background image

Optidrive ODE-2 User Guide Revision 3.20 

 

www.invertekdrives.com 

25

 

 

8

 
M

od
b

u

R

TU Co

m

m

u

n

ic

ati

on

8.

 

Modbus RTU Communications 

8.1.

 

Introduction 

The Optidrive E2 can be connected to a Modbus RTU network via the RJ45 connector on the front of the drive. 

8.2.

 

Modbus RTU Specification 

Protocol 

Modbus RTU 

Error check 

CRC 

Baud rate 

9600bps, 19200bps, 38400bps, 57600bps, 115200bps (default) 

Data format 

1 start bit, 8 data bits, 1 stop bits, no parity. 

Physical signal 

RS 485 (2-wire) 

User interface 

RJ45 

8.3.

 

RJ45 Connector Configuration 

For full MODBUS RTU register map 

information please refer to your Invertek 

Drives Sales Partner. 

 

When using MODBUS control the Analog and 

Digital Inputs 

can be configured as shown in section 7.3 

 

No Connection 

No Connection 

0 Volts 

-RS485 (PC) 

+RS485 (PC)  

+24 Volt 

-RS485 (Modbus RTU) 

+RS485 (Modbus RTU) 

 

 

 

 

 

 

 

Warning: 

This is not an Ethernet 
connection. Do not connect 
directly to an Ethernet port.

 

 

8.4.

 

Modbus Telegram Structure 

The Optidrive ODE-2 supports Master / Slave Modbus RTU communications, using the 03 Read Holding Registers and 06 Write Single Holding 
Register commands. Many Master devices treat the first Register address as Register 0, therefore it may be necessary to convert the Register 
Numbers detail in section 8.5 by subtracting 1 to obtain the correct Register address. The telegram structure is as follows:- 
 

Command 03 – Read Holding Registers 

 

Command 06 – Write Single Holding Register 

Master Telegram 

Length 

 

Slave Response 

Length 

 

Master Telegram 

Length 

 

Slave Response 

Length 

Slave Address 

1  Byte 

 

Slave Address 

1  Byte 

 

Slave Address 

1  Byte 

 

Slave Address 

1  Byte 

Function Code (03) 

1  Byte 

 

Starting Address 

1  Byte 

 

Function Code (06) 

1  Byte 

 

Function Code (06) 

1  Byte 

1

st

 Register Address 

2  Bytes 

 

1

st

 Register Value 

2  Bytes 

 

Register Address 

2  Bytes 

 

Register Address 

2  Bytes 

No. Of Registers 

2  Bytes 

 

2

nd

 Register Value 

2  Bytes 

 

Value 

2  Bytes 

 

Register Value 

2  Bytes 

CRC Checksum 

2  Bytes 

 

Etc... 

 

 

 

CRC Checksum 

2  Bytes 

 

CRC Checksum 

2  Bytes 

 

 

 

 

CRC Checksum 

2  Bytes 

 

 

 

 

 

 

 

 

8.5.

 

Modbus Register Map 

Register 
Number 

Par. 

Type 

Supported 

Commands 

Function 

Range 

Explanation 

Low Byte 

High Byte 

R/W 

03,06 

Drive Control Command 

0..3 

16 Bit Word.  
Bit 0 : Low = Stop, High = Run Enable 
Bit 1 : Low = Decel Ramp 1 (P-04), High = Decel 
Ramp 2 (P-24) 
Bit 2 : Low = No Function, High = Fault Reset 
Bit 3 : Low – No Function, High = Coast Stop 
Request 

R/W 

03,06 

Modbus Speed reference setpoint 

0..5000 

Setpoint frequency x10, e.g. 100 = 10.0Hz 

R/W 

03,06 

Acceleration and Deceleration Time 

0..60000 

Ramp time in seconds x 100, e.g. 250 = 2.5 seconds 

03 

Error code 

Drive status 

 

Low Byte = Drive Error Code, see section 10.1 
High Byte = Drive Status as follows :- 
0 : Drive Stopped 
1: Drive Running 
2: Drive Tripped 

 

03 

Output Motor Frequency 

0..20000 

Output frequency in Hz x10, e.g. 100 = 10.0Hz 

 

03 

Output Motor Current 

0..480 

Output Motor Current in Amps x10, e.g. 10 = 1.0 Amps 

11 

03 

Digital input status 

0..15 

Indicates the status of the 4 digital inputs 
Lowest Bit = 1 Input 1 

20 

P00-01 

03 

Analog Input 1 value 

0..1000 

Analog input % of full scale x10, e.g. 1000 = 100% 

21 

P00-02 

03 

Analog Input 2 value 

0..1000 

Analog input % of full scale x10, e.g. 1000 = 100% 

22 

P00-03 

03 

Speed Reference Value 

0..1000 

Displays the setpoint frequency x10, e.g. 100 = 10.0Hz 

23 

P00-08 

03 

DC bus voltage 

0..1000 

DC Bus Voltage in Volts 

24 

P00-09 

03 

Drive temperature 

0..100 

Drive heatsink temperature in ºC 

All user configurable parameters are accessible as Holding Registers, and can be Read from or Written to using the appropriate Modbus 
command. The Register number for each parameter P-04 to P-047 is defined as 128 + Parameter number, e.g. for parameter P-15, the register 
number is 128 + 15 = 143. Internal scaling is used on some parameters, for further details, please contact your Invertek Drives Sales Partner. 
 
 

Summary of Contents for Optidrive ODE-2-11005-1H01 Series

Page 1: ...ptidrive ODE 2 User Guide Revision 3 20 www invertekdrives com 1 1 Introduction User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 11kW 0 5 15HP 110 480V Installation and Operating Instructions...

Page 2: ...13 Motor Nameplate Details Enter the motor rated voltage in P 07 Enter the motor rated current in P 08 Enter the motor rated frequency in P 09 Keypad operation can be found on page 16 Control Termina...

Page 3: ...nter the motor rated current in P 08 Enter the motor rated frequency in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse...

Page 4: ...cy in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse Ratings given on page 26 Recommended cable sizes shown on page 26...

Page 5: ...factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted For shielded motor cable lengths greater than 100m and...

Page 6: ...ctions 13 4 6 Motor Thermal overload Protection 14 4 7 Control Terminal Wiring 14 4 8 Connection Diagram 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4 10 Control Terminal Conne...

Page 7: ...ses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the drive control cables whilst power...

Page 8: ...50 1KB4 ODE 2 22150 1K04 1 5 ODE 2 22020 1HB4 ODE 2 22020 1H04 2 7 2 ODE 2 22220 1KB4 ODE 2 22220 1K04 2 2 ODE 2 22030 1HB4 ODE 2 22030 1H04 3 10 5 2 N A ODE 2 32040 1K04 2 4 0 N A ODE 2 32050 1H04 2...

Page 9: ...97 5 5 0 22 10 0 39 1 0 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 110 4 33 63 2 48 5 5 0 22 10 0 39 1 7 3 8 3 261 10 28 246 9 69 247 9 72 6 0 24 175 6 89 131 5 16 80 3 15 5 5 0 22 1...

Page 10: ...All Frame Sizes Control Terminals 0 5 Nm 4 5 lb in Power Terminals 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmen...

Page 11: ...For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched mo...

Page 12: ...tor ground must be connected to one of the ground terminals on the drive Ground Fault Monitoring As with all inverters a leakage current to earth can exist The Optidrive is designed to produce the min...

Page 13: ...t power supply faults Part numbers are shown in the table Supply Frame Size AC Input Inductor 230 Volt 1 Phase 1 OPT 2 L1016 20 2 OPT 2 L1025 20 3 N A 400 Volt 3 Phase 2 OPT 2 L3006 20 2 OPT 2 L3010 2...

Page 14: ...s of different voltages e g 24 Volt DC and 110 Volt AC should not be routed in the same cable Maximum control terminal tightening torque is 0 5Nm Control Cable entry conductor size 0 05 2 5mm2 30 12 A...

Page 15: ...un in PI Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Pres...

Page 16: ...turned to minimum 5 Turn the potentiometer to maximum The motor will accelerate to 50Hz the default value of P 01 under the control of the accelerating ramp time P 03 The display shows 50Hz at max sp...

Page 17: ...the motor P 10 Motor Rated Speed 0 30000 0 Rpm This parameter can optionally be set to the rated nameplate rpm of the motor When set to the default value of zero all speed related parameters are displ...

Page 18: ...1 0 0 Hz Rpm P 21 Preset Frequency Speed 2 P 02 P 01 0 0 Hz Rpm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected...

Page 19: ...ut Software Protection Enables the internal brake chopper without software protection An external thermal protection device should be fitted P 35 Analog Input 1 Scaling 0 0 500 0 100 0 Scales the anal...

Page 20: ...erence between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops suffi...

Page 21: ...y This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain operat...

Page 22: ...e or similar to digital input 3 7 Open Stop disable Closed Fwd Run enable Open Stop disable Closed Rev Run enable External trip input Open Trip Closed Run Analog input 1 reference Closing digital inpu...

Page 23: ...ton Open Keypad speed ref 24V Preset speed 1 3 1 Open Stop disable Closed Run enable Closed remote UP push button External trip input Open Trip Closed Run Closed remote DOWN push button Connect extern...

Page 24: ...trip input Open Trip Closed Run PI feedback analog input Connect external motor thermistor PTC type or similar to digital input 3 4 Normally Open NO Momentary close to run Normally Closed NC Momentary...

Page 25: ...2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Checksum...

Page 26: ...0 75 1 8 5 16 10 1 5 14 4 3 1 5 14 50 N A 1 1 5 2 13 9 25 20 2 5 12 7 1 5 14 50 N A 2 1 5 2 15 2 25 20 2 5 12 7 1 5 14 100 100 2 2 2 3 19 5 25 25 4 10 10 5 1 5 14 100 50 3 4 5 30 5 40 40 4 8 16 2 5 12...

Page 27: ...recommends the installation of input line reactors Frequency 50 60Hz 5 Variation Short Circuit Capacity Voltage Rating Min kW HP Max kW HP Maximum supply short circuit current 115V 0 37 0 5 1 1 1 5 5...

Page 28: ...vertek standard braking resistor is being used P 34 MUST be 1 Increase the deceleration time P 04 or 2nd deceleration time P 24 Reduce the load inertia For Other Brake Resistors Ensure the resistance...

Reviews: