background image

13

EN

6.   INSTRUCTION FOR REPAIRING APPLIANCES 

CONTAINING REFRIGERANT R290

1.  Checks to the area 

Prior to beginning work on systems containing flammable refrigerants, safety checks are 

necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating 

system, the following precautions shall be complied with prior to conducting work in the 

system. 

Work procedure

Work shall be undertaken under a controlled procedure so as to minimize the risk of a 

flammable gas or vapor being present while the work is being performed.

2.  General work area

All maintenance staff and others working in the local area shall be instructed on the nature 

of work being carried out. Work in confined spaces shall be avoided. The area around the 

workspace shall be sectioned off. Ensure that the conditions within the area have been 

made safe by control of flammable material.

3.  Checking for presence of refrigerant

The area shall be checked with an appropriate refrigerant detector prior to and during 

work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that 

the leak detection equipment being used is suitable for use with flammable refrigerants, 

i.e. nonspeaking, adequately sealed or intrinsically safe. 

4.  Presence of fire extinguisher

If any work is to be conducted on the refrigeration equipment or amy associated parts, 

appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or 

CO

2

 fire extinguisher adjacent to the charging area.

5. No ignition sources

No person carrying out work in relation to a refrigeration system which involves exposing 

any pipe work that contains or has contained flammable refrigerant shall use any sources 

of ignition in such a manner that it may lead to the risk of fire or explosion. All possible 

ignition sources, including cigarette smoking, should be kept sufficiently far away from the 

site of installation, repairing, removing and disposal, during which flammable refrigerant 

can possibly be released to the surrounding space. Prior to work taking place, the area 

around the equipment is to be surveyed to make sure that there are no flammable hazards 

or ignition risks.”No Smoking” signs shall be displayed. 

6. Ventilated area

Ensure that the area is in the open or that it is adequately ventilated before breaking into 

the system or conducting any hot work. A degree of ventilation shall continue during the 

period that the work is carried out. The ventilation should safely disperse any released 

refrigerant and preferably expel it externally into the atmosphere.

7. Checks to the refrigeration equipment 

Where electrical components are being changed, they shall be fit for the purpose and 

to the correct specification. At all times the manufacturer’s maintenance and service 

guidelines shall be followed. If in doubt consult the manufacturer’s technical department 

for assistance.

Summary of Contents for SMR-25L

Page 1: ...USER S MANUAL DEHUMIDIFIER ENGLISH MODEL SMR 25L...

Page 2: ......

Page 3: ...PONENTS DIAGRAMS PARTS NAMES 7 5 OPERATING INTRODUCTION HOW TO OPERATE 8 5 1 TOUCH KEY AND THE DISPLAY PANEL 8 5 2 THE NAME AND FUNCTION OF TOUCH KEY 8 5 3 INDICATIONS 10 5 4 CONTINUOUS DRAINAGE 11 5...

Page 4: ...if children operate Never disassemble the unit and never try to carry out repair or replace the unit s spare parts by yourself Please let the professional person to repair the machine 5 Place the mac...

Page 5: ...tance between the unit and the wall or other obstacles from all sides as below requirement 17 This appliance can be used by children aged from 8 years and above and persons with reduced physical senso...

Page 6: ...be result 2 ADDITIONAL WARNINGS FOR APPLIANCES WITH R290 REFRIGERANT refer to the nameplate for the type of refrigerant used l REFER TO THE USER S MANUAL PRIOR TO USING THIS APPLIANCE l R290 refrigera...

Page 7: ...7 EN 4 COMPONENTS DIAGRAMS PARTS NAMES Display Panel Water Tank Handle Infrared detection head Touch Button Air Deflector Intake Continuous Drainage Hose...

Page 8: ...omatically stop while the fan will continue to operate Continuous fan operation contributes to energy savings as the device identifies the relative humidity of the area allowing the compressor to oper...

Page 9: ...full regardless the room humidity Press the Continue button for 5 seconds and the control panel will show the evaporator temperature for 2 seconds and the ambient temperature for 3 seconds Tips adjus...

Page 10: ...oil and avoid creating mildew After 90 minutes the Inner Dry function will end and the device will shut down 5 3 Indications Bucket Full Indicator The indicator Full Water Tank will show up when the b...

Page 11: ...ection In order to extend the compressor s lifetime there is a 5 minutes delay after the compressor s last operation for the compressor to start operating again High and Low temperature protection Whe...

Page 12: ...eakage A0 The device tipped over or is placed on a surface with high inclination Unplug the device and place it on a leveled surface Plug in the device and turn it off In the event of any of the above...

Page 13: ...associated parts appropriate fire extinguishing equipment shall be available to hand Have a dry powder or CO2 fire extinguisher adjacent to the charging area 5 No ignition sources No person carrying...

Page 14: ...shall be located at the most critical point to warn of a potentially hazardous situation Particular attention shall be paid to the following to ensure that by working in electrical components the casi...

Page 15: ...gas evacuate purge again with inert gas open the circuit by cutting or brazing The refrigerant charge shall be recovered into the correct recovery cylinders The system shall be flushed with OFN to ren...

Page 16: ...be labeled stating that it has been de commissioned and emptied of refrigerant The label shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammab...

Page 17: ...pment containing flammable refrigerants Determined by local regulations 20 Discarded appliances supplies flammable refrigerants See National Regulations 21 Storage of equipment appliances The storage...

Page 18: ...anual are for explanatory purposes only The actual shape of the unit you purchased may be slightly different but the operations and functions are the same The company may not be held responsible for a...

Page 19: ...tor l Fill all the fields as shown below once the warranty submission has been completed a confirmation message will be sent to your email Full Name Address Postal Code Phone Number E mail Unit Type S...

Page 20: ...20 GR 1 21 2 R290 23 3 24 4 25 5 26 5 1 26 5 2 26 5 3 29 5 4 29 5 5 30 6 R290 31...

Page 21: ...21 GR 1 1 2 3 4 5 6 7 8 9...

Page 22: ...22 GR 10 11 12 13 14 15 16 17 8...

Page 23: ...23 GR 18 19 30 m 2 R290 l l To R290 95g R290 l l R290 R290...

Page 24: ...24 GR 3 1 5 C 35 C 30 RH 80 RH 2 3 4...

Page 25: ...25 GR 4...

Page 26: ...26 GR 5 5 1 5 2 POWER ON OFF POWER 3 5 24 5 POWER DRY Dry...

Page 27: ...27 GR 12 12 12 12 2 12 1 CONTINUE CON 5 2 3 AUTOMATIC HUMID 40 70 RH 5 1 5...

Page 28: ...28 GR SWING LEFT RIGHT SWING UP DOWN FAN SPEED CHILD LOCK 3 TIMER 12 INNER DRY 2 90 90 90...

Page 29: ...29 GR 5 3 FULL WATER TANK 5 10 16 C 5 4...

Page 30: ...30 GR 5 5 5 3 C 40 C 38 C 5 C LO 30 RH 32 RH HI 80 RH 80 RH HI C1 C2 C3 C4 C7 C8 0...

Page 31: ...31 GR 6 R290 1 2 3 4 CO2 5 6...

Page 32: ...32 GR 7 8 9 10...

Page 33: ...33 GR 11 12 13 O LFL 25 14...

Page 34: ...34 GR 15 16 80 17...

Page 35: ...35 GR 18 19 20 21 22...

Page 36: ...36 GR 211 300 3300 www inventoraircondition gr media library...

Page 37: ...nventor QR 2 4 mail email 5 Inventor 3 email email newsletter Inventor l link QR code https www inventoraircondition gr egiisi inventor l email A email newsletter Inventor l email A email newsletter I...

Page 38: ...NOTES...

Page 39: ......

Page 40: ...v 1 2 DEHUMIDIFIER...

Reviews: