EtherCAT Interface 

User Guide

 

Overview 

 
This option module is specifically designed to be used with the Optidrive P2 
and Optidrive HVAC range of variable speed drive products and is intended for 
professional incorporation into complete equipment or systems. If installed 
incorrectly it may present a safety hazard. Before commencing installation 
and commissioning, the user should ensure they are fully familiar with the 
Optidrive P2, and in particular have read the important safety information and 
warnings contained in the Optidrive P2 / Optidrive HVAC User Guide. 
 

Note 

 
This User Guide is intended to be used with Optidrive P2 & HVAC firmware 
version 1.20 or later. The firmware version of the drive can be displayed in 
parameter P0-28. Previous versions of firmware can be upgraded using 
Optitools Studio PC software. Contact your local Invertek Sales Partner for 
further Information. 
 

Available Functions 

 
The EtherCAT Interface is intended to be installed in the Optidrive option slot, 
and allows the Optidrive to be connected to an EtherCAT network. The 
interface offers the following functionality :- 

 

CANopen over Ethernet 

 

DS301 Compliant 

 

Fast Cyclic I/O data transfer 
 

XML File 

An EtherCat Slave Interface Identification XML file for the interface can be 
obtained from 

www.invertekdrives.com 

IP Address Configuration 

If it is desired to change the IP Address, an IP address configuration tool is 
available for download from 

www.invertekdrives.com

 

Compatibility 

This Option is suitable for use on the following product ranges: 
Optidrive P2 (ODP-2-.... Drives) 
Optidrive HVAC (ODV-2-...  Drives) 

Model Code 

OPT-2-ETHCAT-CC 

Invertek Drives Ltd 
Offa’s Dyke Business Park 
Welshpool  
Powys, UK 
SY21 8JF

 

 

 

Layout 

 

Item 

 

❶ 

RUN LED 

❷ 

ERROR LED 

❸ 

EtherCAT Port 1 

❹ 

EtherCAT Port 2 

❺ 

Port 1 Activity LED 

❻ 

Port 2 Activity LED 

 

RUN LED 

State 

Indication 

Off 

INIT : Init State (or no power) 

Green 

OPERATIONAL : CoE Device in Operational State 

Green Blinking 

PRE-OPERATIONAL State 

Green Single Flash 

SAFE-OPERATIONAL State 

Red 

Fatal Error 

 

ERROR LED 

State 

Indication 

Off 

No Power / Error 

Red Blinking 

Invalid Configuration 

Red Double Flash 

Application Watchdog Timeout 

Red 

Module Exception State 

 

Link / Port Activity LEDs 

Off 

No Link 

Green 

Link Established, no communication 

Green Flickering 

Lint Established & Communicating 

 

Installation 

 

Ensure the drive power is 
removed prior to installing the 
option module 

 

Remove the blanking cover from 
the option module slot 

 

Carefully slide the option 
module into the slot, ensuring 
that the locating tabs are 
correctly aligned. Do not use 
excessive force 

 

Tighten the 2 clamping screws to 
secure the module in place 

 

PLC Configuration 

 
Configuration of the PLC varies between different systems.  
Refer to information on the specific PLC system in use for further guidance. 
 

 

Optidrive Setup 

 

 

Set the drive to Fieldbus control mode by setting parameter P1-12 = 4 

 

Ensure Advanced Parameter Access is enabled on the drive by setting P1-
14 = 101 

 

By default, the module supports DHCP, and the IP address will be 
automatically configured. If a fixed IP address is desired, this can be 
configured using the IP address configuration tool available from 
www.invertekdrives.com 

 

 

 

 

 

 