Function parameters
-54-
Function
code
Name
Description
Default
value
Modify
P04.07
V/F frequency
3 of motor 1
When
=1, the user can set V/F curve
through
V/F is generally set according to the load of the
motor.
Note:
V1
<
V2
<
V3, f1
<
f2
<
f3. Too high low
frequency voltage will heat the motor excessively
or damage. The overcurrent speed or overcurrent
protection may occur to the VFD.
Setting range of
: 0.00Hz
Setting range of
: 0.0%
–110.0%
Setting range of
Setting range of
: 0.0%
–110.0%
(the rated voltage of motor 1)
Setting range of
(the rated frequency of motor 1)
Setting range of
: 0.0%
–110.0%
(the rated voltage of motor 1)
00.00Hz
○
P04.08
V/F voltage 3 of
motor 1
00.0%
○
P04.09
V/F slip
compensation
gain of motor 1
This function code is used to compensate the
change of the rotation speed caused by load
during compensation SVPWM control to improve
the rigidity of the motor. It can be set to the rated
slip frequency of the motor which is counted as
below:
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the motor, its
; n is the rated rotating
speed of the motor and its function code is
; p is the pole pair of the motor. 100.0%
corresponds to the rated slip frequency
△
f.
Setting range: 0.0
–200.0%
100.0%
○
P04.10
Motor 1 low
frequency
vibration
control factor
In the SVPWM control mode, current fluctuation
may occur to the motor on some frequency,
especially the motor with big power. The motor
cannot run stably or overcurrent may occur. These
phenomena can be canceled by adjusting this
parameter.
Setting range of
: 0
–100
Setting range of
: 0
–100
10
○
P04.11
Motor 1 high
frequency
vibration
control factor
10
○