC time
2 stages
P10.30
P10.28
Multi-step speeds are in the range of --f
max
–f
max
and it can be set continuously.
Goodrive20-EU series VFDs can set 16 stages
speed, selected by the combination of multi-step
terminals 1
–4, corresponding to the speed 0 to
speed 15.
0.0%
○
P10.03
Running time
of step 0
0.0s
○
P10.04
Multi-step
speed 1
0.0%
○
P10.05
Running time
of step 1
0.0s
○
P10.06
Multi-step
speed 2
0.0%
○
P10.07
Running time
of step 2
0.0s
○
P10.08
Multi-step
speed 3
0.0%
○
P10.09
Running time
of step 3
0.0s
○
P10.10
Multi-step
speed 4
0.0%
○
P10.11
Running time
of step 4
0.0s
○
P10.12
Multi-step
speed 5
0.0%
○
P10.13
Running time
of step 5
0.0s
○
Summary of Contents for Goodrive20-EU VFD Series
Page 1: ......
Page 173: ...6 6 0 0 1 0 0 4 8 4...