background image

Inventum Technologies BV 

– VMS-47C55-EN-V1 

 

6. Installation

 

6.1 Preparation 

 

Do not place the device in a metal casing. 

 

1.

 

Press the clip and pull the top section from the 
bottom section.

 

2.

 

When using screws: Use the mounting plate as 
a template.

 

3.

 

When using tape:

 

a. 

Make sure the surface is smooth, 
clean, and degreased.

 

b. 

Remove the foil from the double-sided tape.

 

 

6.2 Commissioning

 

1.  Place the batteries. All leds are ON for 3 

seconds. 

2.  Wait until the status led shows the binding 

mode. If the device shows another indication, 
the device is already bound. See 8.2 on how to 
bind the device again

.

 

3.  Make sure that the RF-control device is in binding mode.  
4.  Tap the button. The device will try to bind to the control device 

and shows the result on the status led. When the communication 
failed, make sure that the RF-control device is in binding mode 
and retry

.

 

 

6.3 Installation procedure 

 Recommended position: We advise to place the sensor at 1 
to 1.5 m from the ground, not directly above a wet zone. 

 

1.  Place the bottom section of the device. 
2.  Fasten the bottom section using the screws 

or tape. 

 

 

 

3.  Place the top section of the device onto the 

bottom section. Close and press until it clicks. 

 

7. Operation 
7.1 Show Status 

Tap the button. The Status led and Mode leds show the status of the 
system 
 

7.2 Set mode 

From the status screen (see 7.1) 
1.  Tap the button. The mode leds show the next selection

.

 

2.  If needed, tap the button within 2 seconds, until the selection 

shows the required mode

.

 

3.  Wait 2 seconds. The device applies the requested mode. The 

Status led and Mode leds show the status of the system. 
 

8. Configuration 

 

 
 
 
 
 

 
8.1 Configuration setpoints

 

From the status screen (see 7.1), use table above. 
1.  Tap the button. The mode leds show the next selection. 
2.  If needed, tap the button within 2 seconds, until the selection 

shows the item. 

3.  Press and hold the button until the Status led starts flashing 

white. 

4.  Release the button. The status led shows the item selected, and 

the Mode leds show its current value. 

5.  If needed, tap the button within 10 seconds, until the Mode leds 

show the value to set. 

 

When setting the fan speed, make sure that the medium fan 
speed is between the low and high fan speed. 

 

6.  Wait 10 seconds. The device applies the configured value. The 

Status led and Mode leds show the status of the system. 

 

8.2 Bind the device again

 

From the status screen (see 7.1). 
1.  Tap the button. The mode leds show the next selection. 
2.  If needed, tap the button within 2 seconds, until the selection 

shows the Auto (4

th

) led. 

3.  Press and hold the button until the Status led starts flashing 

white. 

4.  Release the button. The status led shows the binding mode. 
5.  Tap the button. The device will try to bind to the control device. It 

shows the result on the status led. 

 

8.3 Perform a factory reset

 

From the status screen (see 7.1)  
1.  See 8.2 stap 1 t/m 4 
2.  Press and hold the button for 10 seconds. The status led shows 

white. 

3.  Release the button. The device releases its binding, resets the 

configured RH-value to the default value and restarts. The device 
will return to the binding mode. 

 

9. Technical data 

9.1

 

Dimensions

 

 

 

Overall dimensions (h x b x d)

 

100 x 100 x 25 mm

 

 

Weight

 

+- 125g

 

9.2

 

Ambient conditions

 

 

 

Operation temperature range

 

0 tot 40 °C

 

 

Shippen & storage temperature range

 

-20 tot 55 °C

 

 

Relative humidity

 

0-90%, non-condensing

 

 

Ingress protection (IEC60529)

 

IP30

 

9.3

 

Battey specifications

 

 

 

Type

 

AA-battery 2x

 

 

Battery lifetime

 

2 years

 

9.4

 

Wireless connections specs.

 

 

 

Communication frequency

 

868.3 MHz

 

 

Output power

 

At least 0dBm

 

 

 

You are not allowed to 
use the device outside 
of Europe

 

9.5

 

RH measurements specs

 

 

 

Measurement range

 

0-100% RH 

 

Measurement accuracy

 

• 

at 11-89% RH

 

• 

at 0-10% RH

 

 

3% RV

 

7% RV

 

 

Measurement resolution

 

1% RV

 

 

Measurement stability

 

1.5% RH over 5 years

 

 

 

 

Status led

 

mode leds

 

 

 

 

 

 

Eco

   

Configuration

 

 

 

 

 

 

 

Step 1

 

Low fan speed

 

Off

 

*

   

 

 

 

Medium fan speed

 

 

*

 

 

 

 

High fan speed

 

 

 

*

   

 

Binding

 

 

 

 

 

Step 2

 

Value

 

Blue/red

 

Low fan speed

 

Off

 

10%

 

20%

 

30%

 

40%

 

Blue/green

 

Medium fan speed

 

30%

 

40%

 

50%

 

60%

 

70%

 

Red/green/ 
blue

 

High fan speed

 

60%

 

70%

 

80%

 

90%

 

100%

 

Red/green

 

Binding

 

 

 

 

 

 