Goodrive100-PV Series Solar Pumping VFD Function parameters
27
Function
code
Name
Detailed illustration of parameters
Default Modify
immediately. And the load coasts to stop
at the mechanical inertia.
P01.18
Operation
protection
0: The terminal running command is
invalid when powering on.
1: The terminal running command is valid
when powering on.
1
○
P01.21
Restart after
power off
0: Disabled
1: Enabled
1
○
P02 Group Motor 1 parameters
P02.00
Motor type
0: Asynchronous motor
1: Reserved
0
◎
P02.01
Rated power of
asynchronous
motor
0.1–3000.0kW
Set the parameter of
the
asynchronous
motor.
In order to ensure the
controlling
performance, set the
according to the name
plate
of
the
asynchronous motor.
GD100-PV
series
VFDs
provide
the
function of parameter
autotuning.
Correct
parameter autotuning
comes from the correct
setting of the motor
Depend
on model
◎
P02.02
Rated frequency
of asynchronous
motor
0.01Hz–P00.03
50.00
Hz
◎
P02.03
Rated rotating
speed of
asynchronous
motor
1–36000rpm
Depend
on model
◎
P02.04
Rated voltage of
asynchronous
motor
0–1200V
Depend
on model
◎
P02.05
Rated current of
asynchronous
motor
0.8–6000.0A
Depend
on model
◎