BPD series PV pumping inverter
Function parameters
25
Function
code
Name
Detailed description
Default Modify
P00.05
Lower limit of
the running
frequency
The lower limit of the running frequency is that of
the output frequency of the inverter.
The inverter runs at the lower limit frequency if the
set frequency is lower than the lower limit.
Note:
Max. o
utput frequency ≥ Upper limit
frequency ≥ Lower limit frequency
Setting range: 0.00Hz
–P00.04 (Upper limit of the
running frequency)
0.00Hz
◎
P00.11
ACC time 1
ACC time means the time needed if the inverter
speeds up from 0Hz to the Max. output frequency
(P00.03).
DEC time means the time needed if the inverter
speeds down from the Max. Output frequency to
0Hz (P00.03).
BPD series inverters have four groups of
ACC/DEC time which can be selected by P05. The
factory default ACC/DEC time of the inverter is the
first group.
Setting range of P00.11 and P00.12:0.0
–3600.0s
Depend
on
model
○
P00.12
DEC time 1
0.0s
○
P00.13
Running
direction
selection
0: Runs at the default direction, the inverter runs in
the forward direction. FWD/REV indicator is off.
1: Runs at the opposite direction, the inverter runs
in the reverse direction. FWD/REV indicator is on.
Modify the function code to shift the rotation
direction of the motor. This effect equals to the
shifting the rotation direction by adjusting either
two of the motor lines (U, V and W). The motor
rotation direction can be changed by QUICK/JOG
on the keypad. Refer to parameter P07.02.
2: Forbid to run in reverse direction: It can be used
in some special cases if the reverse running is
disabled.
0
○
P00.18
Function
restore
parameter
0: No operation
1: Restore the default value
2: Clear fault records
0
◎