Version 1.00
| Fieldbus Guide |
37
www.invertekdrives.com
11
Additional Status Registers
11.3. Extended Status Registers
Modbus
RTU
Register
CAN
Open
Index
Sub
Index
PDO
Map
Parameter
Number
Upper
byte
Lower
Byte
Format
Type
Scaling
2001
-
-
-
-
Status Word 2
WORD
R
See Below
2002
-
-
-
-
Motor Output Speed
S16
R
1dp, e.g. 100 = 10.0Hz
2003
-
-
-
-
Motor Output Current
U16
R
1dp, e.g. 100 = 10.0A
2004
-
-
-
-
Motor Output Power
U16
R
2dp, e.g. 100 = 1.00kW
2005
-
-
-
-
IO Status Word
WORD
R
See Below
2006
-
-
-
-
Motor Output Torque
U16
R
4096 = 100%
2007
-
-
-
P0-08
DC Bus Voltage
U16
R
600 = 600 Volts
2008
-
-
-
P0-09
Heatsink Temperature
S16
R
50 = 50°C
2009
-
-
-
P0-01
Analog Input 1
S16
R
1dp, e.g. 500 = 50.0%
2010
-
-
-
P0-02
Analog Input 2
U16
R
1dp, e.g. 500 = 50.0%
2011
-
-
-
-
Analog Output
U16
R
1dp, e.g. 500 = 50.0%
2012
-
-
-
P0-05
PI Output
U16
R
1dp, e.g. 500 = 50.0%
2013
-
-
-
P0-20
Internal Temperature
S16
R
50 = 50°C
2014
-
-
-
P0-07
Motor Output Voltage
U16
R
200 = 200 Volts RMS
2015
-
-
-
-
IP66 Pot Input value
U16
R
1dp, e.g. 500 = 50.0%
2016
-
-
-
-
Trip Code
U16
R
See Below
11.3.1. Status Word 2 - Register 2001
Status Word 2 provides an optional additional status word which may be used in additional or as an alternative to the status word
in register 6. This status word is the first word in a block of 16 registers which may be read using a single “Read Multiple Registers”
command enabling an efficient method to transfer important status information.
Bit
Definition
Bit is HIGH under the following conditions:
0
Ready
No trip / fault
No mains loss
Hardware enable input is present
1
Running
Drive running
2
Tripped
Drive tripped
3
Standby
In Standby Mode
4
Fire Mode
Fire mode is active
5
Reserved
N/A
6
Speed Set-point Reached (At Speed)
Drive is enabled
Output Frequency = Set point
7
Below Minimum Speed
Drive is enabled
Output Frequency / Speed < P-02
8
Overload
Output current > P-08
9
Mains Loss
Mains power not detected
10
Heatsink > 85°C
Heatsink temperature > 85°C
11
Control Board > 80°C
Control PCB temperature > 80°C
12
Switching Frequency Reduction
PWM switching frequency is reduced from set value
13
Reverse Rotation
Motor rotates is in reverse direction
14
Reserved
N/A
15
Live Toggle Bit
This bit will toggle each time this register is read