
2.
●
B
C
D
A
Installation of connection pipe
1.
Align the center of the piping flare with the pyramidal face of relevant valve.
Screw in the flare nut by hand and then tighten the nut
with spanner and torque wrench refer to the following.
Spanner
Torque wrench
Indoor unit piping
Taper nut Piping
NOTE: Firstly connect the connection pipe to indoor unit, then to outdoor unit; pay attention
to the piping bending, do not damage the connection pipe; the joint nut couldn’t tighten too
much, otherwise it may cause leakage.
Exhausting(with A5mm hexagon wrench)
When using refrigerant of outdoor unit:
1. Tighten nuts A, B, C, D substantially.
2. Remove cover from check valve A (As show
in Fig.18)
3. Twist open core of liquid valve B with hexagon
wrench, and at the same time hold screw driver
against core of gas valve A to let gas out. After
15 seconds of exhausting and refrigerant appears,
close one-way valve and tighten bonnet.
4. Fully open cores of both liquid valve and gas valve,
tighten bonnet, then check with soap water or leakage
detector to see if there is any leaking in the joints of
piping between indoor and outdoor units.
Fig.18
Gas side
Outdoor unit
Indoor unit
Check valve
Pipe joint
Joint nut
Limited block
Bonnet
Valve sterm
One-way valve
Installation of Indoor Unit
Hex nut
Tightening torque (N.m)
Ф
9.52
Ф
16
60
~
65
35
~
40
Ф
6
15
~
20
Ф
12
50
~
55
Ф
19
70
~
75
Air discharge method
Length of connection pipe
Charge volume of additional refrigerant
Use refrigerant of
Below 5m
Volume on nameplate
Use vacuum pump
Use vacuum pump
5-15m
20-30m
outdoor unit
24K model Volume on na30g/m
48K model Volume on na100g/m
33
Summary of Contents for R2FI-50
Page 40: ...4 6 12 20 22 28 30 34 36 1 25 17 19 8...
Page 41: ...1...
Page 42: ...2...
Page 43: ...CO 3...
Page 44: ...Anti freezing 2 C 5 10 Anti cold Air 90 1 2 3 4...
Page 45: ...18 C 21 C 48 C 24 C 7 C 27 C 1 2 5 80...
Page 46: ...1 2 3 4 5 6 4 24K 6...
Page 47: ...7 48K 1 2 3 4 5 6...
Page 49: ...and 1 C 16 C 30 C 3 LC 3 1 20 5 5 2 20 5 5 1 2 and and 9...
Page 50: ...10 AUTO Auto Turbo Turbo Turbo TIMER FAN 5 1 1 5...
Page 56: ...3 SLEEP LIGHT 13 14 SLEEP LIGHT 16 1 A 2 3 1 5V 4 3 2 15 MODE F C OFF MODE C F 16...
Page 57: ...3 17 4 5 4 5...
Page 58: ...FUNC 6 18...
Page 59: ...1 2 1 2 1 2 3 FC FC 4 19...
Page 60: ...1 2 3 40 C 7 7 7 2 8 8 1 8 20...
Page 61: ...21...
Page 62: ...22 3 Waiting...
Page 63: ...23 timer Breakoff low...
Page 64: ...H1 24 E1 E3 E4 E5 F1 F2 F3 F4 F5 E1 E3 E4 E5 F1 F2 F3 F4 F5 HEAT 2 5 HEAT 10...
Page 65: ...25 O E 1 2 3 1 2 3 4 5 6 7 5 m 15 m 8 9...
Page 66: ...26 1 2 3 4 1 5 1 5 m 32A 25A 24 48 1 2 AC 3 4 5 6...
Page 67: ...27 380 415V 3N 220V 3 220V 1 2 3 4 5 6 7 8 9 10 1 2 3...
Page 68: ...200cm 28 24K 30cm 10cm 5cm 60cm 30cm 10cm 60cm 10cm 200cm...
Page 69: ...200cm 29 48K 30cm 10cm 5cm 30cm 60cm 10cm 60cm 10cm 200cm...
Page 70: ...1 2 30 11 12 10 1 9 3 2 11 1 2 3 9mm 4 12 3...
Page 71: ...13 7 1 2 14 14 31 48K 24K N L brown L1 L2 L3 N N 1 2 3 L N 4 13 5 6...
Page 72: ...32 E 2 16 17 15 100mm 15 3 16 1 1 2 90 3 4 1 2 3 1 2...
Page 74: ...When using vacuum pump 20 34 76cmHg 19 1 2 3 Lo 4 Lo 15 1 0 x 105pa 76cmHg 5 6 7 19 25 20...
Page 75: ...35 1 2 21 21 24K 48K 24K N1 2 3 L2 N L1 L3 L2 L1 N L3 L2 N L1 L3 48K...