inVENTer Connect controller platform | Installation instructions
TROUBLESHOOTING
8
Troubleshooting
Overview
Fault
Possible cause
Remedy
Easy Connect e16 controller
Fans not working
Devices were not recognised/
paired by the controller.
Pair the device again.
Controller does not
function
Programming unit is incorrectly/not
connected.
Check wiring.
No electrical contact.
Check cables. Ensure cables are stripped
sufficiently (approx. 8.5 mm).
Indicator lights do not
light up
Faulty controller.
Replace controller.
There is no power.
Check power supply.
Connect inner cover
Fans not working
Inner cover not connected to the
controller.
Start device pairing.
Fan cable not connected.
Connect the fan cable
Indicator lights do not
light up
Inner cover faulty.
Replace the inner cover.
There is no power.
Check power supply.
LED flashes RED
Error in the system
Restart device pairing.
Sensor technology
No measured values
Sensors not paired
Start device pairing.
With: Indoor / Outdoor humidity / temperature sensor
RED LED flashes on the
Easy Connect e16
Battery level low
Change the batteries
If you cannot eliminate the fault, please contact our technical customer service. You can find infor
-
mation on how to do this in the following section (
10: Service).
List of error codes
Error code
Description
F 01
Time and date on the controller not set or not confirmed
F 02
At least one ventilation device/sensor is no longer reachable
F 03
Firmware update failed
F 04
Battery status of the Indoor/Outdoor humidity/temperature sensors is low
F 05
Switching contact triggered or switching contact is out of operation
F 06
Filter change required
F 07
Ventilation system must be cleaned