
55
9.2.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution(P0)
Error Code
P0
Malfunction decision
conditions
When the voltage signal that IPM send to compressor drive chip
is abnormal, the display LED will show “P0” and AC will turn off.
Supposed causes
●
Wiring mistake
●
IPM malfunction
●
Outdoor fan ass’y faulty
●
Compressor malfunction
●
Outdoor PCB faulty
Trouble shooting:
Check the wiring between main PCB
and compressor
Correct the connection or replace
the wires and connectors.
Yes
No
Check the IPM
No
Yes
Replace the IPM board or replace
the main PCB
Check the outdoor fan and the
outdoor unit ventilation
No
Please refer to the solution of
【
Fan
Speed Has Been Out Of Control
】
malfunction
Yes
Check the compressor resistance
values
No
Replace the compressor.
Yes
Replace the outdoor main PCB
Summary of Contents for P6MVI-09WFR
Page 8: ...8 For P6MVI 09WFR...
Page 9: ...9 For P6MVI 12WFR For P6MVI 18WFR...
Page 10: ...10 For P6MVI 24WFR...
Page 11: ...11 3 2 Outdoor Unit...
Page 14: ...14 For P6MVO 24...
Page 16: ...16 P6MVO 09 P6MVO 12 16022000020169...
Page 17: ...17 P6MVO 18 P6MVO 24...
Page 18: ...18...
Page 25: ...25 cap to a torque of 18N m Be sure to check for gas leakage...